Setup & Programming the Operating Parameters in the Telguard TG-4
When the Telguard is received from the factory and is powered up for the first time, it is immediately ready for activation, provided the default settings
are what you want (note: registration form must be sent to Telular). The STC LED # 2 will flash to indicate any failure conditions. The Mode LED # 3
will be on and the STC 1 and STC 2 relays will be tripped. If changes are required to the default settings, the Telguard can be programmed using a
line-mans butt-set connected to T & R Test Points or a POTS phone connected to the panel RJ-45 jack (black connector where the alarm panel is
normally connected).
TO PROGRAM THE Telguard TG-4
A.
Put the line-mans butt-set in talk mode or pick up the POTS phone.
B.
Connect power to the Telguard, when ready for programming you will hear 2 beeps.
C.
Press #, *, this will put the Telguard into a Master Access programming mode, 2 beeps.
D.
Enter changes required. The syntax for programming a specific memory location is as follows:
MEMORY LOCATION
(3-digits), will respond with 2 beeps, then VALUE, will respond with 2 beeps.
E.
Then press *, you will hear 2 beeps then hang up. This saves the change and exits the programming mode.
Mem Loc.
Field
Default Value
Setting
831
Mode of operation
01
1 = Telco Primary/Cellular Backup
2 = Cellular Primary/Telco Backup
3 = Cell Only
833
C/C Reporting Format
09
01 = 4x2 pulse, 40pps 2300 hz 02 = 4x2 pulse, 20pps 2300 hz
03 = 4x2 pulse, 10pps 1400 hz 04 = 3x1 pulse, 40pps, 2300 hz
05 = 3x1 pulse, 20pps, 2300 hz 06 = 3x1 pulse, 10pps, 1400 hz
07 = Radionics IIe or IIIa2 08 = Contact ID
09 = Auto Format Detect
11 = SIA2 (300 Baud)
12 = DMP
850
STC1 Trip Output
Reporting
Normally Open
04
(LFC only)
Enter the SUM TOTAL of the events that you wish to trip the STC relay by
ADDING the corresponding values:
00 = Not Used
04 = LFC
32 = DTF
01 = AC Failure
08 = NSC
63 = ALL
02 = Low Battery
16 = RFC
851
STC2 Trip Output
Reporting
Normally Closed
59
(all except LFC)
Enter the SUM TOTAL of the events that you wish to trip the STC relay by
ADDING the corresponding values:
00 = Not Used
04 = LFC
32 = DTF
01 = AC Failure
08 = NSC
63 = ALL
02 = Low Battery
16 = RFC
852
STC Trip Delay for NSC
2 (60 sec)
1=30 seconds
4=10 minutes
7=45 minutes
2=60 seconds
5=20 minutes
8=60 minutes
3=3 minutes
6=30 minutes
9=24 hours
858
STC History
N/A
0 = terminate STC history display mode
1 = start STC history display mode
2 = clear STC history
861
CFC Number of Events
0 (disabled)
0 = disabled
2 = 4 attempts
1 = 2 attempts
3 = 8 attempts
862
CFC Between Events
1 (30 sec)
1 = 30 seconds
3 = 70 seconds
5 = 90 seconds
2 = 60 seconds
4 = 80 seconds
6 = 99 seconds
868
PPF Delay
0 (disabled)
0 = disabled, 1 = 10 seconds, 2=20 seconds, … 15=150 seconds
872
AC Failure Delay
02 (2 hours)
0-24 hours
873
Trip Input Reporting
0 (no report)
0 = no report
1 = report trip
874
Trip Input Restoral Reporting
0 (no report)
0 = no report
1 = report restoral
875
Trip Input Swinger Function
0 (disabled)
0 = swinger function disabled
1 = swinger function enabled
899
Factory Default Unit
NOTE: SPECIAL LED INDICATIONS DURING ACTIVATION
If the Telguard fails to confirm activation it will be displayed on the LEDS:
System Status LEDs
Activation Indications
ALL LEDS FLASHING
FAILED ACTIVATION
– SIGNAL TOO WEAK
LED #1 & LED #4 FLASHING
ACTIVATION ERROR
– CALL TECH SUPPORT
LED #1 ON
ACTIVATION SUCCESSFUL
LED #2 OFF
NOT ACTIVATED. NEED TO CONNECT PANEL AND TRIP ZONE
On either a FAILED ACTIVATION or ACTIVATION ERROR, the unit MUST BE RESET BY PRESSING THE RSSI
BUTTON TWICE. The activation message MUST BE RESENT or the TELGUARD will transmit all signals through
the telco connection.