Replacing the Filters 

The Room-Side Replaceable FFU is designed so that the HEPA or ULPA filter can be 

replaced from inside the cleanroom without breaching the controlled environment. The 

filter assembly is separate from the fan module, which stays in place in the ceiling grid. 

Follow these instructions to replace the filter. 
A)

 

First, you must remove the stainless steel screen covering the filter that is held in 

place with friction catches (Photo 1). This screen protects the filter from damage 

and enhances airflow uniformity.  

 

Photo 1

: Friction catches hold the screen to the fan module housing. 

 

B)

 

Next, rotate the metal tabs that help hold the HEPA filter in place (see Photo 3).  

    

Photo 3

: Filter-face grille’s metal tabs. 

C)

 

Gently let the used filter drop down, and set aside. The filter assembly is 

surrounded by a channel containing gel seal. Wipe any residual gel from the 

knife-edge of the fan module still in the ceiling to prepare for the replacement 

filter. Position your new filter carefully before pushing into place; the knife-edge of 

the fan module should be centered in the channel (equal amounts of gel on both 

sides). Photo 4 shows the gel-filled channel of the RSR filter.  

 

Photo 4

: Gel-filled channel of RSR filter. 

D)

 

Rotate the metal tabs so that they lock in the new HEPA filter. 

 

E)

 

Reinstall the stainless steel screen by pushing up on the friction catches until the 

screen clicks into place. 

 

 

F)

 

To replace the pre-filter located at the top of the fan module, slide the old filter out 

of the two tracks holding it in place on top of the FFU and then slide in the new 

pre-filter. 

 

Summary of Contents for RSR ECM

Page 1: ... configurations with other products systems such as ductwork or hoods 2 0 Operation The unit consists of a 1 3 HP electronically commutative motor driving a forward curved centrifugal impeller Air is drawn into the unit through a pleated pre filter and in turn to an insulated chamber where it is then directed to an exit HEPA filter with a built in diffuser The unit can also be equipped with a 3 8 ...

Page 2: ...he screen to the fan module housing B Next rotate the metal tabs that help hold the HEPA filter in place see Photo 3 Photo 3 Filter face grille s metal tabs C Gently let the used filter drop down and set aside The filter assembly is surrounded by a channel containing gel seal Wipe any residual gel from the knife edge of the fan module still in the ceiling to prepare for the replacement filter Posi...

Page 3: ...nimum 60 RPM measured Industry Standard MODBUS Networking RTU Protocol RS485 9600 8 n 1 6 2 Control Modes The EC Motor Control Card offers three different control modes for operating the FFU MODBUS RTU networking 0 10 VDC analog control or manual control through an onboard potentiometer Manual Control Mode The onboard potentiometer can be manually adjusted at the EC Motor Control Panel using a Phi...

Page 4: ...ble is removed 9 0 Control Card Electrical Specifications Electrical Ratings Input Voltage AC 50 60Hz 12 28V1 AC Input Voltage DC 14 30V DC Operating Current AC 35 mA AC Operating Current DC 30 mA DC Accessory Current 5V 10V 503 mA DC Accessory Current V RFU2 1003 mA DC 1 Refers to actual AC voltage values 2 V RFU is rectified and capacitive filtered but is unregulated 3 Maximum current values sta...

Page 5: ...separately For Terra s Policy and Procedures for Returning Goods see Terra s Internet site www TerraUniversal com Generally customers can improve the chance of collecting on a freight claim by following these procedures 1 formally requesting that the carrier inspect the shipment immediately upon suspecting damage or shortage to verify condition 2 notifying the carrier upon discovery of concealed d...

Reviews: