background image

 

 

TFH-280A 

© 2010

 

 

2012 Telefire Fire & Gas Detectors Ltd 

 

Revision 1.01   January 2012 

 

– Page 3 of 4 – 

3.3 

Post-Installation – Field Test 

Perform a field test (also known as "Walk Test") to ensure that all detectors function 
properly.  Please see the control panel's manual for a detailed explanation on how to 
perform a field test. 
Testing is automatic other than the activation of the detector that is done manually by 
putting a magnet next to the detector's test point.  See section  4.1.1 for a detailed 
explanation on how to perform the test. 
Ensure that the detector functions properly and is included in the necessary activation 
matrices. 

   Warning    

Do not apply naked flame to the detector! 

3.4 

Documentation 

Mark the detector's address on the label. 

Maintenance 

The ADR-3000 control panel monitors the analog detectors continuously.  Any abnormal 
condition in the detector will cause a trouble signal to be displayed on the control panel. 

4.1 

Periodic Testing 

Fire alarm systems should be checked periodically.  Please refer to NFPA and local fire 
codes to determine service frequency. 
Use the control panel’s Walk Test mode to perform automatic reset.  Please refer to the 
control panel’s manual for additional details on how to perform Walk Test. 

4.1.1  Test Procedure – Locally 

1.  Apply a magnet to the side of the detector next to the LED for 3 – 5 seconds.  This 

activates an internal testing circuit that simulates presence of alarm temperature in 
the detector, tests the sensing mechanism and the detector's electronic circuit. 

   Warning    

Do not apply naked flame to the detector! 

2.  The analog value representing the temperature will be transmitted to the control 

panel for evaluation.  The control panel will transmit a signal to the detector to turn 
on its LED.  During the test the detector’s values may be observed at the control 
panel.  Please refer to the ADR-3000 manual for additional information. 

3.  Once the detector is in alarm mode, it keeps the alarm condition until reset by the 

control panel.  If the control panel is in "Walk Test" mode, it will reset the alarm after 
a few seconds.  Please refer to the ADR-3000 manual for instructions on how to 
conduct a walk test. 

4.1.2  Test Procedure – From the Control Panel  

It is also possible to test the detector using the ADR-3000’s “Monitor” option menu.  
Please refer to the ADR-3000 manual for instructions on how to use and interpret the 
monitor screen. 

Reviews: