TemperZone OPA 161RKTYH Installation & Maintenance Download Page 2

Dimensions (mm) 

      OPA 161RKTYH

PROJECTION

Not to Scale

 

POINT LOads (kg) 

WEIGHT

 

(kg)

  37 

60 

60 

68 

225

5.  Fit R410A compatible gauges and 

measure the suction and discharge 
pressures.

6.  Test the operation of the high pressure 

safety control by switching off the 
outdoor air fan.

7.  Test the operation of the reversing valve 

by running the unit in both the heating 
and cooling mode.

8.  Check that the motors are running 

smoothly.

9.  Check the supply air flow at each outlet.
10. Touch up any outdoor unit paintwork 

damage to prevent corrosion.

OUTDOOR UNIT CONTROllER (OUC)

The Outdoor Unit Controller (OUC) includes 
a temperature sensing head pressure 
control which enables the system to com-
pensate for outdoor ambient temperatures 
below 20°C on cooling cycle, and above 
15°C on heating cycle. The OUC also has 
features which protect against icing or 
overheating of coils, rapid cycling of the 
compressor and loss of refrigerant charge. 

If the outdoor unit fans take some time 
to begin rotating when the system is 
powered on, or they don't appear to be 
rotating appropriately while the compressor 
is running, consult the OUC label on 
the electrical box. If necessary, refer 
to 

temperzone 

for further diagnostic 

information.

MAINTENANCE
Weekly For First Four Weeks

1.  Check indoor air filters (if fitted) and 

vacuum or wash clean as necessary.

2.  Check condensate drain for free 

drainage.

3.  Check compressor compartment for oil 

stains indicating refrigerant leaks.

4.  Check tightness of electrical 

connections.

Six Monthly

1.  Check the tightness of all fan and motor 

mountings.

2.  Check tightness of electrical 

connections.

SUPPLY

AIR

RETURN

AIR

1154

MOUNTING CENTRES

1160

OVERALL

1200

 OVERALL

OUTDOOR

AIR FLOW

1000 MIN.

 CLEARANCE

500 MIN. CLEARANCE

X

Y

Z

W

OUTDOOR

AIR FLOW

ELECTRICAL

ACCESS

PANEL

60

342

35

125

ACCESS

PANEL

2000 MIN. CLEARANCE

1070

 OVERALL

160

1065

860

725

MOUNTING CENTRES

12 DIA. HOLES

DRAIN

15 BSPF

11

ELECTRICAL

HOLES

25 DIA.

187

225

190

75

3.  Check suction and discharge operating 

pressures.

4.  Replace indoor unit air filters (if fitted).
5.  Check condensate drain for free 

drainage.

Yearly

1.  Check all refrigerant piping for chafing 

and vibration.

2.  Check the operation of electric heaters, 

if fitted.

3.  Check air supply at all diffusers.
4.  Check for excessive noise and vibration 

and correct as necessary.

5.  Check for insulation and duct damage 

and repair as necessary.

6.  Remove lint and dust accumulation 

from outdoor coil fins. 

7.  Touch up any outdoor unit paintwork 

damage to prevent corrosion.

NOTE

The manufacturer reserves the right to 
change specifications at any time without 
notice or obligation.  Certified dimensions 
available on request. 