Telguard TG-7FP Installation & Operating Guide
19
56052401 Rev A
Compatible Alarm Panels
Any UL/ULC/cUL Listed alarm panel that supports one of the formats listed below is compatible
and may be used with the TG-7FP:
In order for the alarm panel to be compatible with the TG-7FP, the alarm panel must be programmed to
transmit alarm messages to the central station using one of the following non-extended formats:
o
Pulse Formats:
o
3+1 pulse; 10pps, Double Round, 1400 Hz ack
o
3+1 pulse; 20pps, Double Round, 2300 Hz ack
o
3+1 pulse; 40pps, Double Round, 2300 Hz ack
o
4+2 pulse; 20pps, Double Round, 1400 Hz ack
o
4+2 pulse; 20pps, Double Round, 2300 Hz ack
o
4+2 pulse; 40pps, Double Round, 2300 Hz ack
•
Contact ID
•
Modem IIe/IIIa
2
/4
•
SIA2 (SIA-DC-03 level 2 release at 300 baud)
•
Sonitrol
•
DMP
Hexadecimal account numbers can be used with 3+1 or 4+2 formats, as well as Contact ID and Modem
(4 or 10 digits for Contact ID, 4 digits for Modem).
UL Compliance Note:
While the TG-7FP supports the above formats, some formats may not meet the
requirements for fire systems set in UL 864. Contact ID and SIA2 are the only formats identified as
complying beginning with UL 864 10
th
Edition. If in doubt, check with your AHJ
.