AIR HANDLING PERFORMANCE

Note: Airflows are for a dry coil. Reduce airflow by 10% in high moisture removal conditions..  

As filters thickness varies, the fan air flows given are for units installed without filters.

OPA 1400RKTMF-P

l/s - Pa

NB Air Flow Selection

If air returning to the indoor coil is regularly expected to be above 50% relative humidity then the coil face 
velocity should be limited to 2.5m/s or less (refer air flow graph above)

Consideration must be given to selecting a airflow and coil face velocity that avoids water carry - over 
problems i.e. in high humidity (tropical/subtropical) conditions or when heavily moisture laden fresh air is 
introduced 

OPA 2100RKTMF-P

l/s - Pa

5000

6000

7000

8000

9000

0

100

200

300

AIR FLOW (l/s)

AV

AILABLE EXTERNA

L PRESSURE (

Pa)

2.5 m/s Face Velocity

400

500

4000

NOMINAL

6V

7V

8V

10V

5V

8.0

4.8

11

11

3.2

9.2

6.4

3.6

7000

8000

10000 11000

0

100

200

300

AIR FLOW (l/s)

AV

AILABLE EXTERNA

L PRESSURE (

Pa) 400

500

6000

NOMINAL

9000

2.5 m/s FACE VELOCITY

7V

9V

5V

8V

6V

7.6

4.0

4.0

16

8.8

Summary of Contents for EcoULTRA OPA 1400RKTMF

Page 1: ...plied in the mounting channels When the unit is being installed on a roof it is recommended that the unit is installed on a substantial structure with vibration isolating pads or mounts If placed on the ground or concrete pad use rubber pads or mounts to give 20mm min ground clearance Flexible duct connections are recommended between the supply and return ducts and the unit Unit is shipped with wo...

Page 2: ...Note 4 SA Temp U6 0 10VDC SA RH U7 0 10VDC The following inputs relate only when using external low level control Capacity Input U8 0 10VDC Enable ID4 24VAC Heat ID5 24VAC Occupancy ID6 24VAC Dehum ID7 24VAC Fault NO7 Relay Notes 1 Factory supplied loose fit as required in controlled space 2 Optionally provide 0 10VDC control of indoor fan speed will be overridden if written to BACnet or Modbus in...

Page 3: ...GD remote display Item no 201 000 379 inside building connection to c pCO J10 port Cable RJ 45 2 Connect Room temperature and humidity sensor directly to Carel c pCO controller See Specification sheet for wiring schematic sheet 2 for wiring details of Room temperature input and Room RH Option 2 In absence of a Carel remote pGD the unit can be controlled using the onboard master controller with its...

Page 4: ... first page shows Airflow setup Enter the required Air flow in l s refer Note below 5 Measure air flows from duct work to verify air flows 6 Scroll down to the next page Commission Systems 7 On this page is a list of all systems each system can be turned on and the capacity set 8 Turn each system on in isolation Leave the capacity at the default 75 Allow to run checking for any unusual noises or v...

Page 5: ...e below objects also need to be written Type Object Instance Object Name Read Write Units Default Range Description AnalogValue 36 BMS_RoomT RW C 5 35 Room temperature written by BMS AnalogValue 37 BMS_RoomRH RW RH 0 100 Room RH written by BMS BinaryValue 4 BMS_RoomT_RH_ ORide RW Bool 0 Bool Use BACnet Room temp and RH BMS_RoomT and BMS_ Room_RH for control To adjust the air flow via BACnet the fo...

Page 6: ...ts the supply air above the current room dew point the aim being to prevent moisture formation on duct work 8 Scroll down to the next page Here the selection can be changed from the default Standard to High Sensible High Latent or Custom setting Each of these presets changes the offset from the current set dew point calculated from the set room temperature and RH to determine the target evaporatin...

Page 7: ...ode regulations and the stop may be set on site to facilitate this Ensure the air flow is equal between full return air and full Economiser by adjusting the damper stops on both Return and Fresh air dampers As previously mentioned a 0 10V dc control signal is required to drive the dampers open and closed This is supplied by the Master Controller c PCO which opens the economiser based on enthalpy m...

Page 8: ...n the unit for operation fault diagnostics information or visit www temperzone biz model search UC8 Controller Press the Alarm button on the pGD to list the most recent faults Refer OPA 2100 Controller Manual for an explanation MA I N TENAN CE 8 MAINTENANCE WARNING HAZARDOUS VOLTAGE ENSURE ALL POWER SUPPLIES ARE ISOLATED BEFORE PERFORMING MAINTENANCE FAILURE TO ISOLATE POWER CAN LEAD TO SERIOUS IN...

Page 9: ...ctions 1 Press Alarm and Enter together for 3 seconds to access the system menu 2 Scroll to TCP IP settings and press Enter button 3 Select Settings DHCP OFF Enter an address in the same subnet set on the PC for example IP 192 168 0 1 MASK 255 255 255 Select Update configuration Yes APPEN D I X I CO N TRO L S E T UP I P AD D RES S ...

Page 10: ...breviations Abbrev Description OAT Ambient Temp C DeICe De ice sensor temp C SLT Suction line temp C EvapT Evaporation temp C DLT Discharge line temp C CondT Condenser temp C SSH Suction superheat K DSH Discharge superheat K ODF Outdoor fan speed IDF Indoor fan speed HP Discharge pressure kPa LP Suction pressure kPa EXV1 Expansion valve A EXV2 Expansion valve B OCT Outdoor Coil Temp C ICT Indoor C...

Page 11: ...he temperature rises above 110 C for longer than 30 minutes The temperature rises above 120 C immediate action The display shows the message Hi t when protection is active 5 High discharge superheat protection Discharge superheat is defined as the difference between the compressor discharge gas temperature and the condensing temperature When this temperature differential becomes very high it is an...

Page 12: ...quires the attention of a service technician The display shows the code of the fault that caused the lock out condition A unit that is locked out can be unlocked using any one of the following methods Remove mains power from the unit for at least 3 seconds then restore power Issue an unlock command via Modbus RTU serial communications Reset the controller via Modbus RTU serial communications 10 Sa...

Page 13: ... s or less refer air flow graph above Consideration must be given to selecting a airflow and coil face velocity that avoids water carry over problems i e in high humidity tropical subtropical conditions or when heavily moisture laden fresh air is introduced OPA 2100RKTMF P l s Pa 5000 6000 7000 8000 9000 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 4000 N...

Page 14: ... 14 ...

Page 15: ... 15 ...

Page 16: ...dney Australian Head Office and Manufacturing Wellington Christchurch Brisbane Melbourne Adelaide Singapore Shanghai Perth Hobart Newcastle Singapore Shanghai Beijing Jakarta Hong Kong Sri Lanka Mauritius Bangalore Bangkok Hanoi Cambodia South Pacific Islands Bangladesh www temperzone biz ...

Reviews: