background image

IJD 2000, 2400

Ducted

Fan Coil Units

Installation &

Maintenance

GENERAL

The IJD ducted fan coil units must be 

installed in accordance with all national and 

local safety codes.

 

Options

1.  Filters

2.  Electric Elements c/w fan run-on timer

3.  Polyester powder coat finish 

ELECTRIC HEAT (Factory Fitted Option)

Refer to wiring diagram for size of elements 

supplied. A fan run-on timer for rapid heat 

dissipation is included with this option.  

A 24 hour power supply is essential for this 

timer to function correctly.

INSTALLATION

Positioning & Mounting

Provide 1 m minimum clearance to both 

ends of the unit.
The unit has a built-in sloping drain tray, 

therefore mount it level.
Fasten the unit down to a firm flat horizontal 

base using the six fixing holes provided in 

the mounting rails. Use the bunged holes 

provided in the base of the filter box to 

access the mounting rail holes from above.
When the unit is being installed on a roof 

it is recommended that the unit is installed 

on a substantial structure with vibration 

isolating springs beneath the unit. These 

springs are not supplied with the unit.

Condensate Drain

The unit has an internal sloping condensate 

drain tray. The drain exit should be trapped 

outside the unit cabinet.  The trap should 

have a vertical height of at least 100 mm. 

The drain should have a slope of at least 1 

in 50 and must not be piped to a level above 

the unit drain tray. (Refer Fig.2).
For long condensate pipe runs, fit a vent 

pipe near the drain trap. The top of the vent 

pipe must be at least 100 mm above the IJD 

unit's drain tray. 
It is essential that the drainage system is 

checked by pouring water in the drain tray 

and seeing that it discharges at the end of 

the drain and does not overflow the drain 

tray.

ELECTRICAL WIRING

The electrical supply required is:  

3 phase 380-415 V a.c. 50 Hz with neutral 

and earth. The supply to have an isolation 

switch adjacent to the unit but not attached 

to the unit. Recommended external circuit 

breaker size is 40 A/ph.

Dimensions (mm)

Not to Scale

Fig. 1

PROJECTION

MODEL 

A B C D E F G H J K  L M N P

IJD 

2000 1680 1385 1280 

1525 120 405  730 405 815 495 1295 495 1297 1347

IJD 

2400 1930 1535 1430 

1825 75  480  775 480 890 325 1630 325 1447 1497

  MODEL  Wt (kg) 

POINT LOADS (kg)

 (4/1 Coil) 

incl. water

 U  V  W X  Y  Z

  IJD 2000 

657 

117  133  149  102  86  70

  IJD 2400 

809 

144  163  184  125  106  87

NOTE

The manufacturer reserves the right to change 

specifications at any time without notice or 

obligation. Certified dimensions available on 

request. 

Condensate Drain

OPEN

DRAIN

MINIMUM

SLOPE

20 mm PER m

(1 IN 50)

100 mm

MINIMUM

200 mm

APPROX.

'U' TRAP

100 mm

APPROX.

VENT PIPE

FOR LONG

CONDENSATE

DRAIN RUNS

Fig. 2

B

OVERALL

2280 OA

F

D

150

60

A

OVERALL

U

W

X

Z

OPTIONAL

VERTICAL SUPPLY

AIR SPIGOT

1000 MINIMUM CLEARANCE

1000 MIN.CLEARANCE

ACCESS

PANEL

ACCESS

PANEL

M

250

890

G

100

250

J

E

2000

ELECTRICAL

BOX

K

L

H

55

890

WATER CONNECTIONS:

4 x 50 (2") BSP MALE

N SPRING CTR

P FIXING CTR

DRAIN 38 BSPM

C

V

Y