OSA 83RKSH & OSA 95RKSH

Reverse Cycle R410A Single Phase

Split System Outdoor Units

Installation &

Maintenance

GENERAL

This OSA 83 and 95 Outdoor Units must be 
installed in accordance with all national and 
local safety codes.

Options

1. Vertical discharge grille.
2. Wall mounting brackets.
3. Anti-vibration mounts (rubber).
4. Soft starter kit
5. Drain connection adaptors - right angle.

INSTALLATION
Positioning

Refer to dimension diagram below for 
minimum clearances. Position the unit so 
that prevailing winds do not blow onto the 
exhaust to slow the fan, and one unit does 
not exhaust toward the inlet of another unit.
The optional vertical discharge grille can be 
used to deflect prevailing winds and reduce 
clearances.
Mount either free standing or on a wall using 
the optional mounting brackets available.

REFRIGERATION PIPING
General

The OSA 83/95 is shipped with a refrigerant 
charge sufficient for a 10 m line length. 
The matched indoor unit is shipped with a 
holding charge of nitrogen. OSA 83/95 units 
have shut-off service valves and swaged 
assemblies. Two loose pipe extensions are 
supplied to enable a choice of exit – side or 
rear; both require brazing.

Recommended Pipe Sizes

Suction pipe : 

16 or 19 mm OD

Liquid pipe : 

10 mm OD

Line Lengths

The standard unit allows for a line length  
up to 30 m. For line lengths between 30 m 
and 40 m, refer to 

temperzone

's 

Split Systems Installation Guide (refer  
www.temperzone.biz/Technical Support)
.
Refer also to Oil Charge overleaf. 
Maximum line length when extended is 40m.
For line lengths in excess of 15 m use a 
19 mm OD suction pipe size. 

Height Separation Limits

Outdoor Unit above Indoor Unit :  16 m
Outdoor Unit below Indoor Unit :  16 m

Vertical Risers

If the outdoor unit is to be installed above 
the indoor unit, then the suction riser should 
be trapped at the bottom of the vertical 
rise and then again at 5 m (maximum) 
intervals. This is to ensure oil return to the 
compressor. The trap to be a 'swan neck' 
curve in the pipe, with no change in the pipe 
size.

Piping

1.  Use clean sealed refrigeration grade 

piping and accessories designed 
specifically for R410A.

2.   Cut pipe with a pipe cutter ONLY.
3.   Use long radius bends (2x pipe dia.).
4.   Insulate the suction (gas) line and seal 

all insulation joints.

5.  Bi-flow type filter dryer may be fitted in 

the liquid line.

6.  Include a process point in the 

interconnecting pipework.

7.  Ensure open pipe ends are sealed until 

the final connection is made.

8.  Immediately before removing brazed 

pipe connection's seal, reduce holding 
charge between connection points and 
service valves to atmospheric pressure. 

Warning

:  Failure to do so may cause 

injury.

Free Standing :  
Fasten the unit down to a firm flat horizontal 
base using the four holes provided in the 
mounting rails.
When the unit is being installed on a roof 
it is recommended that the unit is installed 
on a substantial structure with vibration 
isolating springs or rubber mounts (optional 
extra) beneath the unit. These items are not 
supplied with the unit.

Wall Mounting Option:
Complete wall mounting instructions are 
supplied with the optional wall mounting kit.

Drain

Four drain holes are provided in the base.  
Three plastic bungs are supplied (loose) 
should you want to direct the condensate 
and/or rain water to one of the holes 
provided. Drain connection adaptors (25/13) 
are available as an optional extra.

Dimensions (mm) 

      OSA 83/95 RKSH

PROJECTION

Not to Scale

Net Weight 85 kg

686 MTG CTR

12 DIA. HOLE+SLOT

ACCESS

PANEL

349

MTG CTR

395

 OVERALL

REFRIG.

CONN’S

25 DIA.

ELECTRICAL

CONDUIT

HOLES

660

OVERALL

1040

OVERALL

72

100 MIN. CLEARANCE

100 MIN.

 CLEARANCE

2000 MIN. CLEARANCE *

750 MIN.

 CLEARANCE

180

25 DIA.

DRAIN

HOLES

174

25

25 DIA.

DRAIN

HOLES

* 600 min with optional Vertical Discharge Grille