
AMC7834EVM Software Overview
20
SLAU608B – December 2014 – Revised May 2016
Copyright © 2014–2016, Texas Instruments Incorporated
AMC7834 Evaluation Module
5.2.5
AMC7834EVM ALARMS Page
The AMC7834
provides access to the programmable out-of-range alarms for the internal
and external temperature sensors, the DAC internal monitoring channels, and the bipolar DAC outputs.
displays the ALARMS Page of the AMC7834EVM. The page displays the name of each alarm,
shown under the
Alarm Name
column, and provides information such as the
Value
,
High Limit
,
Low Limit
,
and
Alarm Status
, with additional options.
Figure 23. ALARMS Page
To use the page, the ADC channel, Temperature Sensors, or bipolar DACs should be enabled in their
respective ADC and DAC page of the GUI. This is achieved by enabling the appropriate channel’s mux.
Once the channels are active, the
Low Limit
and
High Limit
fields are available for edit (see
Figure 24. Low Level Configuration Page
The
Write Settings
button is used to write the values from the
Low Limit
and
High Limit
fields into the
device. The
Read Alarm
button is used to read the state of the active channels. When an alarm is
triggered, the Alarm Status displays the text
Tripped
in red. If the channel values are within the range of
the alarm thresholds, the status displays
No Alarm
in black text.
displays the ADC Channel False Alarm protection, CH-FALR, drop-down list, which contains
integer values that are related to the consecutive number of samples required for the alarm to activate.
The lists defaults to 16 consecutive samples, therefore requiring 16 conversions with an over-range value
before the alarm is triggered. The temperature sensing inputs also have their respective False alarm
protection. The lists for these inputs default to 4 consecutive samples before the alarms are triggered.