33
INV L1-L2-L3 phase status codes
178
Inverter stopped but on inverter L1 phase output still DC voltage sensed
278
Inverter stopped but on inverter L2 phase output still DC voltage sensed
378
Inverter stopped but on inverter L3 phase output still DC voltage sensed
179
During inverter run at last 25 milliseconds the L1 phase output alternance is not changed
279
During inverter run at last 25 milliseconds the L2 phase output alternance is not changed
379
During inverter run at last 25 milliseconds the L3 phase output alternance is not changed
180
At the end of 4 times retry During soft start after 4 seconds still the L1 phase output voltage is
less then 30 volts AC
280
At the end of 4 times retry During soft start after 4 seconds still the L2 phase output voltage is
less then 30 volts AC
380
At the end of 4 times retry During soft start after 4 seconds still the L3 phase output voltage is
less then 30 volts AC
181
At the end of 4 times retry During soft start at the end of 4 seconds L1 output voltage is bigger
then (output high/2) value
281
At the end of 4 times retry During soft start at the end of 4 seconds L2 output voltage is bigger
then (output high/2) value
381
At the end of 4 times retry During soft start at the end of 4 seconds L3 output voltage is bigger
then (output high/2) value
182
During power on L1 phase bypass SCR must be off but at the L1 phase output there is AC
voltage
282
During power on L2 phase bypass SCR must be off but at the L2 phase output there is AC
voltage
382
During power on L3 phase bypass SCR must be off but at the L3 phase output there is AC
voltage
183
L1 phase by-pass SCR must be on but there is only positive alternance at the UPS output
283
L2 phase by-pass SCR must be on but there is only positive alternance at the UPS output
383
L3 phase by-pass SCR must be on but there is only positive alternance at the UPS output
184
L1 phase by-pass SCR must be on but there is only negative alternance at the UPS output
284
L2 phase by-pass SCR must be on but there is only negative alternance at the UPS output
384
L3 phase by-pass SCR must be on but there is only negative alternance at the UPS output
185
L1 phase by-pass SCR must be on but there is no output voltage at the UPS output
285
L2 phase by-pass SCR must be on but there is no output voltage at the UPS output
385
L3 phase by-pass SCR must be on but there is no output voltage at the UPS output
186
Output CB is energized but at the L1 phase output there is only positive alternance
286
Output CB is energized but at the L2 phase output there is only positive alternance
386
Output CB is energized but at the L3 phase output there is only positive alternance
187
Output CB is energized but at the L1 phase output there is only negative alternance
287
Output CB is energized but at the L2 phase output there is only negative alternance
387
Output CB is energized but at the L3 phase output there is only negative alternance
188
Output CB is energized but at the L1 phase output there is no AC voltage
288
Output CB is energized but at the L2 phase output there is no AC voltage
388
Output CB is energized but at the L3 phase output there is no AC voltage
189
During load on by-pass on the L1 output short circuit sensed
289
During load on by-pass on the L2 output short circuit sensed
389
During load on by-pass on the L3 output short circuit sensed
190
On L1 phase output reverse current sensed
290
On L2 phase output reverse current sensed
390
On L3 phase output reverse current sensed
191
During load on inverter ,on L1 phase by-pass line leakage current sensed
291
During load on inverter ,on L2 phase by-pass line leakage current sensed
391
During load on inverter ,on L3 phase by-pass line leakage current sensed
Summary of Contents for DS300S Series
Page 1: ...DS300S SERIES DSP Controlled UPS 10 15 20 kVA 3 Phase In 3 Phase Out USER MANUAL...
Page 2: ......
Page 17: ...14 Figure 2 3 External Battery Connections 60x12V 30x12V Batteries 30x12V Batteries...
Page 18: ...15 Figure 2 3a DS300S Series 10 15 20 KVA Internal Battery Connections 60x12V 5Ah...
Page 19: ...16 Figure 2 3a DS300S Series 10 15 20 KVA Internal Battery Connections 60x12V 7 9Ah...
Page 56: ......
Page 57: ...AGKK10621 10 2021...