Quick Start Guide
Quick Start Guide
796 Tek Drive, Crystal Lake, IL 60014 USA
+1 847 857 6076 | +1 847 655 7428
+1 847 655 6147
www.tek-trol.com
The meter is provided factory calibrated to display -50.0 at 4 mA and 150.0 at 20 mA. HI and LO coarse and fine
controls are labeled on the front of the display. Use the HI and LO controls for large range changes during
calibration and the HI FINE and LO FINE controls for precision changes.
Apply a 4 mA signal and adjust the LO controls to display the desired reading. Apply a signal between 16 and
20 mA and adjust the HI controls to display the desired reading. Complete the calibration procedure by making
minor adjustments to the LO and HI controls as necessary.
7. Setting Up The Meter
Calibrating the Meter
The meter is provided factory calibrated to display -50.0 at 4 mA and 150.0 at 20 mA. HI and LO coarse and fine
controls are labeled on the front of the display. Use the HI and LO controls for large range changes during
calibration and the HI FINE and LO FINE controls for precision changes.
Apply a 4 mA signal and adjust the LO controls to display the desired reading. Apply a signal between 16 and
20 mA and adjust the HI controls to display the desired reading. Complete the calibration procedure by making
minor adjustments to the LO and HI controls as necessary.
Minimum & Maximum Input Span
Decimal point may be set using a three position jumper on the rear of the display module. To access the
connectors, unscrew the two captive screws that fasten the display module. Remove the display module and
place the jumper on the desired pins as indicated on the board for decimal point locations of D.DDD, DD.DD,
DDD.D, or remove it if no decimal point is desired.
Setting the Decimal Point
The following table shows the factory setting for most of the programmable parameters on the meter. Next to
the factory setting, the user may record the new setting for the particular application.
Factory Defaults & User Settings