background image

Heat test 

 
Use a hair dryer of 1000-1500 W or an heat tool from an approved manufacturer. Direct the heat towards the sensor from its side. 
Hold the heat source at about 15 cm away from the sensor in order to prevent damage to its cover during testing. 
The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LED should be activated 
by the control panel itself.

 

CAUTION 

 
Dust  covers  help  to  protect  the  devices 
during  shipping  and  when  first  installed. 
They  are  not  intended  to  provide  complete 
protection  against  contamination,  therefore, 
detectors  should  be  removed  before  con-
struction,  major  re-decoration  or  other  dust 
producing  work  is  started.  DUST  COVERS 
MUST BE REMOVED BEFORE THE SYSTEM 
CAN BE MADE OPERATIONAL. 

 WARNING 

 

Disconnect loop power before installing the 

detector. 

5.

 When the detector is firmly engaged verify the alignment 

between the detector and the raised reference marks on the 
base (figure 7). 
 

6.

 After all detectors and other loop devices have been 

installed, apply power to the loop in accordance with the 
control panel’s installation instructions. 
 

7.

 Test the detectors as described in the section headed 

“TESTING”.

 

1.

 Position the detector centrally 

on its mounting base (

ensure it is 

level

). 

2.

  Rotate clockwise applying 

gentle pressure. The detector will 
drop into its keyed location. 

3.

 

Press more firmly

 to win the 

force of the contacts. 

4.

 Continue to rotate clockwise a 

few degrees until the detector has 
fully engaged in the mounting 
base. 

ANTI-TAMPER MECHANICAL BLOCK FEATURE 

 
The detector may be locked onto its base by remov-
ing the small plastic element on the base’s detector 
blocking hook by using a suitable tool (e.g. a small 
screwdriver) inserted through the access hole on 
the side of the mounting base (figure 6). 
To remove the detector from the base, if mechani-
cally blocked, insert a suitable tool (e.g. a small 
screwdriver) through the access hole on the side of 
the mounting base (figure 6). 

Figure 6 - The anti-tamper block and its handling. 

TAMPER DETECTION 

 
A fault condition is triggered on the  protocol compatible control panel if a detector, on the loop, is removed from its mounting base.

 

TESTING 

 
Detectors should be tested after installation and during periodic maintenance visits (it is recommended each device should be tested 
at least once per year). When the system has been reset, allow at least one minute for power stabilisation. 
Detectors can be tested as follows: 

If the detector does not respond to the tests correctly it may be necessary to clean it: in this case follow the instructions indicated in 
the “MAINTENANCE” paragraph. 
 

If testing fails again after maintenance then replace the detector with a new one and return the faulty one for servicing. 

Alignment between the detector and 
the base’s reference raised marks. 

Figure 7 - The correctly installed detector. 

Magnet test position (model TMD-01). 

MAINTENANCE 

 
Before starting any maintenance work, isolate and disable the system in order to avoid accidental and unwanted alarm or fault condi-
tions. Remove the detector from its mounting base to allow inspection in good light at ground level. Inspect the thermistor area; use a 
small, soft bristle brush to dislodge any evident contaminants such as insects, spider webs, hairs, etc. Use a small vacuum tube or 
clean, dry and compressed air to suck up or blow away any remaining small particles from the thermistor area. 
Wipe the exterior housing of the detector with a clean, damp, lint free cloth to remove any surface film that can later attract airborne 
contaminants. After all detectors have been inspected, repositioned on their mounting bases and power has been re-applied, check 
correct operation as described under the “TESTING” paragraph. 

 

WARNINGS AND LIMITATIONS

 

 
Our devices use high quality electronic components and plastic materials that are highly resistant to 
environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace the 
devices in order to minimize the risk of reduced performance caused by external factors. Ensure that this 
device is only used with compatible control panels. Detection systems must be checked, serviced and 
maintained on a regular basis to confirm correct operation. 
Smoke sensors may respond differently to various kinds of smoke particles, thus application advice 
should be sought for special risks. Sensors cannot respond correctly if barriers exist between them and 
the fire location and may be affected by special environmental conditions. 
Refer to and follow national codes of practice and other internationally recognized fire engineering stan-
dards. 
Appropriate risk assessment should be carried out initially to determine correct design criteria and up-
dated periodically. 
 

WARRANTY

 

 
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manu-
facturing defects, effective from the production date indicated on each product. 
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling 
or usage. 
Product must be returned via your authorized supplier for repair or replacement together with full informa-
tion on any problem identified. 
Full details on our warranty and product’s returns policy can be obtained upon request. 

TELEDTA S.R.L. 

Via Giulietti, 8 
20132, Milano 

Italy 

 
  
  

EN 54-5 
Point type heat detector 
Class A1R and B (class P) 
 
SF3500E 
 
Technical data: see docu-
ment TDS-LV350  held by 
the manufacturer. 

  

Figure 4 -   adaptor base with shorting clip and  deep adaptor base 
with shorting clip loop wiring. 

Figure 5 -  Universal adaptor base with shorting clip and deep 
adaptor base with shorting clip loop wiring. 

TELEDATA S.R.L.

 - Via Giulietti 8a, 20132, Milan, Italy 

www.Teledata-i.com 

  

L20-LV350-4001 (v2.1) 

   

Reviews: