when fast deleration is disabled is around 10 seconds.
shows phase current and motor electrical
speed waveform when the motor decelerates from 100% duty cycle to 10% duty cycle. Time taken for the motor
to decelerate from 100% duty cycle to 10% duty cycle when fast deleration is enabled is around 1.5 seconds.
Please note that when fast deceleration is enabled and anti-voltage surge (AVS) is disabled, there might be
voltage spikes seen in supply voltage. Enable AVS to protect the power supply from voltage overshoots during
motor deceleration.
Phase current
Speed
Figure 4-3. Phase current and motor speed - Faster deceleration disabled
Phase current
Speed
Figure 4-4. Phase current and motor speed -Faster deceleration enabled
4.3.8 Preventing supply voltage overshoot during motor stop and deceleration
For applications that require preventing supply voltage overshoots during motor stop or deceleration, it is
recommended to follow below steps.
Preventing supply voltage overshoot during motor stop: