Telefire LI-3000 Technical Manual Download Page 3

 

 

LI-3000 / LI-3000E 

© 1999

 

 

2015 Telefire Fire & Gas Detectors Ltd 

 

Revision 1.14   May 2015 

 

– Page 1 of 6 – 

Introduction 

The LI-3000 and LI-3000E short-circuit line isolators are intended for use in the signaling 
line circuit (SLC) of Telefire's addressable control panels. 
The devices are connected to and powered by the SLC and are used to protect against 
short circuit by disconnecting the short circuit from the rest of the SLC. 
The LI-3000 requires an address that is set by the PROG-4000 device programmer. 
The LI-3000 and LI-3000E enable wiring the SLC Loop in a closed loop (NFPA Style 6 
Class A) as well as branching T-shaped (NFPA Style 4 Class B) wiring configuration. 
Class A configuration does not reduce system capacity.  To establish an NFPA Style 6 
Class A loop in an ADR-3000 requires a minimum of 3 LI-3000 per loop. 
Each SLC Loop is capable of addressing 127 devices, including the addresses occupied 
by the LI-3000 modules.  A single-loop line card that is configured as Class A can 
address up to 127 addresses (including LI-3000 line isolators), and a dual-loop line card 
can address up to 254 addresses (including LI-3000 line isolators) in two Class A loops. 

Compatibility 

The LI-3000 and LI-3000E are compatible with the full range of Telefire's addressable 
control panels and addressable devices. 

Application 

3.1 

Characteristics 

After power up or reset of the system, the isolator checks for short-circuit condition.  If no 
short-circuit is detected the isolator switches the circuit on and enables normal operation 
of the second connection of the SLC Loop. 
Whenever a short-circuit condition occurs the Isolator opens the circuit automatically and 
disconnects the faulty side of the loop.  Three seconds later it resets and performs a 
second test, and then again a minute later.  It repeats the test for eight minutes, and 
then periodically it will re-test every two minutes.  The test cycle restarts when the 
module is reset. 
The yellow LED flashes each time the module is addressed by the control panel.  A 
short-circuit condition will cause the LED of the shorted side to latch on. 
An open circuit in a Class A configuration will send a trouble message to the control 
panel.  The LI-3000 will latch on the LED corresponding to the open side. 
As many as 20 Isolator modules can be installed in each SLC Loop. 

3.2 

Class A Configuration 

Configuring a loop as Class A does not reduce loop capacity, other than the addresses 
used by the short circuit line isolators themselves – each loop is still able to work with 
127 addresses. 

   Note    

Short circuit line isolators model LI-3000 have an address and report of a 
disconnection on one of the sides to the control panel. 
LI-3000E line isolators do not have an address.  The control panel will report 
missing devices in case of disconnection. 

Summary of Contents for LI-3000

Page 1: ...Technical Manual TELEFIRE FIRE GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel 972 3 970 0400 Fax 972 3 921 1816 eMail info telefire co il Web www telefire co il LI LI LI LI 3000E 3000E 3...

Page 2: ...line and UL standards and Fault as used in EN 54 standards are used interchangeably throughout this manual i Note Do not install operate and maintain this LI 3000 or LI 3000E before fully reading this...

Page 3: ...ble devices 3 Application 3 1 Characteristics After power up or reset of the system the isolator checks for short circuit condition If no short circuit is detected the isolator switches the circuit on...

Page 4: ...r LI 3000 or LI 3000E Other LI 3000 modules shall have the jumper in place In ADR 3002C dual loop line cards both loops shall be Class A or both loops shall be Class B this definition is done for each...

Page 5: ...e temporary disconnected before adding devices to a control panel Measure the wiring to ensure there are no shorts before connecting the wiring to the control panel Connecting or adding devices to a c...

Page 6: ...nable key again to switch between Class A and Class B again To disable the line card press the Disable key To add an Isolator module to the system select the manual device programming screen in the co...

Page 7: ...Ltd Revision 1 14 May 2015 Page 5 of 6 Figure 3 LI 3000 and LI 3000E Line Isolation Modules Figure 4 Connecting an LI 3000E in a raised base 4 3 Post Installation Tests Test that the system still work...

Page 8: ...4 0 mA during short or open 5 2 LI 3000E Module PCB Dimension W H 25 75 mm AIB 800 Dimensions W H D 133 119 36 mm Operating Temperature Range 10 C 60 C 14 F 140 F Relative Humidity Range 10 93 non con...

Reviews: