17 

 

4.1.2  Connection type 

 

In the “

Connection type

” menu the type of connection can be selected (USB or different options 

for connecting over the Internet), information can be seen about the connection process, and the 
installer and superadmin password can be changed. The default superadmin password is 

1234

If you wish to use the installer level access as well, for this the password should be configured 
separately by clicking on the “

Change Installer password

” button (for “

Actual password

” enter 

the superadmin password). 

Available options: 

  Change Installer password: 

The 

installer 

level 

password can be changed 
after clicking on this button. 

  Change Superadmin password: 

The superadministrator level password can be changed after clicking on this button. 

Enter  the  actual  password,  then  the  new  password  and 

its  confirmation,  then  click  “

OK

”. 

The password should consist of at least 4, but not more than 8 characters. 
Accepted characters are: numbers (0...9), lower case letters (a...z), and capital letters (A...Z). 
Attention! The following characters should not be used: ^ ~ < > = | $ % " '.

 

Details

: in this window you can follow the connection progress.

 

  Restart the device: 

If necessary, you can restart the connected device by clicking on this button. 

 

 

Summary of Contents for ecoLINE PRO

Page 1: ...ALLATION AND APPLICATION MANUAL for device version v2 00 Document version 2 0 16 09 2020 Product models ecoLINE PRO 2G IN4 R1 ecoLINE PRO 3G IN4 R1 ecoLINE PRO 3GA IN4 R1 ecoLINE PRO 4G IN4 R1 ecoLINE...

Page 2: ...software 9 3 2 Methods for connecting to the device 9 3 2 1 Configuring directly via USB 10 3 2 2 Remote connecting to devices via cloud service 11 3 2 3 Remote connecting to devices which are using...

Page 3: ...ier Elite alarm systems 48 5 1 4 Bentel alarm systems 51 5 1 5 Inim alarm systems 54 6 Arming and disarming the alarm control panel through the mobile application 58 7 Updating the firmware 59 7 1 Upd...

Page 4: ...artition and zone options Output control through the mobile application which can also be used to arm or disarm the connected alarm system remotely 1 2 Differences between the 2G 3G 3GA 4G and 4GA mod...

Page 5: ...ast one of the configured receivers IP addresses If the device does not receive an ACK signal from any of the configured receivers it will attempt to resend the report up to 10 times per IP address An...

Page 6: ...tion in the given input s settings In this case the input will become activated when the closed contact between the given input IN1 IN4 and the V terminal or the COM terminal becomes open 2 2 Connecti...

Page 7: ...t requires a SIM card with available mobile Internet that may use either public or private APN Installing the SIM card 1 Pull the metal security lock of the SIM holder towards the LED until you hear a...

Page 8: ...utput control If the used power source is not sufficient for the operation of the device this may cause malfunctions 2 7 LED indicator signals Slowly flashing green Normal operation connected to the m...

Page 9: ...menu found in the Software settings Settings menu where you can choose out of multiple appearance themes The software saves changes related to appearance upon closing and applies the saved settings w...

Page 10: ...ble as when connecting without a password To try a different password close the connection using the Disconnect button enter the new password and then connect again using the Connect button The softwa...

Page 11: ...ault superadmin password 1234 Device ID the device identifier of the ecoLINE PRO device to which you wish to connect The format of this unique burned in during production and thereby unchangeable devi...

Page 12: ...the message The superadmin and installer passwords are both accepted default superadmin password 1234 Example on the usage of the command mentioned above 1234 connect Send the mentioned request comman...

Page 13: ...word Changing the APN settings failed Changing the APN settings failed typing error in the message or other error Wait for the device s reply After it has confirmed that it has connected to the cloud...

Page 14: ...TEX MVP option in the Connection type section If you have registered the device in the Device register menu select the device you want to access from the Device Name drop down menu or select the serve...

Page 15: ...ct the receiver where the device is online from the Server drop down menu and enter the device identifier in the Device ID field and the connection password in the Device password field The receiver a...

Page 16: ...ng the settings options and configuring offline Using the Offline device selector it is possible to view the settings options of the ecoLINE PRO device and to configure and save the settings in advanc...

Page 17: ...radmin password Available options Change Installer password The installer level password can be changed after clicking on this button Change Superadmin password The superadministrator level password c...

Page 18: ...for storing and easy handling of device contact details used for remote programming You can add new device contact details to the database and also edit delete and clone entries for easy adding of dev...

Page 19: ...appropriate field Device ID the device identifier The format of the device identifier is for cloud usage and the TELLMon protocol FF FF FF FF FF FF 6x2 hexadecimal characters unique burned in during p...

Page 20: ...of servers or receivers with similar contact details Function buttons available in the Server register menu update the records from database add new server or receiver clone entry duplicate edit entry...

Page 21: ...er making changes in the settings write the settings into the device by clicking on the Write button The program will warn you to write the settings when leaving a page where changes have been made Ov...

Page 22: ...made in any menu Saving settings to file To save all device settings to file click on the Save to file button Loading settings from file To load saved settings from file click on the Load from file bu...

Page 23: ...y use 2G GPRS network only 3G only use 3G UMTS network only 4G only use 4G LTE network only 3G network usage is supported by the 3G A IN4 R1 and the 4G A IN4 R1 model of the ecoLINE PRO only 4G networ...

Page 24: ...h can be configured from 30 to 86400 seconds depending on the selected communication protocol Time zone in this section you can select whether the given server or receiver sends the timestamp used for...

Page 25: ...settings according to the requirements of the device alarm control panel or other device connected to the serial port of the ecoLINE PRO Available options baud rate parity and stop bits You can find f...

Page 26: ...vice To read the settings from the device click on the Read button This will read all settings in all menus Writing the settings into the device After changing the settings or entering new settings in...

Page 27: ...restore to the event automatically based on the configured input type NO NC and the input state The software includes a built in event code search tool which contains the list of standard Contact ID...

Page 28: ...output can be used for other control purpose too considering the load rating Available options Reading the settings from the device To read the settings from the device click on the Read button This w...

Page 29: ...the parameter configuration window Controlled partition the contact output can be used to arm or disarm one partition of the alarm system In this field you can configure the number of the partition y...

Page 30: ...sing the QR code In order to use the mobile application it is necessary to enable cloud usage in the Functions and permissions menu The device works with the ecoLINE PRO mobile app available for iOS d...

Page 31: ...ng to the registered mobile devices about other events e g failures of the alarm system connected to the device Input events enable Push message sending to the registered mobile devices about events g...

Page 32: ...ile device and then clicking on the Delete button If you delete a mobile device the application used on the given device will no longer access the ecoLINE PRO device 4 2 5 Functions and permissions In...

Page 33: ...usage enable this option if you want to use the device with the mobile application or if you want to access it remotely with the programming software over cloud connection If this option is enabled th...

Page 34: ...a USB Available status information Device Device ID the unique identifier of the device 6x2 hexadecimal characters This identifier is burned in during production and thereby it is unchangeable You can...

Page 35: ...the settings Number of connections the number of active connections with servers receivers Inputs Outputs IN1 IN4 the actual state of the contact inputs Output the actual state of the output OUT Repor...

Page 36: ...ing By clicking on this button the program will download the stored and will display new events as well By clicking on the arrow next to this button you can choose from the drop down menu how many eve...

Page 37: ...t code IP1 IP2 reporting to IP1 IP2 server receiver IP addresses Legend of marks shown in the IP1 IP2 columns Event reporting is in progress 2 Secondary channel No need to report because reporting thr...

Page 38: ...e changed using the dropdown menu You can choose between multiple appearance themes Software logs Extended logging for troubleshooting you can enable this option if you encounter an issue when using t...

Page 39: ...hows the availabilities of the manufacturer the version of the programming software and the path of the data folder where the software stores the logs By clicking on the path link the data folder will...

Page 40: ...serial data communication through IP connection The remote connection between the programming software of the alarm system and the alarm control panel is ensured by the ecoLINE PRO device and the Remo...

Page 41: ...vel driver interface produced for this purpose Connect the serial port output of the level driver interface to the serial port of the ecoLINE PRO then link the level driver interface with the alarm co...

Page 42: ...rial Client software and configure the settings in the order below Device ID enter the device identifier 6x2 hexadecimal characters separated by colons of the ecoLINE PRO device connected to the alarm...

Page 43: ...yware programming software For Spectra alarm control panels Baud rate 9600 baud For EVO alarm control panels Baud rate 57600 baud Start connecting Then the programming software will open the serial po...

Page 44: ...44 After you have finished remote programming the alarm control panel you can delete the created virtual serial port by clicking on the Delete port button...

Page 45: ...e ecoLINE PRO device as shown in the figure above then plug it onto the alarm control panel Software settings Configure the serial port settings in the Serial port section of the General menu in the e...

Page 46: ...arm control panel Using the Read from QR code button you can also read the device ID from the image file saved from the programming software that contains the QR code with the device ID Virtual serial...

Page 47: ...ftware will open the serial port and will establish the connection with the alarm control panel After you finished remote programming the alarm control panel you can delete the created virtual serial...

Page 48: ...er interface to the serial port of the ecoLINE PRO then link the level driver interface with the alarm control panel using the supplied special cable as shown in the figure above Configure the jumpers...

Page 49: ...the ecoLINE PRO device connected to the alarm control panel Using the Read from QR code button you can also read the device ID from the image file saved from the programming software that contains th...

Page 50: ...software Then the programming software will open the serial port and will establish the connection with the alarm control panel After you have finished remote programming the alarm control panel you...

Page 51: ...the ecoLINE PRO device as shown in the figure above then plug it onto the alarm control panel Software settings Configure the serial port settings in the Serial port section of the General menu in the...

Page 52: ...Read from QR code button you can also read the device ID from the image file saved from the programming software that contains the QR code with the device ID Virtual serial port enter the number of t...

Page 53: ...ftware will open the serial port and will establish the connection with the alarm control panel After you finished remote programming the alarm control panel you can delete the created virtual serial...

Page 54: ...e ecoLINE PRO device as shown in the figure above then plug it onto the alarm control panel Software settings Configure the serial port settings in the Serial port section of the General menu in the e...

Page 55: ...the ecoLINE PRO device connected to the alarm control panel Using the Read from QR code button you can also read the device ID from the image file saved from the programming software that contains th...

Page 56: ...ommunication port in the Ability Suite programming software in the Settings Application settings menu Example for selecting the serial communication port in the Smart League programming software in th...

Page 57: ...ith the Ability Suite programming software Start connecting with the Smart League programming software Then the programming software will open the serial port and will establish the connection with th...

Page 58: ...of the Controlled partition After doing the wiring and configuring the settings correctly to arm and disarm the alarm system activate the output of the ecoLINE PRO in the mobile application using the...

Page 59: ...e version number Open the update application and click on the FIRMWARE button Connect the device to the computer via USB Power up the device and then click on the Start button Do not power down the de...

Page 60: ...ttings using the programming software To restore the factory default settings click on the Restore factory default settings button in the Connection type menu The reset process may take more than 1 mi...

Reviews: