F96CTN and G96CTN (Series A): Installation, Start-up, Operating, Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
55
Adjustments
For proper operation and long term reliability, the Furnace input rate
must be /-2 percent of input rate on furnace rating plate, or as
adjusted for altitude.
The gas input rate on rating plate is for installations at altitudes up to
2000 ft. (609.6M).
A93059
Fig. 62 – Orifice Hole
In the USA, the input rating for altitudes above 2000 ft. (609.6M) must
be reduced by 2 percent for each 1000 ft. (304.8M) above sea level.
. The natural gas manifold pressures in
adjust
for BOTH altitude and natural gas heating value.
In Canada, the input rating must be reduced by 5 percent for altitudes of
2000 ft. (609.6M) to 4500 ft. (1371.6M) above sea level. The natural gas
manifold pressures in
adjust for BOTH altitude and natural gas
heating value.
Table 18 – Altitude Derate Multiplier for U.S.A.
*Derate multiplier factors are based on midpoint altitude for altitude range.
NOTE:
For Canadian altitudes of 2000 to 4500 ft. (609.6 to 1371.6M),
Use USA altitudes of 2001 to 3000 ft. (609.6 to 914.4M).
To adjust manifold pressure to obtain the proper input rate, first,
determine if the furnace has the correct orifice installed. At higher
altitudes or different gas heat contents, it may be necessary to change the
factory orifice to a different orifice. Tables have been provided in the
furnace installation instructions to match the required orifice to the
manifold pressure to the heat content and specific gravity of the gas. To
do this:
1. Obtain average yearly gas heat value (at installed altitude) from
local gas supplier.
2. Obtain average yearly gas specific gravity from local gas supplier.
3. Find installation altitude in
.
4. Find closest natural gas heat value and specific gravity in
.
5. Follow heat value and specific gravity lines to point of intersection
to find orifice size and low-and high-heat manifold pressure
settings for proper operation.
6. Check and verify burner orifice size in furnace. NEVER ASSUME
ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas
leaks with an open flame. Use a commercially available soap solution
made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury
or loss of life.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw. This can
result in unregulated manifold pressure and result in excess overfire and
heat exchanger failures.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes,
etc.) can cause excessive burner noise and misdirection of burner
flames. This can result in flame impingement of heat exchangers,
causing failures. See
BURNER
ORIFICE
NOTICE
!
The NATURAL GAS manifold pressure adjustments in
compensate for BOTH altitude AND gas heating value. DO NOT apply
an additional derate factor to the pressures shown in
. The
values in this table are NOT referenced to sea level; they are
AS-MEASURED AT ALTITUDE.
The heating content of natural gas at altitude may already provide for a
reduction in capacity of the furnace. Be sure to obtain the expected
in-season gas heating value of the gas from the gas supplier BEFORE
making any adjustments for capacity or altitude. Refer to
. No
adjustments to the furnace may be necessary at altitude for certain gas
heating values.
Refer to the instructions provided in the factory-specified LP/Propane
conversion kit for instructions for setting gas manifold pressures for
LP/Propane applications.
ALTITUDE
PERCENT
OF
DERATE
DERATE
MULTIPLIER
FACTOR*
FT.
M
0–2000
0-610
0
1.00
2001–3000
610-914
4-6
0.95
3001–4000
914-1219
6-8
0.93
4001–5000
1219-1524
8-10
0.91
5001–6000
1524-1829
10-12
0.89
6001–7000
1829-2134
12-14
0.87
7001–8000
2134-2438
14-16
0.85
8001–9000
2438-2743
16-18
0.83
9001–10,000
2743-3048
18-20
0.81