High-Power GMT Series Fuse Panels
Models 0HPGMT Installation Guide
© Telect, Inc. All rights reserved. 5.1.17 130316-7
1.509.926.6000 :: telect.com
10
1”
1 1 /4 "
(3” for FFA)
1 3 /4 "
(3 1/2” for FFA)
19” OR 23”
1” (19” RACK)
3” (23” RACK)
FRONT OR REAR PANEL
1.4 Installation Procedures
!
ALERT
ALERT! Install this product within a restricted access location where access is through the use of a tool,
lock and key, or other means of security and is controlled by the authority responsible for the location. Only
qualified personnel may install and maintain this product.
!
ALERT
ALERT! Verify all connections meet requirements specified in local electric codes or operating company
guidelines before supplying power. Protect this equipment with a fuse or breaker sufficient to interrupt power
levels specified under Electrical Specifications, on page 4.
!
ALERT
ALERT! Each panel is tested at the factory. Telect recommends you perform the testing outlined in the
following installation procedure to ensure that no damage has occurred during shipping and handling.
Both sides A and B input circuits, as applicable, need to be tested.
1.4.1 Installing the Panel
Except for Dual-Circuit 20/20 GMT Panels, brackets are provided for either flush or extended EIA or WECO
mounting in a 19" or 23" rack. Dual-Circuit 20/20 GMT Panels must be mounted to a 23" EIA or WECO rack.
1. Locate an unused rack position and mount panel using four 12- to 24-thread cutting screws, washers and
starwashers provided, as shown in Figure 6.
2. Tighten the screws to 35 in.-lb (4.29 N·m).
MOUNTING BRACKETS
Figure 6 - Mounting Dimensions
3. Remove the see-through cover.