Astra-Z-8845 Ver. B
Wireless
Repeater / Router
Operation Manual
Revision 8845-bv1_4_en
This operation manual is intended for studying the operating
principles, proper use, storage, and maintenance of the
Wireless
Repeater/Router
Astra-Z-8845
version
B
(hereinafter referred to as
router
) (Figure 1).
The manufacturer reserves the right to make alteration regarding
refinement of the product without prior notification. All
improvements are included in new revision of the operation
manual.
List of Abbreviations
:
Astra-Zitadel System
: Astra-Zitadel on-site Wireless Intrusion
/ Fire Detection and Alarming System;
Control panel
: Astra-Z-812M / Astra-Z-8945 ver.A Control
Panel;
AL
: Alarm Loop;
LT
: Astra-942 Laser Tester;
FW
: Firmware;
MSS
: Astra-Z Monitoring Software Suite.
1 Function
1.1
The router is designed for operation
within the Astra-Zitadel system.
1.2
The router is intended:
- for retransmitting messages (notifications,
control commands, responses, handshakes,
etc.) from wireless devices within the Astra-
Zitadel system through all retransmission
levels to the control panel;
- for automatically routing messages from
wireless devices if the current data transfer route is lost;
- for controlling external devices (sirens, lighted signs) via its
outputs.
1.3
The router ensures operation directly with 30 detectors
(plus two mobile devices).
1.4
The router ensures control of passive detectors and other
devices with
«dry contact»-type outputs through the
Zone-
GND
input with current control.
1.5
Power is supplied to the router from an external
redundant 10-27 V power supply unit (e.g. Astra-712/0).
2 Specification
Technical Parameters of Radio Channel
Operating frequency range, MHz ..................... 2 400 to 2 483, 5
Number of operating channels at 5 MHz intervals ................... 16
Channel width, MHz .................................................................. 2
Wireless coverage range, line-of-sight, m, min .................... 1000
AL Technical Parameters
Zone-GND terminal voltage
in standby mode, V ....................................................... 2,7 to 5,0
Zone-GND terminal
active ripple voltage, mV, max ................................................. 50
AL resistance*, kΩ, in status:
-
«Normal», .................................................................. 3,0 to 5,0
-
«Violation» ............................................................ <3,0 or >5,0
Relay Output Technical Parameters
- Relay 1:
Loading voltage, V, max ........................................................ 100
Loading current, mA, max ..................................................... 150
- Relay 2:
Loading voltage, V, max ........................................................ 250
Loading current, A, max ............................................................ 5
General technical parameters
Power supply voltage, V ................................................. 10 to 27
Current consumption
(at power supply voltage 10 V), mA, max:
- in transmitting mode, relay opened, registered
in wireless network ................................................................ 122
- in transmitting mode, relay closed, registered
in wireless network ................................................................ 160
Technical readiness time, s, max............................................. 20
Overall dimensions, mm, max ................................... 101
63
32
Weight, kg, max .................................................................... 0,07
Operating Conditions
Temperature range,
°
C .................................. from -30 up to +50
Relative air humidity, % .................................... up to 95 at 35
°
C
without condensation of moisture
__________________________________
* The permissible parameter spread for resistance is not more than 10%.
3 Delivery Set
Astra-Z-8845 version B ........................................................ 1pcs
Screw 2.9×25 ...................................................................... 4 pcs
Dowel 5х25 ......................................................................... 4 pcs
Operation Manual ............................................................. 1 copy
4 Structure
4.1
Structurally the router is designed as a block consisting of a
base and removable cover. Mounted inside the block is a printed
circuit board (PCB) with radio elements (Figure 2).
Figure 2
4.2
Mounted on PCB are
red
and
white
LEDs
for router’s
functional status and the wireless network status supervision
respectively.
4.3
Mounted on PCB is a tamper switch, which results in the
«Tampering» notification when the cover is removed.
4.4
Mounted on PCB is a terminal block. For terminal function
see Table 1.
Table 1: Terminals
Terminal
Name
Terminal function and characteristics
+12V,
GND
Input for power supply connection
GND,
Zone
AL Input with current control for external devices
with
«dry contact» outputs connecting.
Wire length must be not greater than 10 m.
RELAY1
RELAY2
Outputs for slave devices connecting
Figure 1
Wire
Insertion
hole