GB

40

INSTALLATION

BATTERY CHARGER CB24 (optional)

ELECTRICAL CONNECTIONS

The equipment must be installed "PROFESSIONALLY" by personnel with qualifications as envisaged by current legislation and in compliance with the
standards EN 12453 and EN 12445 governing safety of the automation.
- Ensure that the automation is equipped with end stops and that these are correctly sized to suit the overall weight of the gate.
- Fix the control unit on a flat and immobile surface, suitably protected against the risk of impact and flooding.

For connections, refer to table 1 and figure 2.
In the case of existing systems a general check should be made of the condition of wiring (section, insulation, contacts) and auxiliary equipment
(photocells, receivers, pushbutton panels, key-operated switches etc.).
Anumber of recommendations for a correct electrical installation are listed below:
- wiring entering the sealed box of the control unit must maintain, when possible, the initial protection rating of IP56.
- The section of the cables must be calculated on the basis of their length and maximum current.
- Do not use a single “multi-pole” type cable for all connections (line, motors, controls etc.) or in common with other equipment.
- Divide the system into at least two sections, for example:
1) power section (power supply line, motors, flashing light, courtesy light, electric lock) minimum wire section 1.5 mm2 (motor line 2.5mm2).
2) signal section (controls, safety contacts, auxiliary power supply) minimum wire section 0.75 mm2
- When very long control cables are used (over 50 metres) decoupling is recommended by means of relays installed in the vicinity of the control unit.

- All N.C. inputs (normally closed) not used in the control unit must be shorted with the common.
- All N.C. contacts associated with the same input must be connected in series.
- All N.O. contacts (normally open) associated with the same input must be connected in parallel.
- For the control unit power supply, the INSERTION OF AN EXTERNAL DISCONNECT SWITCH (not supplied) is envisaged, which must be
independent and sized according to the load.

A system with the T224 can also operate in the event of a power failure, by the insertion of two 12V 2.2Ah rechargeable batteries (not supplied) and a
battery charger model CB24, all without modifications to the rest of the system.
It is recommended, in the case of new systems, to connect the battery and battery charger after testing, observing figure 2 and taking special care to
observe wire polarity.
Connection sequence:
- shut off the 230V power supply
- connect terminals 3 and 4 of the CB24 to terminals 28 and 29 of the control unit T224.
- connect the 2 batteries (in series) with the wires supplied to terminals 1 and 2 of the battery charger.
- ensure that the control unit is powered correctly.
- restore the 230V power supply

- New batteries reach full charge status after approx. 10 hours.
- The number of possible manoeuvres when battery-operated depends on many factors;
as a guideline, around 4 complete cycles are possible in the following conditions:
- gates of 150Kg per leaf
- system with 2 pairs of photocells, plug-in receiver and 1 flashing light (20W max.)
- batteries fully charged
- within 5 hours of failure of the 230V power line
- The control unit slows down the flashing status of the flashing light output in the following condition: battery operation with 230V power
failure.

Summary of Contents for T224

Page 1: ...STIMMT CETTE NOTICE S ADRESSE DES TECHNICIENS SP CIALIS S DANS L INSTALLATION EL PRESENTE FOLLETO EST DESTINADO AL PERSONALT CNICO ESPECIALIZADO EN INSTALACIONES DEZE HANDLEIDING IS BESTEMD VOOR VAKBE...

Page 2: ...necorsa cancelli a singola anta con o senza finecorsa cancelli a doppio scorrevole con finecorsa cancelli a singolo scorrevole con finecorsa La centralina dotata di controllo motore a encoder e o ampe...

Page 3: ...gresso chiuso led spento ingresso aperto 19 Dip switch funzioni 20 Reset centralina cortocircuitare per un attimo i 2 pin equivale a togliere e ridare alimentazione alla centralina 23 Connettore per i...

Page 4: ...ltolunghe oltrei50metri consigliabileildisaccoppiamentocondeirel montativicinoallacentralina TuttigliingressiN C normalmentechiuso chenellacentralinanonvengonoutilizzatidevonoesserecortocircuitaticoni...

Page 5: ...Elettro Serratura 24Vcc 24Vcc 24Vcc 24Vcc 24Vcc 12Vcc Lampeggiante Spia cancello aperto COSTA APRE FT2 FT1 JOLLY 4 JOLLY 1 JOLLY 3 JOLLY 2 STOP P P PEDONALE Alimentazione fotocellule con Foto test ve...

Page 6: ...zzato Vedi modo ingressi Jolly tab 2 dip switch n 3 e 4 Vedi modo ingressi Jolly tab 2 dip switch n 3 e 4 Vedi modo ingressi Passo Passo e Pedonale tab 2 dip switch n 1 e 2 Vedi dip switch funzioni n...

Page 7: ...rallentamento Durantelafasediapprendimentosiazioner pi volteiltasto part 1 difig1 inalternativasipu usareilcomando morsetto22 fig 2 oppure iltrasmettitoreradiomemorizzatosulprimocanaledelricevitore Ne...

Page 8: ...ipetere l autoapprendimento posizionandoleanteinmodocheriescanoachiudereper5secondisenzaincontrarelabattuta se succede questo IMPORTANTE anche durante questo movimento le ante non devono andare contro...

Page 9: ...e il pulsante P P quando l anta con M2 arriva nella zona desiderata di rallentamento Per evidenziare e confermare la registrazione il motoreM2sifermaperunattimoeriparteinapertura 18 Quandoledueanteson...

Page 10: ...rizzareiltempopausa IlledLD3sispegneelacentraleescedallaprogrammazione Procedura 1 Bloccare il cancello leggermente aperto 2 Tenendo premuto il pulsante Prog effettuare un reset cortocircuitando col c...

Page 11: ...TAB 2 I 11...

Page 12: ...g 1 Alimentarelacentraleeattenderecheiledsullariceventesispengano Sulla ricevente premere brevemente il pulsante del canale da memorizzare P1 passo passo o P2 pedonale il led corrispondente inizia a l...

Page 13: ...nodeifermimeccanicidiadeguatarobustezzaafineaperturaefinechiusuradelleante Verificarelostatodieventualicavigi presentinell impianto Fareun analisideirischidell automazioneediconseguenzaadottarelesicur...

Page 14: ...rse portails un vantail avec ou sans fin de course portails deux vantaux coulissants avec fin de course portails un vantail coulissant avec fin de course La logique de commande est munie de contr le m...

Page 15: ...e lectrique 13 Touche pour Programmation et Stop 14 Touche P3 programmation temps de Pause 15 Touche Pas pas P P 16 Led Programmation LD3 17 Bornier pour connexion commandes et s curit s 18 Led de sig...

Page 16: ...ntrant dans le coffret tanche de la logique de commande doivent tre install es sans compromettre si possible le degr de protection IP56 La section des c bles doit tre calcul e suivant leur longueur et...

Page 17: ...rique 24Vcc 24Vcc 24Vcc 24Vcc 12Vcc Clignotant 24 Vcc Voyant portail ouvert BARRE P ALPEUSE OUVERTURE PHOTOCELL 2 PHOTOCELL 1 JOLLY 4 JOLLY 1 JOLLY 3 JOLLY 2 STOP P P PI TON Alimentation Photocellules...

Page 18: ...si elle n est pas utilis e Voir mode entr es Jolly tab 2 dip switch n 3 et 4 Voir mode entr es Jolly tab 2 dip switch n 3 et 4 Voir mode entr es Pas pas et Pi ton tab 2 dip switch n 1 et 2 Voir dip s...

Page 19: ...tissement Durantlaphased apprentissageonactionneraplusieursfoislatoucheP P pos 15fig 1 enalternativeonpeututiliserlacommandeP P borne22 fig 2 oul metteurradiom moris surlepremiercanaldur cepteur Dansl...

Page 20: ...cela se produit r p ter l auto apprentissage en positionnantlesvantauxdemani requ ilsparviennent fermerpendant5secondessansrencontrerlabut e IMPORTANT durantcemouvement nonpluslesvantauxnedoivent pasf...

Page 21: ...M2 arrive dans la zone d sir e de ralentissement Pour mettre en vidence et confirmer le r glage le moteur M2 s arr te un instant et repart en ouverture 18 Quand les deux vantaux sont en position d ouv...

Page 22: ...ur dip switch 11 sur MODIFICATIONDEL OUVERTUREPI TON modalit 1moteur OFFvoirpart 19fig 1 Proc dure 1 Bloquerleportaill g rementouvert 2 EnmaintenantlatoucheProgenfonc e effectueruner initialisationenc...

Page 23: ...F 23 TAB 2...

Page 24: ...resserbri vementlatoucheducanal m moriser P1pas pasP2pi ton laledcorrespondantecommence clignoter Silaledeffectuedesclignotementsdoublesattendreetr p terl op ration lapetitetouchenedoit trepress equ u...

Page 25: ...oi Etablir unplan demaintenance del installation aumoins tous les6mois pourlesdispositifs des curit eninscrivantsur unregistre pr vu cet effet lesinterventionseffectu es L installation de l automation...

Page 26: ...cancelasdeunahojaconosinfindecarrera cancelascorrederasdoblesconfindecarrera cancelascorrederassimplesconfindecarrera Lacentralest equipadacon controldelmotorporencodery oamperim trico desaceleraci nd...

Page 27: ...13Bot ndeProgramaci nyParada 14Bot nP3 programaci ntiempodePausa 15Bot nPasoapaso P P 16LedProgramaci n LD3 17Regletadeconexi nparamandosydispositivosdeseguridad 18Leddese alizaci nestadoentradasdema...

Page 28: ...os que entran en la caja estanca de la central deben instalarse manteniendo invariado dentro de lo posible el grado de protecci nIP56original Lasecci ndeloscablesdebecalcularseseg nsulongitudylacorrie...

Page 29: ...a 12Vcc 24Vcc 24Vcc 24Vcc 24Vcc Luz intermitente 24Vcc Indicador luminoso cancela abierta BANDA ABRIR PHOTOCELL 2 PHOTOCELL 1 JOLLY 4 JOLLY 1 JOLLY 3 JOLLY 2 STOP P P PEATONES Alimentaci n fotoc lulas...

Page 30: ...a entrada al com n si no se la utiliza V ase modo entradas Jolly tab 2 dip switch n 3 y 4 V ase modo entradas Jolly tab 2 dip switch n 3 y 4 V ase modo entradas Paso a Paso y Paso de peatones tab 2 di...

Page 31: ...ayaquelladedesaceleraci n Durantelaetapadeaprendizajeseaccionar variasveceselbot nP P det 15defig 1 comoalternativasepuedeutilizarelmandoP P borne22 fig 2 obien eltransmisormemorizadoenelprimercanalde...

Page 32: ...IMPORTANTE en este movimiento las hojas no deben llegar hasta el tope si esto sucede repita el autoaprendizaje colocando las hojas en una posici nquelogrencerrarsedurante5segundossinquelleguenhastael...

Page 33: ...bot nP PcuandolahojaconM2llegaalazona deseada dedesaceleraci n Paraevidenciaryconfirmarlamemorizaci n elmotorM2se detieneduranteuninstanteyarrancaenapertura 18 Cuandolasdoshojasest nenposici ndeapertu...

Page 34: ...s lo si la central est en modalidad 1 motor dip switch 11 en OFF v ase det 19defig 1 Procedimiento 1 Bloqueelacancelaligeramenteabierta 2 Manteniendopulsadoelbot nPROG realiceunreajustecortocircuitand...

Page 35: ...E 35 TAB 2...

Page 36: ...telacentralyespereaquelosledsdelreceptorseapaguen Pulse brevemente en el receptor el bot n del canal que se ha de memorizar P1 paso a paso o P2 paso de peatones el led correspondiente comenzar aparpad...

Page 37: ...araci nCEdeconformidad Aseg resedequeelusuariohayacomprendidoelcorrectofuncionamientoautom tico manualydeemergenciadelautomatismo Informe al usuario porescrito por ejemplo enlos manuales deinstruccion...

Page 38: ...with or without limit switches double leaf sliding gates with limit switches single leaf sliding gates with limit switches The control unit is equipped with encoder and or current sensitivity motor co...

Page 39: ...top 14 Pushbutton P3 Pause time programming 15 Step by Step pushbutton S S 16 Programming Led LD3 17 Terminal board for connection of controls and safety devices 18 Indicator leds for control input st...

Page 40: ...ecommendedbymeansofrelaysinstalledinthevicinityofthecontrolunit AllN C inputs normallyclosed notusedinthecontrolunitmustbeshortedwiththecommon AllN C contactsassociatedwiththesameinputmustbeconnectedi...

Page 41: ...25 Aux electric lock 24Vdc 24Vdc 24Vdc 24Vdc 24Vdc 12Vdc flashing light Gate open indicator OPEN EDGE FT2 FT1 JOLLY 4 JOLLY 1 JOLLY 3 JOLLY 2 STOP P P PEDESTRIAN Power supply of photocells with Photot...

Page 42: ...Inverts travel during closing Connect this input to the common if not used See Jolly inputs mode table 2 dip switch no 3 and 4 See Jolly inputs mode table 2 dip switch no 3 and 4 See Step step and Ped...

Page 43: ...ntrolcanbeused terminal22 fig 2 orthe radiotransmittermemorisedonthefirstchannelofthereceiver Onsystemswithelectriclock thismustbefittedontheleafconnectedtomotorM1 Powerupthecontrolunitandcheckcorrect...

Page 44: ...earning procedure positioningthegateleafssothattheycanclosefor5secondswithoutcomingintocontactwiththeendstop IMPORTANT also during this movement the leafs must not come into contact with the end stop...

Page 45: ...whentheleaf withM2reaches the required deceleration zone Toindicate andconfirm recording motor M2 stops forafewseconds and thenrestartsinopening 18 Whenthetwoleafsarebothintheopenposition thepausetime...

Page 46: ...and use a screwdriver to short the jump Reset detail 20 of fig 1 3 Keep the Prog key pressed 4 5 After three seconds led Ld3 and the flashing light turns on Programming procedure activated 6 At this...

Page 47: ...GB 47 TAB 2...

Page 48: ...asfollows Insertthereceiverintheconnector detail23offig 1 Powerupthecontrolunitandwaitforthereceiverledstoturnoff Onthereceiver brieflypressthepushbuttonofthechanneltobememorised P1step steporP2pedest...

Page 49: ...ualrisksandofforeseeablemisuse Informtheuserinwriting intheuseinstructionsforexample Ofpossiblenonsecludedresidualrisksandofforeseeableimproperuse Todisconnectthepowersupplywhencleaningtheareathatisau...

Page 50: ...halter einteiligeToremitoderohneEndschalter zweiteiligeSchiebetoremitEndschalter einteiligeSchiebetoremitEndschalter DieSteuerungistausgestattetmit Antriebskontrolle berEncoderund oderStrommesser prog...

Page 51: ...ef rProgrammierungundStopp 14TasteP3 ProgrammierungderPausezeit 15TasteSchrittbetrieb P P 16LEDProgrammierung LD3 17KlemmleistezumAnschlussvonSchalt undSicherheitsvorrichtungen 18LEDStatusanzeigederSt...

Page 52: ...hteBoxderSteuerungsindsodurchzuf hren dassdieanf nglicheSchutzartIP56erhaltenbleibt DerKabelquerschnittmussaufGrundihrerL ngeunddesH chststromsberechnetsein F r die verschiedenen Anschl sse Linie Antr...

Page 53: ...oss 12Vcc 24Vcc 24Vcc 24Vcc 24Vcc Blinkleuchte 24Vcc Leuchtanzeige Tor auf SCHALTLEISTE FFNET Ft2 Ft1 JOLLY 4 JOLLY 1 JOLLY 3 JOLLY 2 STOP P P GEHFLUGELOFFNONG Versorgung der Fotozellen mit Fotozellen...

Page 54: ...4 Siehe Modus der Jolly Eing nge Tab 2 Dip Switch Nr 3 und 4 Siehe Modus der Eing nge Schrittbetrieb und Gehfl gel Tab 2 Dip Switch Siehe Dip Switch Nr 1 und 2 Diesen Eingang am Sekund rkreis des mitg...

Page 55: ...tigt Det 15 inAbb 1 es kann aber auch der Befehl P P Klemme 22 Abb 2 oder der im ersten Empf ngerkanalgespeicherteFunksenderbenutztwerden EininderAnlagevorhandenesElektroschlossmussandenT orfl gelmont...

Page 56: ...egen den Endanschlag laufen in einem solchen Fall muss die Selbsterlernung wiederholtwerden dieTorfl gelsoanbringen dasssieohneAufprallenaufdenEndanschlag5Sekundenlangschlie enk nnen WICHTIG auch bei...

Page 57: ...dr cken wennder anM2 angeschlossene Torfl gel in dengew nschten Verlangsamungsbereich gelangt Umdie Speicherung zu best tigen stopptderAntriebM2kurzundstartetdannwiederin ffnung 18 WennbeideTorfl gelg...

Page 58: ...rn DieLEDLD3schaltetausunddieProgrammierungistbeendet Die Gehfl gel ffnungszeit kann nur programmiert werden wenn 1 Antrieb an der Steuerung angeschlossen ist Dip Switch 11 auf OFF NDERUNGDERGEHFL GEL...

Page 59: ...D 59 TAB 2...

Page 60: ...derstecken Detail23inAbb 1 DieSteuerungspeisenundwarten bisdieLEDsamEmpf ngerausschalten AmEmpf ngerkurzaufdieTastedeszuspeicherndenKanalsdr cken P1Schrittbetrieb P2Gehfl gel dieentsprechendeLEDbeginn...

Page 61: ...ush ndigen Sicherstellen dassderBedienerdiekorrekteautomatischeundmanuelleFunktionsweisesowiedenNotbetriebderAutomatisierungverstandenhat Den Benutzer schriftlich beispielsweise in der Bedienungsanwei...

Page 62: ...vleugels met of zonder eindschakelaar poorten met n enkele vleugel met of zonder eindschakelaar dubbele schuifpoorten met eindschakelaar enkele schuifpoorten met eindschakelaar De besturingseenheid i...

Page 63: ...rammering Pauzeduur 15KnopStap voor stap P P 16LedProgrammering LD3 17Klemmenbordvooraansluitingbediening enveiligheidsorganen 18Ledvoorsignaleringstatusingangenbediening Ledaan inganggesloten leduit...

Page 64: ...en box van de besturingseenheid binnenkomen moeten zo ge nstalleerd worden dat de aanvankelijke beschermingsklasse IP56 kan blijven worden behouden De doorsnede van de kabels moet worden berekend op b...

Page 65: ...ux Elektrisch slot 24Vcc 24Vcc 24Vcc 24Vcc 24Vcc 12Vcc Knipperlicht Controlelampje poort open LIJST OPEN ft2 FT1 JOLLY 4 JOLLY 1 JOLLY 3 JOLLY 2 STOP P P VOETG Stroomvoorziening fotocellen met Fototes...

Page 66: ...nr 3 en 4 Zie modus ingangen Jolly tab 2 dipschakelaar nr 3 en 4 Zie modus ingangen Stap voor stap en Voetgangersopening tab 2 dipschakelaar nr 1 en 2 Nr 1 und 2 Zie dipschakelaar functies nr 1 en nr...

Page 67: ...edrukt als alternatief zal de bediening P P klemmetje22 afb 2 opderadiozenderdieopheteerstekanaalvandeontvangerinhetgeheugenisopgeslagen kunnenwordengebruikt Indeinstallatiesmeteenelektrischslotmoetda...

Page 68: ...uitte voeren waarbijudevleugelszozetdatzijerinslagenin5secondentesluitenzondertegendeaanslagtekomen BELANGRIJK ook bij deze beweging mogen de vleugels niet tegen de aanslag komen als dit gebeurt dien...

Page 69: ...van vertraging komt Om te tonendat afstelling heeftplaatsgevonden en dattebevestigenstoptdemotorM2eventjesengaatdaarnavanstartindeopeningsrichting 18 Wanneerdetweevleugelsbeideindeopeningsstandstaan...

Page 70: ...sturingseenheid zich in de modaliteit 1 motor bevindt dipschakelaar 11 op OFF zie onderdeel 19 afb 1 Procedure 1 Blokkeer de poort wanneer die enigszins open staat 2 Terwijl u de knop Prog houdt inged...

Page 71: ...NL 71 NL TAB 2...

Page 72: ...anafb 1 Zetdebesturingseenheidonderspanningenwachtdatdeledjesopdeontvangeruitgaan Druk eventjes op de knop van het te bewaren kanaal op de ontvanger P1 stap voor stap of P2 voetgangersdoorgang het des...

Page 73: ...handbediendeennoodwerkingvandeautomatiseringbegrepenheeft De gebruiker moet schriftelijk ge nformeerd worden bijvoorbeeld in de gebruiksaanwijzing over de eventuele aanwezigheid van restrisico s waart...

Page 74: ...NOTE 74...

Page 75: ...75...

Page 76: ...porte delproductoparalaraparaci nocambio GARANZIA GARANTIE GARANT A GB D NL This warranty covers any failure and or malfunctioning due tomanifacturingfaultsand orbadworkmanship The warranty is automat...

Reviews: