IJD 2000, 2400
Ducted
Fan Coil Units
Installation &
Maintenance
GENERAL
The IJD ducted fan coil units must be
installed in accordance with all national and
local safety codes.
Options
1. Filters
2. Electric Elements c/w fan run-on timer
3. Polyester powder coat finish
ELECTRIC HEAT (Factory Fitted Option)
Refer to wiring diagram for size of elements
supplied. A fan run-on timer for rapid heat
dissipation is included with this option.
A 24 hour power supply is essential for this
timer to function correctly.
INSTALLATION
Positioning & Mounting
Provide 1 m minimum clearance to both
ends of the unit.
The unit has a built-in sloping drain tray,
therefore mount it level.
Fasten the unit down to a firm flat horizontal
base using the six fixing holes provided in
the mounting rails. Use the bunged holes
provided in the base of the filter box to
access the mounting rail holes from above.
When the unit is being installed on a roof
it is recommended that the unit is installed
on a substantial structure with vibration
isolating springs beneath the unit. These
springs are not supplied with the unit.
Condensate Drain
The unit has an internal sloping condensate
drain tray. The drain exit should be trapped
outside the unit cabinet. The trap should
have a vertical height of at least 100 mm.
The drain should have a slope of at least 1
in 50 and must not be piped to a level above
the unit drain tray. (Refer Fig.2).
For long condensate pipe runs, fit a vent
pipe near the drain trap. The top of the vent
pipe must be at least 100 mm above the IJD
unit's drain tray.
It is essential that the drainage system is
checked by pouring water in the drain tray
and seeing that it discharges at the end of
the drain and does not overflow the drain
tray.
ELECTRICAL WIRING
The electrical supply required is:
3 phase 380-415 V a.c. 50 Hz with neutral
and earth. The supply to have an isolation
switch adjacent to the unit but not attached
to the unit. Recommended external circuit
breaker size is 40 A/ph.
Dimensions (mm)
Not to Scale
Fig. 1
PROJECTION
MODEL
A B C D E F G H J K L M N P
IJD
2000 1680 1385 1280
1525 120 405 730 405 815 495 1295 495 1297 1347
IJD
2400 1930 1535 1430
1825 75 480 775 480 890 325 1630 325 1447 1497
MODEL Wt (kg)
POINT LOADS (kg)
(4/1 Coil)
incl. water
U V W X Y Z
IJD 2000
657
117 133 149 102 86 70
IJD 2400
809
144 163 184 125 106 87
NOTE
The manufacturer reserves the right to change
specifications at any time without notice or
obligation. Certified dimensions available on
request.
Condensate Drain
OPEN
DRAIN
MINIMUM
SLOPE
20 mm PER m
(1 IN 50)
100 mm
MINIMUM
200 mm
APPROX.
'U' TRAP
100 mm
APPROX.
VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS
Fig. 2
B
OVERALL
2280 OA
F
D
150
60
A
OVERALL
U
W
X
Z
OPTIONAL
VERTICAL SUPPLY
AIR SPIGOT
1000 MINIMUM CLEARANCE
1000 MIN.CLEARANCE
ACCESS
PANEL
ACCESS
PANEL
M
250
890
G
100
250
J
E
2000
ELECTRICAL
BOX
K
L
H
55
890
WATER CONNECTIONS:
4 x 50 (2") BSP MALE
N SPRING CTR
P FIXING CTR
DRAIN 38 BSPM
C
V
Y