Line Interactive UPS 

                                                                400/600/800 VA 

 

This UPS utilizes voltage that may be hazardous. Do not 
attempt to disassemble the unit.    The unit contains no user 
replaceable parts.    Only factory service personnel may 
perform repairs. 

 

This pluggable type A equipment with battery already installed 
by the supplier is operator installable and may be operated by 
laymen. 

 

The mains socket outlet that supplies the UPS shall be 
installed near the UPS and shall be easily accessible. 

 

During the installation of this equipment it should be assured 
that the sum of the leakage currents of the UPS and the 
connected loads does not exceed 3.5mA. 

 

Connection to any other type of receptacle other than a 
two-pole, three-wire grounded receptacle may result in shock 
hazard as well as violate local electrical codes. 

 

In the event of an emergency, press the "OFF" button and 
disconnect the power cord from the AC power supply to 
properly disable the UPS. 

 

Do not allow any liquids or any foreign object to enter the 
UPS.    Do not place beverages or any other liquid-containing 
vessels on or near the unit. 

 

This unit intended for installation in a controlled environment 
(temperature controlled, indoor area free of conductive 
contaminants). Avoid installing the UPS in locations where 
there is standing or running water, or excessive humidity. 

 

Do not plug the UPS input into its own output. 

 

Do not attach a power strip or surge suppressor to the UPS. 

 

Do not attach non-computer-related items, such as medical 
equipment, life-support equipment, microwave ovens, or 
vacuum cleaners to UPS. 

 

 

Install the UPS in a protected area that is free of excessive dust 
and has adequate air flow. Place the UPS away from other units at 
least 20 cm to avoid interference. For best performance, keep the 
indoor temperature between 0

°

 C and 40

°

 C. 

 

All connected equipment should be turned off, then disconnect 
from the UPS to avoid battery drain. Unplug the UPS from the wall 
outlet. Then turn off the UPS for storage.    Store the UPS unit 
covered and upright in environments where the ambient 
temperature is -20 C to 50 C with its battery fully charged. 

 

MODEL 

400 

600 

800 

CAPACITY 

400VA/240W 

600VA/360W 

800VA/480W 

Input Voltage 

110/120 VAC 

Input Voltage Range 

85-145 VAC 

Output Voltage   
Regulation   

±

  10 % (Bat. mode) 

Transfer Time   

Typical 2-6 ms 

Waveform 

Simulated Sine Wave 

Battery Type 

12V/4.5Ah 

12V/7Ah 

12V/9Ah 

Battery Number 

Charging Time 

6 hours recover to 90% capacity 

Dimension (DxWxH) 

279 x 101 x 142 

Net Weight (kgs) 

3.55 

4.25 

4.9 

Humidity 

0-90% RH @ 0-40

°

C (non-condensing) 

Noise Level 

Less than 40dB 

*Specifications are subject to change without notice. 

  Do not dispose of batteries in a fire as they may explode. 

  A battery can present a risk of electrical shock and high short 

circuit current.    The following precautions should be observed 
when working on batteries: 

1) Remove watches, rings, or other metal objects from the hands. 
2) Use tools with insulated handles. 
3) Wear rubber gloves and boots. 
4) Do not lay tools or metal parts on top of batteries. 
5) Disconnect charging source prior to connecting or 

dis-connecting batteries terminal. 

  Internal battery voltage is 12VDC.Sealed, lead-acid, 6-cell 

battery. 

  Servicing of batteries should be performed or supervised by 

personnel knowledgeable of batteries and the required 
precautions.    Keep unauthorized personnel away from 
batteries. 

  When replacing batteries, replace with the same number and 

type of sealed lead-acid battery. 

  Do not open or mutilate the battery or batteries.    Release 

electrolyte is harmful to the skin and eyes.    It may be toxic. 

  Attention, hazardous through electric shock. Also with dis- 

connection of this unit from the mains, hazardous voltage still 
may be accessible through supply from battery. The battery 
supply should be therefore disconnected in the plus and minus 
pole at the connectors of the battery when maintenance or 
service work inside the UPS is necessary. 

  To reduce the risk of overheating the UPS, do not cover the 

UPS' cooling vents and avoid exposing the unit to direct 
sunlight or installing the unit near heat emitting appliances such 
as space heater or furnaces. 

  Unplug the UPS prior to cleaning and do not use liquid or spray 

detergent. 

 

Problem 

Possible Cause 

Solutions 

LED not lit. 

The UPS is not on. 

Press the power switch 
again to turn on the UPS. 

Battery  voltage  is  too 
low. 

Charge the battery at least   
6 hours. 

Battery fault. 

Replace the battery. 

The UPS 
always on 
battery mode. 

Power cord loose. 

Re-plug the power cord. 

The UPS 
continuously 
beeps. 

Overload. 

Remove some unnecessary 
loads. Before reconnecting 
equipment, please verify 
that the load matches the 
UPS capability specified in 
the specs. 

Backup time 
too short. 

Battery voltage is too 
low. 

Charge the battery at least   
6 hours. 

Overload. 

Remove some unnecessary 
loads. Before reconnecting 
equipment, please verify 
that the load matches the 
UPS capability specified in 
the specs. 

Battery defect. 

Replace the battery. 

If any abnormal situations occur that are not listed above, please 
call for service immediately. 

SAVE THESE INSTRUCTION-This manual contains important instructions that should be followed 

during installation and maintenance of the UPS and batteries. 