856 Status code
Status
Inverter warning
Description
UPS is currently in SLAVE mode ,MASTER function transferred to another UPS
Restart
--
Returning to fault
--
857 Status code
Status
Inverter warning
Description
In parallel system there is no MASTER communication packages ,output switch
turned on after 2 seconds MASTER mode started
Restart
--
Returning to fault
--
858 Status code
Status
Inverter warning
Description
In parallel system there is no MASTER communication packages ,output switch
turned on after 2 seconds MASTER mode started during on bypass
Restart
--
Returning to fault
--
859 Status code
Status
Inverter alarm
Description
In parallel system transfer the load to maintenance bypass command received
Restart
--
Returning to fault
--