TELEDYNE OLDHAM SIMTRONICS recommends using pure gases: using mixed
gases can alter the accuracy of gas measurements due to cross interferences between
the sensors.
The calibration gas concentration value shall be between 15% and 100% of the
measurement range.
6.3.3
Date and Time Settings
•
From the
Maintenance menu (Figure 38), select
the option
Update the BM 25A/AW date and
time from a PC.
•
Click
OK to validate and exit.
Figure 43: the
Time Settings
menu
6.3.4
Monitoring Report menu
Follow the steps below:
•
From the
Maintenance menu (Figure 38),
select
’Checking card’.
•
Fill in the fields (user's information for
instance)
•
Create the monitoring report (.ctr file)
•
From the PC (
COM 2100 files) open the
files to edit or print.
Figure 44: the
Monitoring Report
menu
Example:
Step 1
Step 2 and 3