4.2.7 CM indication
The CM has the following LED indication functionality:
CM “Power“ indication;
CM “Ready“ state indication;
CM “Malfunction“ state indication.
CM state
Indication
LED Power
LED Ready
LED Malfunction
Power supply voltage is
absent more than 3 minutes
off
off
off
"Close" operation is
preparing
continuous
off
off
CM is ready and operable
continuous
continuous
off
Power supply voltage is absent for
more than 1.5
seconds
off
continuous
1 blink
Exessive trip or close time
continuous
off
2 blinks
Actuator coil isolated
continuous
off
3 blinks
Short circuit of Actuator coil
continuous
off
4 blinks
Manual Trip and Lock
continuous
off
5 blinks
Overheat
continuous
off
6 blinks
State of ISM is not defined
continuous
off
7 blinks
Internal fault of the CM
continuous
off
continuous
Notes.
1. Number of blinks in series followed by 1.5 s intervals, continuous light or off state are shown for LED indicators.
2. Period of checking Actuator Coil state (short circuit / isolated) – 10 s.
Priority of the fault indication starting from the highest one:
1. CM overheat ;
2. ISM state is open without command from the CM;
3. Exessive trip or close time;
4. Manual Trip and Lock;
5. Short circuit of Actuator coil;
6. Actuator coil isolated;
7. Power supply voltage is absent more than 1.5 seconds.
Table 11 - CM indication
The placement of LED inicators are shown in Figure 79. The LED indicators are visible from two directions.
1. “Power“ LED indicator
2. “Malfunction“ LED indicator
3. “Ready“ LED indicator
2
1
Figure 79
CM_16 LED indicators
3
The self-diagnostic system inside the CM detects possible malfunctions and reports them via the Malfunction
LED blink signals and Malfunction Relay state. The explanation of the LED blink codes is given in Table 11.
Summary of Contents for TAVRIDA ELECTRIC VCB15 LD
Page 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Page 3: ...1 Product description...
Page 7: ...2 Nameplates and seals...
Page 11: ...3 Product handling...
Page 23: ...4 Installation...
Page 50: ...5 Commissioning...
Page 57: ...6 Operation...
Page 61: ...7 Maintenance and troubleshooting...
Page 66: ...8 Disposal...
Page 68: ...Appendix 1 Product range...
Page 71: ...Appendix 2 Overall drawings...
Page 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Page 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Page 85: ...Appendix 3 Secondary schemes...
Page 86: ...87...
Page 87: ...88...
Page 88: ...89...
Page 89: ...90...
Page 90: ...91...
Page 91: ...92...
Page 92: ...93...