8
6.3
Environment Requirement
Project
Requirement
Room Space
When installing multi-row of racks, please make the distance 1.2~1.5M
between front door and back door, and the distance 0.8M between rack
and wall.
Room Floor
Non-conducting, dust-free
Ground anti-static material volume resistivity: 1×10
7
-1×10
10
, ground
current-limiting resistance: 1M
, floor bearing weight:
>
450KG/M
2
Temperature
Long-term operation: 5~40ºC, short-term operation: 0~45ºC,
air-conditioner is a good option.
Relative Humidity
Long-term operation: 20%~80%, short-term operation: 10%-90%
Ambient Pressure
86-105KPa
Doors and Windows
Seal by dust-prevention rubber strip, double glass is a good option for
window and seal it tightly.
Fire Requirement
Automatic fire alarm system and hand-held fixed fire extinguish system
are required.
Power Requirement
3 stand alone power supply system for equipment, air-conditioner, and
lighting. Alternating current power supply for equipment (220V, 50Hz,
24.2W). Please check before running the device.
Signal
connection
System
setting
Run
device
Inspection
Fix
device
Power cable and ground
wire connection