background image

 

Chapter 8 – Maintenance 

 

 

TestEquity 1016C-1027C Temperature Chamber 

Page 8-11

 

Refrigeration System Charging Instructions 

 

!

 

WARNING:

  Repair of the refrigeration system must be performed only by a properly 

trained mechanic who is experienced in repairing cascade refrigeration 

systems. Do NOT substitute any component. Do NOT substitute refrigerants. 

Improper repairs will void the warranty. 

 

These instructions are intended as guidelines for repairing TestEquity chambers. Details such as 

how to attach a gauge manifold are not covered. These are NOT do-it-yourself instructions! 

 

R-404A High-Stage Charge 

TestEquity does NOT recommend charging the system by relying on a clear sight glass only. 

Although a clear sight glass generally means the system is fully charged, it can be misleading. 

For example, if the system is charged on a cool day or with an empty chamber, it could be 

undercharged for hot days or with a heavy load. The proper charging procedure is as follows: 

 

1.

 

Repair any leaks before recharging. 

2.

 

Attach a vacuum pump and manifold gauge to the suction and discharge ports.  

3.

 

Evacuate the system to at least 100 microns. DO NOT GUESS! You must use a micron 

gauge. 

4.

 

Use a charging scale to weigh in 80 ounces (5 pounds) of R-404A. 

5.

 

Verify the cooling performance as outlined in “How to verify the chamber performance”. 

 

NOTE: If the Temperature Controller is cycling (Cool Light cycles on/off), the sightglass may 

appear 1/2 to 2/3 full. This is normal. 

 

R-508B Low-Stage Charge 

 

1.

 

Repair any leaks before recharging. 

2.

 

Attach a vacuum pump and manifold gauge to the suction, discharge, and expansion tank 

ports. Attaching to the expansion tank is very important because it is otherwise very difficult 

to evacuate the tank through the pressure regulator or capillary tube that is connects it to the 

system. 

3.

 

Evacuate the system to at least 100 microns. Do NOT guess! You must use a micron gauge. 

4.

 

Do NOT put any additives in the system. Pentane is NOT necessary or desirable. 

5.

 

Charge the system until the standby pressure is 130 PSIG. Allow time for the charge to 

equalize as read on the suction and discharge gauges. This is 10 PSIG higher than the target 

amount of 120 PSIG. See NOTE below. 

6.

 

Verify the cooling performance as outlined in “How to verify the chamber performance”. 

 

NOTE:  

If the low-stage has been evacuated and recharged, the standby pressure should be 

rechecked after 24 hours to make sure it is 120 PSIG. This is because the refrigerant mixes with 

the POE oil in the compressor, causing a lower standby pressure than was initially observed. Do 

not mistake this initial loss of pressure with a leak. After verifying that there is no leak, you may 

need to top-off the charge if the pressure is too low. 

Summary of Contents for 1016C

Page 1: ...1027C Temperature Chamber 1016C all serial numbers 1027C serial number 50625 and above Operation and Service Manual TestEquity LLC 6100 Condor Drive Moorpark CA 93021 Support 877 512 3457 Toll Free 80...

Page 2: ......

Page 3: ..._______________________________________________________________________ 3 2 COOL Light __________________________________________________________________________ 3 2 Loading the Chamber ______________...

Page 4: ..._________________________________________________ 8 5 Theory of Operation______________________________________________________________8 7 Troubleshooting _____________________________________________...

Page 5: ...30 C 85 F or below 16 C 60 F ambient room temperature is NOT recommended CAUTION The Input Voltage label on the back of the chamber indicates the input voltage configuration as shipped from the factor...

Page 6: ...n Do not attempt to modify the setup values unless you thoroughly understand what you are doing The correct values are documented in the EZ Zone Limit Controller Setup Parameters section of this manua...

Page 7: ...need to open the door while the chamber is operating wear safety goggles to prevent the high velocity airflow from blowing particles or objects into your eyes WARNING This chamber operates at extreme...

Page 8: ......

Page 9: ...t the electrical compartment b Inspect the refrigeration machinery compartment c Check the low stage refrigeration charge e Verify the chamber performance Installation Location The chamber will produc...

Page 10: ...onfiguration This chamber can be easily configured for operation from a 208 V 60 Hz or 230 V 60 Hz 3 Phase nominal input Other input voltages and 50 Hz operation are available as special options and a...

Page 11: ...nch circuits on the load side of the Main Disconnect Switch are individually fused However your local electrical code may require a separate disconnect switch within sight of the chamber Power Source...

Page 12: ......

Page 13: ...details on how to use the Temperature Controller CAUTION This chamber has a crankcase heater to protect the high stage compressor The chamber must be connected to the power source AND the Main Disconn...

Page 14: ...re ensures the longest possible life for the high stage compressor if the chamber has been removed from the power source for more than 24 hours CONDITIONING Switch ON Mode The CONDITIONING Switch enab...

Page 15: ...nd surfaces that are hot or cold to prevent severe burns or frostbite Protective gloves are recommended CAUTION If your test sample is energized it may be capable of raising the workspace temperature...

Page 16: ...during low temperature operation or water when maintaining over 0 C and cooling is required To avoid moisture condensation make sure the port plugs are inserted at all times Also avoid opening the cha...

Page 17: ...and is written by the manufacturer Watlow for a wide variety of applications and configurations Not all features or functions are applicable Only the capabilities of a model PM6L1AJ AAAABAA are appli...

Page 18: ...han your actual chamber temperature set point to prevent nuisance tripping 5 Press the RESET Key to return to the Home Page 6 The upper display will show the actual chamber temperature while the lower...

Page 19: ...t can be used to remove power to your test sample if the Limit Controller s temperature limits are exceeded The safety contacts are rated as follows Resistive 10 A 250 VAC or 10 A 28 VDC Inductive 7 A...

Page 20: ......

Page 21: ...Connect the hose from the Dry Air system to the fitting which is designated PURGE on the rear panel Connect a supply of compressed air to the 3 8 inch FPT shutoff valve of Dry Air system Connect the...

Page 22: ......

Page 23: ...nstallation be determined by a qualified electrician who is familiar with industrial plant wiring I need to send the chamber outside North America Will it work with their power Outside North America m...

Page 24: ...the temperature set point may be 25 0 C The actual temperature varies between 25 4 C and 24 5 C This corresponds to 0 4 C and 0 5 C or a total of 0 9 C of RELATIVE variations These specifications are...

Page 25: ...ssor if the chamber has been removed from the power source for more than 24 hours Can the person who services our air conditioning also service the chamber Probably not Most air conditioning mechanics...

Page 26: ......

Page 27: ...Time Cool Down Example empty From 85 C to 40 C 125 C 23 min 5 4 C min Heat Up Example empty From 40 C to 85 C 125 C 15 min 8 3 C min Input Power Requirements 230 V 10 60 Hz 3 PH Max Current Draw 39 A...

Page 28: ...e empty From 85 C to 40 C 125 C 28 min 4 46 C min Heat Up Example empty From 40 C to 85 C 125 C 17 min 7 35 C min Input Power Requirements 230 V 10 60 Hz 3 PH Max Current Draw 39 A Recommended Service...

Page 29: ...aintenance Intervals Daily or As Needed Clean chamber interior and exterior Listen for abnormal noise or vibration Every 3 Months Inspect the door seal Inspect the refrigeration machinery compartment...

Page 30: ...gnize changes from normal operating noises can be a valuable way to identify problems and prevent further damage Examples of noises to be aware of include Circulator motor and fan noises with compress...

Page 31: ...wo low stage gauges marked R 508B on the left side of the rear of the chamber 3 The two gauges have different scales However they should read the same value of pressure This indicates that the system...

Page 32: ...tes 5 The chamber temperature should slowly increase and stabilize to 85 C It should NOT overshoot beyond 85 C by more than a few tenths of a degree and the compressors should NOT need to turn ON in o...

Page 33: ...seldom goes out of calibration If you try to calibrate the instrumentation before determining that calibration is necessary you may make it worse if done incorrectly Variations in temperature through...

Page 34: ...er For the F4T Controller If calibration of the temperature controller is necessary refer to the F4T Touch Screen Controller User s Guide For the F4 Controller If calibration of the temperature contro...

Page 35: ...w temperature safety limits are exceeded TCR2 turns off CR3 which turns off C1 PCR1 will disable CR1 if the input power phase sequence is incorrect Cooling is accomplished by a cascade refrigeration s...

Page 36: ...cuum The hot gas regulator is adjusted to keep the suction pressure at 8 PSIG when SV1 is OFF This is also called bypass mode The temperature controller alternately cycles SV2 and SV1 through cool rel...

Page 37: ...SR2 is defective Heater is shorted to chassis Does not cool at all 1 If F4T upper PWR bar is 100 F4 controller light 1B is ON F4T Compressor Output F4 DigitalOut 8 is ON the Cool light on front panel...

Page 38: ...pped from TestEquity and only occurs in cool mode 1 Re enter values as shipped from TestEquity 2 Control parameters may need to be changed for your unique test conditions 3 Control parameters may need...

Page 39: ...g performance as outlined in How to verify the chamber performance NOTE If the Temperature Controller is cycling Cool Light cycles on off the sightglass may appear 1 2 to 2 3 full This is normal R 508...

Page 40: ...ing out of service for even one day then you should purchase critical spare parts in advance Although most parts are standard and available from a variety of local distributors some parts are either h...

Page 41: ...1 200023 1 ea Switch ON OFF ON Carlingswitch RC911 RA B 0 N XLR1 SW2 200275 1 ea F4 Temperature Controller Watlow F4SH CKA0 01AE TCR1 200001 1 ea F4T Temperature Controller Watlow F4T1L2EAA2E1017 TCR1...

Page 42: ...ion Valve Suction Cool LS Sporlan SBFS B ZP 3 8 x 5 8 odf 26 100507 1 ea Filter Drier Sporlan C 083 S 4 100070 2 ea Gauge 0 x 400 PSIG Pressure Miljoco CUSTOM 13 100495 2 ea Gauge 30 x 200 PSIG Compou...

Page 43: ...Sd Limit Sides both Alt high High only or LoW Low only L hY Limit Hysteresis 2 Change not recommended A ty Alarm Type oFF Do Not Change PAr1 Upper Display ACPu Alt none PAr2 Lower Display Lst Alt Lh...

Page 44: ......

Page 45: ...r labor if they initiate service on their own without prior approval from TestEquity Replacement parts must be supplied by TestEquity for in warranty claims Purchaser will not be reimbursed for parts...

Page 46: ......

Page 47: ...Chapter 11 Drawings TestEquity 1016C 1027C Temperature Chamber Page 10 1 Chapter 10 Drawings...

Page 48: ......

Page 49: ...P CC 20 LP CC 20 Main Disconnect Switch DSW TB1 TB2 Control Transformer TR1 F1 F2 F7 F8 C1 C2 SSR2 SSR1 CR1 CR3 FNM 3 F3 F9 F4 F5 F6 PCR1 F10 F11 C3 F12 SSR4 TM1 SSR3 TB2 Terminals H1 H2 H3 G G G TB1...

Reviews:

Related manuals for 1016C