background image

9

76683

NOTE:  To determine the size of the branch gas line from the main gas line to the fireplace, enter the tables below (for iron
pipe or copper tubing) using the distance from the gas meter or second stage regulator to the furthest appliance on the
gas system.  Select a pipe or tube diameter which has enough capacity to meet the maximum input requirement of the
fireplace.  Regardless, do not use less than 1/2" diameter for the branch line.  For any distances required longer than
shown in these tables, refer to the National Fuel Gas Code.

NOTE:  There may be a local gas utility requirement specifying a minimum diameter for gas piping.  All units require a 1/2 inch pipe
connection at the gas valve.

Gas Line Pipe Sizing

CAPACITY OF PIPING

Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas - 0.6 (1000 BTU/Cubic Foot)

Specific Gravity for Propane Gas - 1.6 (2550 BTU/Cubic Foot)

Length

Nominal Inches for Iron Pipe Sizes (1,000s BTU/hr)

of

1/2” D

3/4” D

1” D

1

¹⁄₄

” D

1

¹⁄₂

” D

Pipe

Natural

Propane

Natural

Propane

Natural

Propane

Natural

Propane

Natural

Propane

20’

92

143

190

296

350

546

730

1135

1100

1711

30’

73

115

152

237

285

444

590

918

890

1385

40’

63

97

130

202

245

380

500

778

760

1183

50’

56

87

115

179

215

334

440

683

670

1043

60’

50

79

105

163

196

304

400

622

610

949

70’

46

71

96

151

180

280

370

576

560

872

90’

40

61

84

130

160

250

320

497

490

763

100’

38

59

79

122

150

235

305

474

460

717

Outside Diameter Copper Tubing, Type L (1,000s BTU/hr)

Tubing Length

1/2”

5/8”

3/4”

7/8”

Feet

0.43

0.545

0.666

0.785

10

110

206

348

536

20

76

141

239

368

30

61

114

192

296

40

52

97

164

256

50

46

86

146

224

60

42

78

132

203

80

36

67

113

174

100

32

59

100

154

WARNING: Use only internally tinned copper tubing. If correct copper tubing is not used, tubing can deteriorate and develop
gas leaks.

Table 1

Gas Inlet Pressure

Natural

Propane

Max.

14.0” w.c.

14.0” w.c.

Normal

7.0” w.c.

11.0” w.c.

Min.*

5.0” w.c.

10.8” w.c.

Regulator Pressure

3.5” w.c.

10.0” w.c.

*Minimum inlet supply pressure for the purpose of input adjustment.

Gas Pressure Check

The gas inlet pressure specified in Table 1 is the pressure
where the field-installed gas line connects to the gas control.
This is measured at the inlet test port on the gas valve in the
appliance.  Ensure that pressure is as shown in Table 1.

The manifold pressure is controlled by the gas valve and should
be checked at the pressure test points as shown in Figure 9 on
Page 11.  The pressure connections accept 1/4” I.D. hose or
tubing.

The pressure should be checked with the appliance burning on
high (highest setting) and all other appliances turned on.  One
must then read the manometer and if pressures are not 10.0”
w.c. for LP or 3.5” w.c. for Natural gas the inlet pressure must
be adjusted or increased until the proper pressures are at-

tained.  If these pressures are greater than 10.2” w.c. for LP or
3.7” w.c. for Natural gas, contact your gas supplier before
operating the appliance.

Pressure is tested by loosening  (do not remove) the screw in
the test port and sliding tubing onto the test port.

CAUTION:  If the appliance's operating pressures are not
checked and adjusted, improper combustion may result in
soot being produced.   Record the results of the gas
pressure check on the appropriate documents.

Testing the Gas Piping.

  Test all piping for leaks.  When

checking gas piping to the heater with gas pressure less than
1/2 psi, shut off manual gas valve for the heater.  If gas piping is
to be checked with the pressure at or above 1/2 psi, the heater
and manual shut off valve must be disconnected during testing
to prevent damage to the regulator on the unit.  (SEE WARN-
ING).

To ensure that the gas lines and connections do not have any
leaks, a pressure test should be performed.  Only a qualified
installer should perform the pressure test to ensure that
the unit is not damaged by high pressures!

WARNING:  Be sure that the gas type indicated on the
gas log rating plate concurs with the gas system in your
building.

Summary of Contents for PS24RN

Page 1: ...from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Section Provisions For Adequate Combustion and Ventilation Air Page 4 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Page 2: ...nt Safeguards 14 Flame Check 14 Managing Heat Output 15 Maintenance Cleaning 15 Troubleshooting 16 Servicing 16 Repair Parts 16 Warranty Information 19 Installation and Startup Checklist 20 Warranty Registration 22 Table of Contents Minimum Dimensions for Existing Solid Fuel Burning Fireplaces This appliance may be installed in an aftermarket permanently located manufactured mobile home where not ...

Page 3: ...ional vehicles bedrooms or bathrooms If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other household gas appliances may require the tank size to be larger Do not operate the vent free heater if the fuel level in the propane tank is below 1 4 full DO NOT use this heater if any part of it has been submerged ...

Page 4: ...e Example Space size 25 length x 25 width x 8 ceiling height 5 000 cu ft volume of space If additional ventilation from adjoining room s is supplied with grills or doorless openings add the volume of these rooms to compute the total volume of the applicable space 2 Divide the space volume by 50 cubic feet to determine the maximum BTU Hr the space can support ________ volume of space 50 cu ft Maxim...

Page 5: ...onal Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent L W D Flue Damper Closed for Unvented Operation and Maximum Heat Output Flue Damper Locke...

Page 6: ...d cause gas leaks Holes are provided just behind the front grate legs and should be used for securing the log set After locating the chassis correctly in the fireplace mark the hole positions on the fireplace floor Drill two 1 8 diameter holes approximately 1 2 deep Use the two screws to secure the chassis to the fireplace floor Fig 3 Clearances NOTE The following instructions regarding installati...

Page 7: ...plies Gas Line Connection If installation is for L P gas have L P installer use two stage regulation and make all connections from storage tank to heater Refer to the National Fuel Gas Code for the proper supply tank size with the Btu s Hr requirements If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other ...

Page 8: ...e Ground Joint Union Tee Fitting Nipple 3 Min Cap 1 8 N P T Plugged Hole for Test Gauge Gas Valve Riser Horizontal Piped Gas Supply Piped Gas Supply 1 All bends in metallic tubing should be smooth elbows are recommended 2 CAUTION Shut off the main gas supply before removing end cap to prevent gas from filling the work area Test for gas leakage when installation is complete T130 Under no circumstan...

Page 9: ... 7 0 w c 11 0 w c Min 5 0 w c 10 8 w c Regulator Pressure 3 5 w c 10 0 w c Minimum inlet supply pressure for the purpose of input adjustment Gas Pressure Check The gas inlet pressure specified in Table 1 is the pressure where the field installed gas line connects to the gas control This is measured at the inlet test port on the gas valve in the appliance Ensure that pressure is as shown in Table 1...

Page 10: ...must be positioned as illustrated The top twig may be positioned as shown in either Figure 7 or Figure 8 The top twig must be placed in the notches provided on top of the rear and center logs The front of the top twig is to rest of the large knot on the front log CAUTION Proper location is critical When positioning the log set make sure that the logs do not interfere with the sides of the fireplac...

Page 11: ...d in a location suitable to you The thermostat wire should be routed from the wall box to the log set and should be routed underneath the log set and pulled up to the valve s wiring terminal as shown in Fig 9 The two wires letter A should not be removed or changed Remove switch wires Letter B The two female ends of your wire can be connected to the two outer connections just below the screw termin...

Page 12: ...me control knob T155 T147 Fig 14 Terminal connection side view T148a Fig 15 Existing valve wiring B B A T148 Fig 16 Attach remote receiver terminals to out two connec tors A Existing valve wiring Do not tamper with B Remote receiver wires red or white on either side Side View Top View T156 Fig 17 Terminal ends ...

Page 13: ...o turn off the gas supply depress the knob slightly and turn clockwise to the OFF position 3 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 4 Refer to Figure 19 Locate the pilot It is at the right side of the burner 5 Refer to Figure 20 Push in the control...

Page 14: ...umes etc can cause burner damage and or produce strong odors If the fireplace is equipped with glass doors the doors must be fully open when the gas appliance is operating WARNING The glowing ember base and all the logs are manufactured from bonded ceramic fiber This is a commonly used material in industry worldwide In the event of the logs and base being removed care should be taken not to damage...

Page 15: ... cleaning should be carried out when the appliance is cold Only limited cleaning will be required under normal use Dusting the front grate or the control knob panel may be required occasionally Do not use any cleaning fluids to clean the logs or any other part of the appliance If the flames show any unusual shapes or behavior or if the burner s fail to ignite properly then the burner holes may req...

Page 16: ...in while Press in control knob while in pilot position in pilot position Ignitor did not spark Ignitor electrode positioned wrong Correct electrode position Ignitor electrode broken Replace assembly Ignitor cable pinched or broken Free ignitor cable if damaged replace it Ignitor cable not connected to ignitor Connect cable to ignitor 2 Pilot will not stay lit Partially clogged ODS pilot orifice Co...

Page 17: ...8 Tube Pilot 78329 78329 1 9 Valve Bracket 76388 76388 2 10 Gas Valve 55463 55462 1 11 Ignitor w Nut Piezo 65180 65180 1 12 Wire Ignitor AD Common 74017 74017 1 13 Mini Rocker Switch PCOA049 PCOA049 1 Wire Assy Rocker Switch 75435 75435 1 14 Manifold Tube Split Nut 76519 76519 1 15 Manifold Tube Split Nut 76520 76520 1 16 Injector 41 Natural 76773 1 17 Injector 49 Natural 76771 1 18 Injector 1 45 ...

Page 18: ...71867 71867 1 Lava Gravel Assy 20000198 20000198 1 Ember Coals 74511 74511 1 24 Log Kit PL24 PL24 1 27 Front Log 24 75974 75974 1 28 Middle Log 24 75973 75973 1 29 Rear Log 24 75972 75972 1 30 Twig 24 or 28 76398 76398 1 28 Log Kit PL28 PL28 Front Log 28 76839 76839 1 Middle Log 28 76840 76840 1 Rear Log 28 76894 76894 1 30 Twig 24 or 28 76398 76398 1 ...

Page 19: ...allation instructions and in compliance with local codes and ordinances The logs must be placed strictly in accor dance with the arrangement described in the installation instructions The Product must be operated and maintained according to the instructions furnished Alteration of the Product in any way is prohibited and voids any and all war ranties Removal of the data plate alters the Products a...

Page 20: ...rners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the product...

Page 21: ...burners as well as proper appearance of flames Verify that ceramic fiber and refractory components are properly positioned and secure Rear burner must not contact logs Verify adequate clearance to mantels and other combustibles Demonstrate correct operation of the product to the consumer NOTE LP models must not be operated if fuel tank is less than 1 4 full Observe the consumer operating the produ...

Page 22: ...er your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products Attn Warranty Registration 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 Model ______________________________________ I certify that I have followed all codes and regulations and adhered to the TEMCO installation instructions I have completed the proper installation and startup chec...

Reviews: