Terofire Products
12
Alarm Zone Wiring Diagrams
The alarm zones are wired as in the diagram below. A 10k end of line
resistor must be fitted at the end of the circuit. Motorised fire bells may
be used, but solenoid bells MUST NOT be connected to the panel.
Some electronic sounders have a choice of tones available. Please see
the sounder instructions for further information.
brownblackorange gold
The colour bars on a 10k resistor are
Attaching a relay to an alarm zone.
Alarm Zone +
Alarm Zone -
C1
C2
NO1
NO2
NC1
NC2
A relay may be connected
anywhere on the alarm zone
wiring, as long as two diodes
(1N4001 or equivalent) are fitted
as shown in the diagram. The
end of line resistor is not shown
here, but must be connected at
the end of the alarm zone wiring.
The relay must have a 24V DC
coil.
+ in/out
+ in/out
- in/out
- in/out
10k
EOL
Alarm
Zone +
Alarm
Zone -