INSTALLATION
4-26
USE AND DISCLOSURE OF DATA
Information contained herein is classified as EAR99 under the U.S. Export Administration Regulations. Export, reexport or diversion contrary to U.S. law is
prohibited.
The duct mount fitting comes in a kit that designed for either flat or round applications. Either application uses most
of the parts in the kit. The exceptions include: one (1) flat washer (2F) used for flat duct applications; two (2) curved
washers (2C & 6C) used for round duct applications.
Follow the instructions below to install the duct mount fitting.
1. Assemble the duct mount fitting properly for the particular duct application prior to tightening the locking nut. The
locking nut digs into the washer for a lasting grip. Refer to
2. Once assembled, position the duct mount fitting onto a duct and mark its position.
3. Remove the fitting and drill 1¾” diameter hole.
4. Position the fitting back on the duct over the 1¾” hole.
5. Using a drill, insert the 4 self-piercing sheet metal screws into place.
6. Next, align pins on the sensor body with slot on the body of the duct mount fitting and turn clockwise to seat.
Refer to
Attaching the Meridian Sensor to the Duct Mount Fitting
Figure 4-13: Attaching the Meridian Sensor to the Duct Mount Fitting
NOTE: Only use with devices configured for remote sensor and without Meridian junction box
assembly.
NOTE: For round duct applications, curve the flat plate (4) by hand to conform to different duct
shapes.