Demarcation Fuse/Circuit Breaker Alarm Panel
Power :: Model 125DM08
1. If necessary, to move or replace the 19-in. brackets, remove the three screws on the sides of the breaker
panel, as shown in Figure 2.
2. Install 19-in. or 23-in. brackets for flush or extended panel presentation on rack.
3. Locate an unused rack position and mount panel using the four thread-cutting screws provided, as shown
in Figure 3.
4. Tighten the screws to 35 in.-lb (4.29 N•m).
5. Use a UL/NRTL-approved crimping tool to attach a UL/NRTL-approved, 2-hole compression lug (fit 1/4-20
dual studs on 5/8 in. centers) onto a #10 to #2 AWG ground wire. (The size of the ground wire depends on
size of input BATT wires.)
6. Attach the opposite end of the ground wire to the relay rack, per local practices.
Figure 3 - Bracket Orientation
Figure 4 - Rack Mounting