Hazardous
Voltage
HAZARDOUS VOLTAGE. Disconnect before working on product
DC supply voltage up to 300V, (+0V tolerance).
DUAL SUPPLY. Disconnect both supplies before working on the product
Hazardous voltage may be present on DC supply and
PR-
,
HV-SW-,
HV-SW+
and
PR+
terminals.
DISCONNECT DEVICE(S)
Each Hazardous Voltage circuit which connects to the ITR shall incorporate a
readily accessible disconnect device installed externally to the ITR.
Disconnect devices shall have contact separation of at least 3mm.
ITR Terminals
HAZARDOUS VOLTAGE. Stray conductors or loose connections.
Provide insulation and strain relief on all Hazardous Voltage terminations to
protect against electric shock hazard.