background image

7

441 01 5001 00

5. When sizing grille or louver, use the free area of opening. If

free area is

NOT

stamped or marked on grill or louver, as-

sume a 20% free area for wood and 60% for metal.

Requirements

1. Provide confined space with sufficient air for proper combus-

tion and ventilation of flue gases using horizontal or vertical

ducts or openings.

2.

Figure 4

illustrates how to provide combustion and ventila-

tion air. A minimum of two permanent openings, one inlet and

one outlet, are required.

3. One opening

MUST

be within 12

²

of the floor and the second

opening within 12

²

of the ceiling.

4. Size openings and ducts per

Table 1

.

Furnace

Furnace

Minimum One Inlet and One Outlet Air Supply is Required

May be in and Combination Shown

Inlet Air Opening Must be Within12

²

(300mm) of floor

Outlet Air Opening Must be Within12

²

(300mm) of ceiling

(1) 1 Square Inch (6cm

2

) per 4000 BTUH

(2) 1 Square Inch (6cm

2

) per 2000 BTUH

Outside Air (This is ONLY a guide. Subject to codes of country having jurisdiction.)

Figure 4

This installation NOT approved in Canada

Gas Vent

Gas Vent

Gas Vent

Gable Vent

Gable Vent

Outlet

Air (1)

Outlet Air (1)

Outlet Air (1)

Furnace

Outlet

Air (2)

Optional Inlet Air (1)

Ventilated Attic

Ventilated Attic

Ventilated Crawl Space

Inlet

Air (1)

Inlet

Air (1)

Inlet

Air (1)

Inlet

Air (2)

Inlet

Air (2)

Top Above Insulation

Top Above Insulation

Soffit Vent

Soffit Vent

5. Horizontal duct openings require 1 square inch of free area

per 2,000 BTUH of combined input for all gas appliances in

area

(

see

Table 1)

.

6. Vertical duct openings or openings directly to outside require

1 square inch of free area per 4,000 BTUH for combined input

of all gas appliances in area

(

see

Table 1).

One permanent opening, commencing within 12

²

of the top of the

enclosure, shall be permitted where the equipment has clear-

ances of at least 1

²

from the sides and back and 6

²

from the front of

the appliance. The opening shall directly communicate with the

outdoors or shall communicate through a vertical or horizontal

duct to the outdoors or spaces (crawl or attic) that freely communi-

cate with the outdoors, and shall have a minimum free area of:

·

1 sq. in per 3000 Btu per hr. of the total input rating of all equip-

ment located in the enclosure, and

·

Not less than the sum of the areas of all vent connectors in the

confined space.

Table 1

Free Area

BTUH

Minimum Free Area Required for Each Opening

BTUH

Input

Rating

Horizontal Duct

(sq. in./2,000 BTUH)

Vertical Duct or

openings to outside

(sq. in./4,000 BTUH)

Rd Duct

(sq. in. /4,000

BTUH)

50,000

25 sq. in.

12.5 sq. in.

4

²

75,000

35.5 sq. in.

18.75 sq. in.

5

²

100,000

50 sq. in.

25 sq. in.

6

²

125,000

62.5 sq. in.

31.25 sq. in.

7

²

EXAMPLE:

Determining Free Area

Furnace Water Heater Total Input

100,000

+

30,000 = (130,000

¸

4,000) = 32.5 Sq. In. Vertical

Furnace Water Heater Total Input

100,000

+

30,000 = (130,000

¸

2,000) = 65 Sq. In. Horizontal

Unconfined Space Installation

!

CARBON MONOXIDE POISONING HAZARD.
Most homes will require additional air.
Failure to supply additional air by means of

ventilation grilles or ducts could result in death

and/or personal injury.
An unconfined space or homes with tight

construction may not have adequate air infiltration

for proper combustion and ventilation of flue

gases.

An unconfined space is defined as an area having a minimum vol-

ume of 50 cubic feet per 1,000 Btuh total input rating for all gas ap-

pliances in area.

Summary of Contents for H8UH5050B12

Page 1: ...nel can perform basic maintenance functions such as cleaning and replacing air filters All other operations must be performed by trained service personnel When working on heating equipment observe precautions in the literature on tags and on labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes i...

Page 2: ...of Supply Air F or C Temperature of Return Air F or C Rise Supply Temp Return Temp F or C Filter Type and Size Fan Time ON Setting Fan Time OFF Setting Manual Gas Shut Off Upstream of Furnace Drip Leg YES NO Drip Leg Upstream of Gas Valve YES NO Blower Speed Checked YES NO All Electrical Connections Tight YES NO Gas Valve OK YES NO Measured Line Pressure When Firing Unit Calculated Firing Rate See...

Page 3: ...lt to provide many years of safe and dependable service providing it is properly installed and maintained However abuse and or improper use can shorten the life of the unit and create hazards for you the owner A The U S Consumer Product Safety Commission recom mends that users of gas burning appliances install carbon monoxide detectors There can be various sources of carbon monoxide in a building ...

Page 4: ...e necessary to resize the existing vent line and chimney to prevent oversizing problems for the other remaining appliances s See applicable codes and Venting and Combustion Air Check and Gas Vent Installation section Location and Clearances If furnace is a replacement it is usually best to install the furnace where the old one was Choose the location or evaluate the exist ing location based upon t...

Page 5: ...RONT 3 Recommended For Service 30 ALL SIDES Of SUPPLY PLENUM 1 SIDES 0 VENT Single Wall Vent 6 Type B 1 Double Wall Vent 1 TOP OF FURNACE 1 Horizontal position Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Cabinet Top Bottom Unit Capacity A B F C D H8UH5050B12 H8UH5075B...

Page 6: ...nd ventilation air can result in death and or personal injury Use methods described here to provide combus tion and ventilation air Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases All duct or open ingsforsupplyingcombustion andventilation airmustcomplywith the gas codes or in the absence of local codes the applicable na tional cod...

Page 7: ...re 1 square inch of free area per4 000 BTUHfor combined input of all gas appliances in area see Table 1 One permanent opening commencing within 12 of the top of the enclosure shall be permitted where the equipment has clear ances ofatleast1 fromthe sides and back and 6 fromthe frontof the appliance The opening shall directly communicate with the outdoors or shall communicate through a vertical or ...

Page 8: ...this furnace can result in death personal injury and or property damage Install the vent in compliance with codes of the country having ju risdiction local codes or ordinances and these instructions These fan assisted combustion furnaces have been classified as Category I appliances which means that they MUST operate with a negative vent pressure Category I Safe Venting Requirements NOTE The follo...

Page 9: ...icates sufficient infiltration air Venting to Existing Masonry Chimney NOTE The tables and notes referred to below are found in the most recent printing of the United States National Fuel Gas Code venting tables Use the United States National Fuel Gas Code or NFGC Tables to size the chimney orvent Dedicatedventing ofone fanassisted furnace into any masonry chimney is restricted The chimney must fi...

Page 10: ...for installations below 2000 in altitude Table 3 Orifice Sizes below 2000 Gas Type Manifold Pressure Specific Gravity Heating Value BTU per Cubic Ft Orifice Size Drill Natural 3 5 w c 800 40 3 5 w c 0 9kP 0 6 900 41 0 9kPa w c 0 6 1000 42 w c 1100 43 Propane 10 w c 2 5kPa w c 1 53 2500 54 Operation Above 2000 Altitude FIRE EXPLOSION CARBON MONOXIDE POISON ING HAZARD This conversion shall be done b...

Page 11: ...FERENT SPECIFIC GRAVITY CONSULT THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 and CAN B149 NOTE The derating of these units at 2 Natural and 4 L P has been tested and approved by AGA High Altitude Air Pressure Switch Altitudes over 4 000 require a different air pressure switch than the one installed at thefactory Check parts list for pressure switch and consult your distributor for ...

Page 12: ...vide a 1 8 inch plug for test gauge connection immediate ly up stream of gas supply connection to furnace 7 Use two pipe wrenches when making connections to prevent gas valve from turning Typical Gas Piping Figure 8 25 24 35a Union Manual Valve Drip leg pipe cap left side entry 8 Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or...

Page 13: ...s Fieldwiringconnectionsmustbemadeinsidethefurnaceconnec tion box A suitable strain relief should be used at the point the wires exit the furnace casing Copper conductors shall be used Line voltage wires should be sized for the input amps stated on the rating plate Furnace must be connected to its own separate circuit Thermostat Thermostat location has an important effect on the operation of the u...

Page 14: ...bjectionable when the unitis located very close to a living area Itis often advisable to route the return air ducts under the floor or through the attic Refer to furnace Technical Support Manual Blower Data for air flow information Size ductwork to handle air flow for heating and air condition ing if used Duct Installation Requirements When furnace supply ducts carry air outside furnace area seal ...

Page 15: ...e high velocity filter providing they meet the minimum size areas Washable high velocity filters can be replaced ONLY with same type and size 2 5 2 0 3 1 Figure 12 Optional Duct Standoff 20 x 25 Optional Filter Rack Filter Installation using Optional Filter Rack When installing or removing a bottom mounted filter slide the two side filter clips to the back of the furnace BEFORE installing or re mo...

Page 16: ...Blower Speed ELECTRICAL SHOCK HAZARD Failure to do so can result in death personal injury and or property damage Turn OFF power to furnace before changing speed taps NOTE The speed taps that the manufacture sets from the factory for this product are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating Since the manufacturer cannot establish the sta...

Page 17: ...s removed from EFT Cool motor speed de energized after 90 second Cool Fan Off Delay time Circulating Fan G Request 24 VAC signals applied to G terminals of EFT control Heat motor speed energized without delay G signal removed from EFT Heat motor speed de energized without delay NOTE 1 Furnaces with PSC blower motors de energize the Low Heat fan speed during the heat exchanger warm up period on a c...

Page 18: ...ry count exceeded failed to light within 4 trials for ignition 6 Flashes 2 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Flame Sense Lost During Run Cycling Pressure Switch or Blocked Condensate 6 Flashes 3 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Airflow Proving Circuit Opened During Run 6 Flashes 4 Notes 1 2 Soft Lockout Maximum recycle coun...

Reviews: