TCW112-WD_R2 - June 2014
Page 2
1.
Short description
TCW112-WD
is an Ethernet controller, which is designed to work in IP-based networks. It has 1
digital and 1 analog input, 1-Wire interface and 1 relay output. It can be managed by WEB interface
and/or SNMP programs.
The relay can be activated either remotely (WEB, SNMP etc.) or locally - from presence/absence
of ping (echo request or echo replay). SNMP trap can be sent for every monitored parameter
(temperature, humidity, analog voltage and dry contact) if it goes outside of previously predefined
range. Special schematic is utilized for long 1-Wire support.
2.
Features
10 Mb Ethernet connectivity;
Password protected, web based configuration and control;
1 digital input with " dry contact" and "logic level" modes;
1 analog input with 0 to 60VDC range;
1 relay with NO and NC contacts;
Long 1-Wire support for 1 temperature (TST1XX) or temperature/humidity (TSH2xx) sensor;
SNMP v.1 support;
SNMP traps sending for alert conditions;
VLAN support;
MAC address filtering;
Remote FTP firmware update.
3.
Technical parameters
Supply voltage, VDC
12 ± 2
Maximum current consumption ( with activated relay), mA
120
Weight, g
45
Dimensions, mm
72 x 50 x 18
Operating temperature, °C
0 to +40
Maximum humidity in 0 to 31°C range, %RH
80
Maximum humidity at 40°C (linear slope between 31-40°C), %RH
50
Minimum high level input voltage for digital inputs, VDC
+2.5
Maximum low level input voltage for digital inputs, VDC
+0.8
Maximum input voltage for digital inputs, VDC
+5.5
Analog input range, VDC
0 to +60
Supply voltage for 1-wire bus (+VW), VDC
5.3 ± 0.2
Maximum output current for 1-wire bus (+VW), A
0.2
Supply voltage for analog sensor (+VA), VDC
5.0 ± 0.1
Maximum output current for analog sensor (+VA), A
0.1
Maximum switchable current for relay contacts, А
3
Maximum switchable voltage for relay contacts, VAC/VDC
30/24