4
PC Unit Mounting Procedure
Please attach PC unit in front connected breaker.
◯
1
Removal of I,J and K
<
For E125,S125,E250,S250
> <
For H125,L125,H250,L250
>
J K
3P:6pcs 3P:3pcs
4P:8pcs 4P:4pcs
L
3P:3pcs
4P:4pcs
◯
2
Removal of M (for H125,L125,H250,L250)
◯
3
Removal of N (for H125,L125,H250,L250)
◯
4
◯
6
Cleaning
◯
7
Insert
◯
8
Check contact state
◯
9
Tightening
M6
×
16
E
4.60
~
5.98N
・
m
M6
×
20
F
4.60
~
5.98N
・
m
◯
5
Mount the carrier B or C to rear side of breaker.
M4
×
16
D
1.0
~
1.7N
・
m
Before mounting the carrier ,make sure that the breakers are in the
I (ON) position.
◯
10
Stick the sticker G on the breaker body.
□
5
Operation check
◯
1
Turn ON the breaker and measure distance O.
◯
2
Turn OFF the breaker and measure distance O.
◯
3
Turn ON the breaker and measure distance P.
◯
4
Turn OFF the breaker and measure distance P.
O
P
ON
Min. 100 (mm)
O OFF
Max. 94 (mm)
ON 12.7-13.3
(mm)
P
OFF
9.7-10.3 (mm)
OPEN THE MCCB
BEFORE MOUNTING
OR REMOVING.
MCCBをOFFにして
取付け・取外し下さい。
3㎜
4㎜
B or C
D
3P : 6pcs
4P : 8pcs
M
3P : 6pcs
4P : 8pcs
N
E or F
⑨
⑥
⑦
⑥
⑧
(for E125,S125,E250,S250)
(for H125,L125,H250,L250)
A
G