8
1.4 Technical Specifications
MODEL
DS3100HT
DS3120HT
DS3160HT
Output (KVA)
100 kVA
120 kVA
160 kVA
Output (KW)
90 kW
108 kW
144 kW
Output Power Factor
0,9
INPUT
Number of Phases
3 Phase + Neutral
Input Voltage
220/380, 230/400 or 240/415 Vac
Input Voltage Tolerance
+20% , -25% (+15% at 240/415Vac)
Input Power Factor (PF)
0,98 - 0,99 (at full load)
Input THDI
<= 5% (at full load)
Input Frequency
50/60 Hz.
±
10%
By-pass Voltage
220/380, 230/400 or 240/415 Vac 3 Phase + Neutral
By-pass Frequency
50 Hz.
±
2%
RFI Level
EN62040-2
OUTPUT
Number of Phases
3 Phase + Neutral
Output Voltage
220/380, 230/400 or 240/415 Vac
Output Voltage Tolerance
±
1%
Output Frequency
50/60 Hz
Output Frequency Tolerance (Synchronous)
±
2%
Output Frequency Tolerance (Battery)
±
0,1% (free/battery operation mode)
Efficiency (100% Load)
up to 94%
Load Crest Factor
3:1
Output Voltage THD (linear load)
<=2%
Overload
125% Load 10min. , 150% Load 1min.
BATTERY
Total Number
56 blocks 12V (2x28 serial 56 batteries, external)
Float Charge Voltage (25
0
C)
±
378V DC
End of Discharge Voltage
±
280V DC
Battery Test
Automatic and Manual
Boost Charge
Available
COMMUNICATION INTERFACES
RS232 Com Port
2 each standard (COM1 and COM2)
External Temperature Measurement Input
Available (standard)
RS485 Comm. Port
Optional
Remote Monitoring Panel
Optional
SNMP Adapter
Optional
Modbus Adapter
Optional
Alarm Relay Contacts
4 each dry contacts (function programmable) 8 optional
Digital Inputs
2 each optional
Emergency Power-Off Input
Available (standard)
ENVIRONMENT
Operating Temperature
0 – 40
0
C
Operating Humidity
<= %90 (non-condensing)
Acoustic Noise
< 68 dB
Dimensions (WxDxH) (mm)
825 x 855 x 1770
Device Type and Protection Class
Class 1 – IP20