2
SADRŽAJ:
1.
Namjena………………….……………….……………….……………….
2.
Sukladnost proizvoda….………………………………………………
3.
Tehnički podaci…………...……………………………………………..
4.
Tipna oznaka………………….……………………………………………
5.
Montaža………………………...…………………………………………..
6.
Dimenzije……..................................................................
7.
Pregled, održavanje, popravak, obnavljanje…………………
8.
Rezervni dijelovi ……………….…….………………………………….
9.
Odgovornost i ovlaštenja…………………..………………………..
10.
Skladištenje i transport….……………………………………………
11.
Jamstvo proizvođača………….……………………………………….
12.
Označavanje……………………………………………………………….
2
2
2
3
4
4
5
5
6
6
6
7
CONTENTS:
1.
Purpose…………………………………...…………....………………….
2.
Product conformity………..………..………………………………..
3.
Technical data……………………………………………………………
4.
Types …………………………….…………………………………………..
5.
Mounting………………………….………………………………..........
6.
Dimensions…………………………………………………………….....
7.
Inspection, maintenance, repair and overhaul……………
8.
Spare parts.………………………………………………………………..
9.
Responsibility and authorization.……………………………….
10.
Storage and transport…………………………………………………
11.
Manufacturer's warranty.…………………………………………..
12.
Marking……..………………………………………………………........
2
2
2
3
4
4
5
5
6
6
6
7
1. NAMJENA
Protueksplozijski zaštićena ovjesna svjetiljka PLFS-N 100 LED
namijenjena je za upotrebu u industrijskim prostorima na
mjestima s potencijalno eksplozivnom atmosferom plinova,
para i prašina u zonama opasnosti 1, 2, 21, 22 sukladno normi
EN 60079-10-1 i EN 60079-10-2.
2. SUKLADNOST PROIZVODA
Konstrukcija svjetiljke sukladna je s normama EN 60598-1 i svim
povezanim normama.
Proizvod je sukladan Pravilniku o opremi i zaštitnim sustavima
namijenjenim za uporabu u potencijalno eksplozivnim
atmosferama, NN br. 34/16.
Proizvod je sukladan ATEX Direktivi 2014/34/EU i normama:
-
EN IEC 60079-0:2018,
-
EN 60079-1:2014,
-
EN IEC 60079-7:2015+A1:2018,
-
EN 60079-28:2015,
-
EN 60079-31:2014.
Proizvod je razvijen, proizveden i ispitan prema postojećem
stanju tehnike sukladno normama EN ISO 9001,
EN ISO 80079-34 i EN ISO 14001.
Proizvod je sukladan LVD Direktivi 2014/35/EU.
Proizvod je sukladan RoHS Direktivi 2011/65/EU.
Proizvod je sukladan EMC Direktivi 2014/30/EU.
3. TEHNIČKI PODACI
Certifikat
FIDI 19 ATEX 0031
Oznaka kategorije i
protueksplozijske zaštite
uređaja:
II 2G Ex db eb op is IIC T6 Gb
II 2D Ex tb op is IIIC T85°C Db
Temperatura okoline:
-40°C /-20°C ≤ Ta ≤ +50°C
Mehanička zaštita:
IP 66
Otpornost na udar:
IK 08
Klasa zaštite:
I (PE - zaštitno uzemljenje)
Nazivni napon Un:
110 – 230 V AC, 127-230V DC
Radni napon:
90 - 305 V AC / 127 - 431 V DC
Nazivna snaga Pn:
35 W/ 60 W / 80 W / 100 W
Faktor snage:
>0,95
LED izvor:
CLU058-1825C4-403M2M2-F1,
Citizen LTD.
OVP zaštita:
IEC 61000-4-5, EN 62031 3kV/1min
-
udarni prenapon 8/20μs 6kV/3kA
1. PURPOSE
Explosion protected pendant light fitting type PLFS-N 100 LED, is
intended for general lighting in industrial areas with potentially
explosive atmosphere Zones 1, 2, 21, 22 in accordance with
EN 60079-10-1 and EN 60079-10-2. The quality of the materials
ensures compliance with standard functionality in standard industrial
atmosphere.
2. PRODUCT CONFORMITY
The product complies with the standards:
-
EN IEC 60079-0:2018,
-
EN 60079-1:2014,
-
EN IEC 60079-7:2015+A1:2018,
-
EN 60079-28:2015,
-
EN 60079-31:2014.
The product has been developed, manufactured and tested according
to the existing state of technique accordance with the
standards EN ISO 9001 and EN ISO 80079-34 and EN ISO 14001.
The product is in compliance with the ATEX Directive 2014/34/EU.
The product is in compliance with the LVD Directive 2014/35 EU.
The product is in compliance with the RoHS Directive 2011/65 EU.
The product is in compliance with EMC Directive 2014/30/EU.
3. TECHNICAL DATA
Certificate:
FIDI 19 ATEX 0031
Category and
explosion protection:
II 2G Ex db eb op is IIC T6 Gb
II 2D Ex tb op is IIIC T85°C Db
Ambient temperature:
-40°C /-20°C ≤ Ta ≤ +50°C
Mechanical protection:
IP66
Resistance to shock:
IK 08
Class of protection:
I (PE - protective earthing)
Rated voltage Un:
110 – 230 V AC, 127-230V DC
Service voltage:
90 - 305 V AC / 127 - 431 V DC
Rated power Pn:
35 W/ 60 W / 80 W / 100 W
Power factor:
>0,95
LED light source:
CLU058-1825C4-403M2M2-F1,
Citizen LTD.
OVP protection:
IEC 61000-4-5, EN 62031 3kV/1min
impulse overvoltage 8/20μs 6kV/3kA