![TELEDYNE OLDHAM SIMTRONICS Everywhereyoulook DG-TT7-S Operating Manual Download Page 15](http://html1.mh-extra.com/html/teledyne-oldham-simtronics/everywhereyoulook-dg-tt7-s/everywhereyoulook-dg-tt7-s_operating-manual_1081077015.webp)
MULTITOX DETECTOR
OPERATING MANUAL
NOSP17668
Revision 03
a
9
2
Techical features
GENERAL
Type
Gas detector
DGi-TT7-E
MultiTox (electrochemical for toxic components)
DGi-TT7-O
MultiTox (electrochemical for measurement of oxygen)
DG-TT7-S
MultiTox (semi-conductor for toxic components)
DGi-RT7 / DG-RT7
Network detector
Calibration
A test is recommended every 3-4 months on DGi -TT7-E and
DGi-TT7 and every 6 months on DG-TT7-S.
OUTPUT SIGNALS
Loop 4-20mA signal
Type active (source) maximum load impedance 700
Ω
« 4-20mA » format
4-20mA with one fault level
(Factory set)
0% full scale 4 mA
100% full scale 20 mA
105% full scale 20.8 mA
Fault or inhibition 1.5 mA
« 0-22mA » format
4-20mA with several fault levels, for PLC and some recent
control units
0% full scale4 mA
100% full scale20 mA
>105% full scale20.8 mA
Inhibition 3.4 mA
Fault measure2.6 mA
Device fault (HW/SW)2.0 mA
Output relays
3 x configurable relays max 1.7A / 30V
AC/DC (
optional)
1
These frequencies of calibration control are provided for information purposes only. The frequency depends on
the operating conditions, the experience and safety requirements.
2
This value changes to 1A when the security function uses the relays and the SIL level is required
Summary of Contents for Everywhereyoulook DG-TT7-S
Page 32: ...MULTITOX DETECTOR OPERATING MANUAL 26 NOSP17668 Revision 03a ...
Page 34: ...MULTITOX DETECTOR OPERATING MANUAL 28 NOSP17668 Revision 03a ...
Page 47: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 41 ...
Page 54: ...MULTITOX DETECTOR OPERATING MANUAL 48 NOSP17668 Revision 03a ...
Page 58: ...MULTITOX DETECTOR OPERATING MANUAL 52 NOSP17668 Revision 03a ...
Page 60: ...MULTITOX DETECTOR OPERATING MANUAL 54 NOSP17668 Revision 03a ...
Page 69: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 63 10 Declaration of conformity ...
Page 70: ...MULTITOX DETECTOR OPERATING MANUAL 64 NOSP17668 Revision 03a ...
Page 71: ...MULTITOX DETECTOR OPERATING MANUAL NOSP17668 Revision 03a 65 ...