It is recommended cable shoes to be used. The fire detector is placed on the base (fig.1,pos.1). It is 
rotated clockwise until reaching the guiding grooves (fig.1,pos.2). It is rotated until rest (fig.3.1). The 

slots of the base and the body should match (fig.3.2). 

 

Locking of the fire detector (fig.4).  

 

 

Before installation, the key (pos.3) is detached from the base and the rib (pos.1) of the locking click 
(pos.2) is cut out. Removing of a fire detector locked to the base. Insert the key into the slot (pos.4) 

push in as in the same time the fire detector is rotated anticlockwise. Remove the key and continue 
to rotate the fire detector in the same direction until it is released from the base. 

Testing 

The smoke detector is tested after installation, following this order:  

1. Voltage is to the detector from controller or auxiliary power supply unit 24V DC/0,1A.  
2. After one minute smoke detector should be activated using a Smoke Detector Tester. It should 
enter fire condition within 40s.  
3. The supply voltage to the detector is interrupted within 2s. Smoke detector should enter duty 

mode and is ready for a new activation within 40s. 

 

 
 
 
 