WB Interface   

WB/4-20mA CONVERTER 

 

 

USER MANUAL 

 

NPMWBEN  

Revision A.0 

 

2

 

PRESENTATION  

2.1

 

Purpose of the MX32v2 controller 

The WB interface is:

 

 

 

equipped  with a compact  (58x105x90 mm) "NORYL" case. Clipping  on to a standardised 
symmetrical DIN rail, it can easily be integrated into an electrical cabinet; 

 

equipped with two identical measuring channels; 

 

equipped,  for each channel, with an analog input (supply of steady current delivering a 
signal in mV to a catalytic  sensor) and a corresponding 4 to 20 mA current output; 

 

the elements required for use are grouped together on the front of the apparatus: 

-

 

at the top for the settings and tests (Figure 1/Ref.1), 

-

 

on the FRONT panel for the indicator  lights (Figure 1/Ref.2), 

-

 

at the bottom  for the connections (Figure 1/Ref.3). 

 

 

Figure  1 

 

 

Summary of Contents for MX32v2

Page 1: ...NP32V2EN Revision D 0 NPMWBEN Revision A 0 WB INTERFACE WB 4 20mA CONVERTER...

Page 2: ...he reproduction of all or any section of this document in any form whatsoever without the written permission of TELEDYNE OLDHAM SIMTRONICS S A S is forbidden The information contained in this manual i...

Page 3: ...truction of the equipment Erreu r Signet non d fini 2 PRESENTATION 4 2 1 Purpose of the MX32v2 controller 4 3 MOUNTING THE CENTRAL UNIT 5 4 CENTRAL UNIT ELECTRICAL CONNECTIONS 6 4 1 DC supply 6 4 2 Fl...

Page 4: ...WB Interface WB 4 20mA CONVERTER USER MANUAL IV NPMWBEN Revision A 0...

Page 5: ...time In case of doubt contact TELEDYNE OLDHAM SIMTRONICS for additional information The aim of this manual is to supply simple and accurate information to the user TELEDYNE OLDHAM SIMTRONICS cannot b...

Page 6: ...precautions of use have been placed on the unit in the form of pictograms These labels are considered an integral part of the unit If a label falls off or becomes illegible please ensure it is replace...

Page 7: ...uch damage 1 6 Warranty Under normal conditions of use and on return to the factory parts and workmanship carry a one year warranty excluding consumables such as backup power supplies audio and visibl...

Page 8: ...trical cabinet equipped with two identical measuring channels equipped for each channel with an analog input supply of steady current delivering a signal in mV to a catalytic sensor and a correspondin...

Page 9: ...on A 0 5 3 MOUNTING THE CENTRAL UNIT The WB interface is mounted on its symmetrical DIN rail and can be fitted in any enclosed electrical cabinet without the need for any special installation It must...

Page 10: ...t conform to standard NF C 15 100 The wires to be connected to the WB interface will have a maximum section of 2 5 mm The WB interface is powered with a 24 V direct current DC supply 4 1 DC supply 24...

Page 11: ...e maximum loop resistance is 16 ohms Example the maximum distance between the WB interface and the sensors will be 500 m with 1 5 mm section conductors 4 3 The 4 20 mA output The 4 20 mA output of eac...

Page 12: ...the WB interface is powered up it is ready for use and the GREEN light emitting diode is lit Figure 1 Ref 4 5 2 Switching off The device is switched off essentially by shutting down the power supply a...

Page 13: ...4 Ref 4 channel 2 The voltmeter should read 40 mV N B Onceset the corresponding 4 20 mA output will deliver 4 mA maintenance switch in normal position 5 3 2 Adjusting the gas span Necessary when chang...

Page 14: ...the value to be set and read on the voltmeter will be U 40 mV 160 mV x 2 5 5 40 mV 80 mV 120 mV In this specific case once set and with the gas the 4 20 mA output will deliver 12 mA maintenance switc...

Page 15: ...or 2 test amber Electrical power supplies DC 21 5 to 30Vdc Consumption 15W Protection fuse Measurement line Cable 3 conductors Maximum line length 500 m with 1 5 mm conductor Maximum loop resistance 1...

Page 16: ...replacement Fuse replacement should only be performed by qualified personnel and power must be first switched off Fuses shall comply with IEC 60127 standard time delay fuse low breaking capacity 250Va...

Page 17: ...WB Interface WB 4 20mA CONVERTER USER MANUAL NPMWBEN Revision A 0 13 8 Certificate of Compliance The document hereafter 1 page reproduces the EU declaration of conformity...

Page 18: ...WB Interface WB 4 20mA CONVERTER USER MANUAL 14 NPMWBEN Revision A 0...

Page 19: ...WB Interface WB 4 20mA CONVERTER USER MANUAL NPMWBEN Revision A 0 15...

Page 20: ...erved NPMWBEN Revision A 0 June 2021 AMERICAS 14880 Skinner Rd CYPRESS TX 77429 USA Tel 1 713 559 9200 EMEA Rue Orfila Z I Est CS 20417 62027 ARRAS Cedex FRANCE Tel 33 0 3 21 60 80 80 ASIA PACIFIC Roo...

Reviews: