6

RAIN sensor

1.1

3.2

L1 ON

Factory setting 

ACTIVATED

ALARM ACTIVATED when

What happens with ALARM ACTIVATED

ALARM NOT ACTIVE when

The sensitive surface of the sensor 

detects drops of water.

The control unit completely 

CLOSES

 the pergola slats. 

The control unit executes 

no command

.

The sensor doesn’t detect any drop.

System operation AFTER rain alarm (draining of water) 

DIP3=OFF

: once the rain alarm has ended, for the following 

6 hours

 the control unit, upon receiving an automatic movement command from the transmitter, will tilt 

the pergola slats to 

33%

 to allow water to drain off. For 

4 minutes

 the control unit can only execute hold-to-run commands, thereby exiting from the alarm status.

DIP3=ON

: once the rain alarm has ended, after 20 minutes the control unit will automatically tilt the pergola slats to 

33%

 to allow water to drain off. For 

4 minutes

 

the control unit can only execute hold-to-run commands, thereby exiting from the alarm status.

Activation/

deactivation of the 

RAIN sensor

Deactivation

Press the “

STOP

” button of a 

memorized 7/42 or 3-channel 

transmitter for 

10 s. 

The buzzer emits 

2 beeps

.

Activation

Press the “

STOP

” button of a 

memorized 7/42 or 3-channel 

transmitter for 

10 s. 

The buzzer emits a continuous 

sound for 

4 seconds

.

STOP

(10 s)

continuous 

sound 4 s

STOP

(10 s)

ATTENTION:

 the deactivation of the sensor has 60 minutes duration.

RAIN

WIND sensor

1.1

3.1

The anemometer (

ANEM4

) detects wind speed, which the control unit compares with the threshold set through 

DIP4

 (see table). 

The control unit is only compatible with anemometers generating 4 pulses per rev.

ACTIVE ALARM when

Once ACTIVE ALARM

DEACTIVATED ALARM when

The measured speed is higher then 

the set threshold (see the table).

The control unit moves the louvres to the 

50%

 of complete 

opening and it 

doesn’t execute any command

L2 

flashes. 

The sensor measures a speed lower than 

the set threshold for at least 30 seconds.

DIP4 Km/h

OFF

45

ON

60

WIND

Alarm priority

HIGH

L2 flashes

Factory setting 

ACTIVATED

Summary of Contents for TVPLS916CTS1

Page 1: ...opying rights M 24Vdc DOC T691 02 TVPLS916CTS1 DATE 03 10 16 24V CONTROL UNIT WITH RADIO RECEIVER TO CONTROL ONE 24V MOTOR FOR ADJUSTABLE SLATS Inputs for rain and wind sensors Product code TVPLS916CT...

Page 2: ...on centre for waste electrical and electronic equipment Hereby Teleco automation s r l declares that the product complies with the essential requirements and other relevant provisions establishedbythe...

Page 3: ...BUTTONS CH5 CH6 CH7 Open STOP Close 3 18 channel transmitter 2 channel transmitter OPEN STOP CLOSE or CLOSE CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH5 CH6 CH7 OPEN STOP CLOSE or CLOSE OPEN STOP CLOSE or CLOSE C...

Page 4: ...ON P1 A 1 BUTTON 1x Press the button of the transmitter relative to the code to memorize B AUTOMATIC COMMANDS 2 or 3 BUTTONS 2x Press the button of the transmitter relative to the code to memorize A 1...

Page 5: ...es the button P3 of the memorized transmitter The buzzer emits a slow intermittent sound Press the button relative to the code to delete within 5 seconds The buzzer will stop sounding 1 1 2 4 2 5 Remo...

Page 6: ...ld to run commands thereby exiting from the alarm status Activation deactivation of the RAIN sensor Deactivation Press the STOP button of a memorized 7 42 or 3 channel transmitter for 10 s The buzzer...

Page 7: ...z Radio memory capability transmitters 16 Rain sensor power supply 12V max 100mA Anemometer 4 pulses rotation ANEM4 Protection rating IP54 Material of the box and its cover Not suitable for direct UV...

Page 8: ...mation France France Tel 33 0 472 145080 Fax 33 0 472 140503 info telecofrance com Teleco Automation GmbH Germany Tel 49 0 8122 9563024 Fax 49 0 8122 9563026 info de telecoautomation com www telecoaut...

Reviews: