Dimensions (mm)
OPA 161RKTYH
PROJECTION
Not to Scale
POINT LOads (kg)
WEIGHT
W
X
Y
Z
(kg)
37
60
60
68
225
5. Fit R410A compatible gauges and
measure the suction and discharge
pressures.
6. Test the operation of the high pressure
safety control by switching off the
outdoor air fan.
7. Test the operation of the reversing valve
by running the unit in both the heating
and cooling mode.
8. Check that the motors are running
smoothly.
9. Check the supply air flow at each outlet.
10. Touch up any outdoor unit paintwork
damage to prevent corrosion.
OUTDOOR UNIT CONTROllER (OUC)
The Outdoor Unit Controller (OUC) includes
a temperature sensing head pressure
control which enables the system to com-
pensate for outdoor ambient temperatures
below 20°C on cooling cycle, and above
15°C on heating cycle. The OUC also has
features which protect against icing or
overheating of coils, rapid cycling of the
compressor and loss of refrigerant charge.
If the outdoor unit fans take some time
to begin rotating when the system is
powered on, or they don't appear to be
rotating appropriately while the compressor
is running, consult the OUC label on
the electrical box. If necessary, refer
to
temperzone
for further diagnostic
information.
MAINTENANCE
Weekly For First Four Weeks
1. Check indoor air filters (if fitted) and
vacuum or wash clean as necessary.
2. Check condensate drain for free
drainage.
3. Check compressor compartment for oil
stains indicating refrigerant leaks.
4. Check tightness of electrical
connections.
Six Monthly
1. Check the tightness of all fan and motor
mountings.
2. Check tightness of electrical
connections.
SUPPLY
AIR
RETURN
AIR
1154
MOUNTING CENTRES
1160
OVERALL
1200
OVERALL
OUTDOOR
AIR FLOW
1000 MIN.
CLEARANCE
500 MIN. CLEARANCE
X
Y
Z
W
OUTDOOR
AIR FLOW
ELECTRICAL
ACCESS
PANEL
60
342
35
125
ACCESS
PANEL
2000 MIN. CLEARANCE
1070
OVERALL
160
1065
860
725
MOUNTING CENTRES
12 DIA. HOLES
DRAIN
15 BSPF
11
ELECTRICAL
HOLES
25 DIA.
187
225
190
75
3. Check suction and discharge operating
pressures.
4. Replace indoor unit air filters (if fitted).
5. Check condensate drain for free
drainage.
Yearly
1. Check all refrigerant piping for chafing
and vibration.
2. Check the operation of electric heaters,
if fitted.
3. Check air supply at all diffusers.
4. Check for excessive noise and vibration
and correct as necessary.
5. Check for insulation and duct damage
and repair as necessary.
6. Remove lint and dust accumulation
from outdoor coil fins.
7. Touch up any outdoor unit paintwork
damage to prevent corrosion.
NOTE
The manufacturer reserves the right to
change specifications at any time without
notice or obligation. Certified dimensions
available on request.