background image

- 1 -

OPA 250–560 RLTFP-DZ (Econex) c/w Economiser & Viking

Air Cooled Packaged Units - Reverse Cycle - R32

Installation & Maintenance

1. GENERAL

Temperzone OPA Outdoor Air Cooled Packaged units.
Follow these instructions to ensure the optimum performance, 

reliability and durability.
Units must be installed in accordance with all national and 

regional regulations and bylaws. National Health and Safety 

regulations must be followed to avoid personal injuries.
The appropriate local permits must be acquired and  

adhered to.
Local regulations on maximum boundary noise need to  

be considered when positioning the unit.
The Economiser/Viking functionality of the unit is designed to 

comply with Australian National Construction Code (NCC 2022) 

and NZ Building Code H1/VM3 which specifies the Enthalpy 

Method of operation for energy efficiency.
The accompanying ‘R32 Handling Ducted Packaged Units’ 

pamphlet forms part of these Installation & Maintenance 

instructions.

!

 WARNING 

These units use R32 refrigerant (Class A2L) which is mildly 

flammable.
The system shall be installed, operated and stored in a well 

ventilated space. If the refrigerant gas comes into contact with 

fire, a poisonous gas may occur. Be aware that R32 does not 

contain an odour.
If indoors, the appliance shall be stored in a room away from 

continuously operating sources known to cause ignition of R32 

refrigerant (for example an operating gas appliance or operating 

electric heater)

This appliance is not intended for use by persons (including children) 

with reduced physical, sensory, or mental capabilities, or lack of 

experience and knowledge, unless they have been given supervision or 

instruction concerning use of the appliance by a person responsible for 

their safety. Children should be supervised to ensure that they do not 

play with the appliance.

003-000-278  09/22

CONTENTS

   

 

 

 

          

Page

1. GENERAL ..............................................................................1
2. INSTALLATION ......................................................................2
3. REFRIGERATION SYSTEM ...................................................2
4. CONTROLS ...........................................................................3
5. START-UP PROCEDURE ......................................................3
6. OPERATION...........................................................................4
7. MAINTENANCE ......................................................................7
8. TROUBLESHOOTING ...........................................................7
9. WARRANTY ...........................................................................8
10. UC8 CONTROLLER DISPLAY .............................................8
11. VIKING CONTROLLER : FACTORY SETTINGS .................8
APPENDIX I : PROTECTION FUNCTIONS  ..............................9
APPENDIX II : AIR HANDLING PERFORMANCE ...................11
COMMISSIONING CHECK LIST .............................................12

Summary of Contents for OPA 250 RLTFP-DZ

Page 1: ...rigerant Class A2L which is mildly flammable The system shall be installed operated and stored in a well ventilated space If the refrigerant gas comes into contact with fire a poisonous gas may occur...

Page 2: ...rain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe refer fig 2 Figure 2 Condensate Drains OPEN DRAIN MINIMUM SLOPE 20 mm PER m 1 IN 50 100 mm MINIM...

Page 3: ...rcing safety timers Figure 4 UC8 Controller The Unit Controller provides several system protection functions These are covered in Appendix I p 9 For additional information refer to the UC8 Controller...

Page 4: ...he UC8 controller via terminal block shown Connect BMS terminal B TX to terminal B1 on the UC8 controller via terminal block shown Multiple OPA units can be daisy chained together For detailed informa...

Page 5: ...eps 2 to 5 for each compressor 7 Test operation of the compressors when operating in heating mode 8 Check for desired supply air flow rate at each outlet 9 Touch up any outdoor unit paintwork damage t...

Page 6: ...ity for example 0V on input VC then the compressor operates on minimum duty If a unit operates on low capacity for extended periods then the unit may periodically perform oil flush cycles Under such o...

Page 7: ...to deliver the heating when most needed Heating capacity at design conditions may be incorrect As the outside temperature falls heat losses through the walls floor and ceiling increase Check the unit...

Page 8: ...AP Capacity 100 Expansion valve 1 opening EE1 Expansion valve 1 75 open Expansion valve 2 opening EE2 Expansion valve 2 75 open 10 UC8 CONTROLLER DISPLAY 11 VIKING CONTROLLER FACTORY SETTINGS Installe...

Page 9: ...an indication that the compressor is being starved of refrigerant gas Common reasons for this could be a lack of refrigerant under charged or loss of charge or a problem with the expansion device for...

Page 10: ...ked out the compressor is not allowed to start Lock out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician T...

Page 11: ...3 4 1 1 INPUT kW 2 5 1 5 0 5 2 0 1 0 3 0 3 5 Amps 500 1000 1500 2000 2500 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 0 NOMINAL INPUT kW 3 0 2 0 1 0 2 5 1 5...

Page 12: ...scroll through list IMPORTANT Digital compressors must be operating at 100 for at least 10 minutes when taking these readings System 1 Cool Cycle Low Pressure SLP kPa Outdoor Ambient temperature C Ev...

Reviews: