To Setup the AFA1000 with BACnet protocol using the pushbutton menus:-
1.
Press Enter from the “Requires set up” screen or if the monitor is in the Run
screen Press and Hold the Enter button for 5 seconds until the Main Menu is
displayed.
2.
Using the + / - buttons select SET UP, and then select CONFIGURE, then enter
the password (the factory default password is 0-0-0-0), press Enter to continue.
3.
Using the + / - buttons select PROTOCOL, and press Enter, then using the +/-
buttons select BACnet and then press Enter to return to the CONFIG MENU.
4.
Using the + / - buttons select BACnet SETTINGS and then press Enter, a sub
menu will appear with the following parameters:-
5.
Using the + / - buttons select the DEVICE INSTANCE parameter and then press
Enter, then using the +/- buttons select the required Instance and press Enter to
continue.
6.
Using the + / - buttons select the STATION ID parameter and then press Enter,
then using the +/- buttons select the required ID and press Enter to continue.
7.
Using the + / - buttons select the BAUD RATE parameter and then press Enter,
then using the +/- buttons select the required rate and press Enter to continue.
8.
Using the + / - buttons select the PARITY parameter and then press Enter, then
using the +/- buttons select the required rate and press Enter to continue.
9.
Using the + / - buttons select the MAX MASTERS parameter and then press
Enter, then using the +/- buttons select the required number of Masters and
press Enter to continue, then select DONE to return to the CONFIG MENU, then
select DONE and RUN.
Parameter
Description
Range
Default
A Device Instance Set the slave ID
for the unit
0000000 to 4194303
0000000
B Station ID
Set the network
ID
0-127
1
C Baud Rate
Set the required
Baud Rate
1200/2400/4800/9600/1440/
19200/38400/57600
38400
D Parity
Set the required
Parity
None/Even/Odd
None
E Max Masters
Set the max
masters (max
devices on the
network)
0-127
1
Summary of Contents for AFA1000/2 MK2
Page 4: ...1 SAFETY ...
Page 9: ...2 OVERVIEW OF THE AIRFLOW MONITOR ...
Page 20: ...3 FUNCTIONS OPERATION ...
Page 27: ...4 COMPONENTS ...
Page 30: ...5 INSTALLATION ...
Page 35: ...6 CONFIGURATION CALIBRATION ...
Page 39: ...7 AUXILIARY FEATURES CONNECTIONS ...
Page 44: ...8 RS485 COMS OUTPUT ...
Page 51: ...9 WARRANTY ...