background image

 

 

 

 

Astra-Z-3645 

 

Wireless Electro-Contact Water Leak Detector 

 

Operating Manual

 

 

 

 

 

 
 

 

 

 

This operation manual is intended for studying the operating principles, 
proper  use,  storage,  and  maintenance  of  Wireless  Electro-Contact 
Water Leak Detector Astra-Z-3645 (hereinafter 

“detector”

) (Fig. 1). 

The  manufacturer  reserves  the  right  to  introduce  changes  which  up-
date and retrofit the detector without prior notice. All such changes will 
be described in an updated revision of the operating manual. 

 

List of Abbreviations

:  

Astra-Zitadel  system 

–on-site  Wireless  Intrusion  /  Fire  Detection  and 

Alarming System Astra-Zitadel; 

Astra-Zitadel  System  Control  Panel

:  Astra-Z-812M,  Astra-Z-8945 

ver.A,  Astra-8945  Pro  or  Astra-812  Pro  Control  Panel  (with  connected 
Astra-Z Wireless Extender);

 

MSS Astra-Z 

– Monitoring Software Suite Astra-Z; 

MSS Astra Pro 

– Monitoring Software Suite Astra Pro; 

LT 

– Laser Tester Astra-942; 

Battery 

 

power supply battery. 

 

1   Function 

 

1.1 

The  detector  generates  and  sends  to  the 

control panel 

“Alarm” notifications when water of any 

chemical composition (except for distilled water) gets 
to detector contact pads. 

1.2 

The  detector  is  powered  by  one  battery  of 

CR2450  type  (voltage 

– 3.0 V) (included in the deli-

very set).   

 

Specifications 

 

Technical Parameters of Wireless Channel 

Bandwidth, MHz ........................................................... 2400 to 2483.5 
Number of active channels with 5 MHz increment ............................ 16 
Channel width, MHz ........................................................................... 2 
Wireless coverage range, line-of-sight, m, min ............................... 300 

 

General parameters 

Power supply voltage, V .............................................................. 2.2-3 
Current consumption, mA, max: 
- radio module ON ........................................................................... 45 
- radio module OFF ..................................................................... 0,010 
Battery replacement indication threshold, V ................................ 2.5

-0.2

 

Power supply voltage lower threshold (deactivating  
threshold retaining battery discharge indication), V ......... below (2.3

-0.2

Battery service life, months, min ...................................................... 18 
Overall dimensions, mm, max .............................................. 64

46

22 

Weight (with battery), kg, max ..................................................... 0.074 

 

Operating Conditions 

Temperature range, 

°

С .......................................... from + 5 up to + 50 

Relative air humidity, % .......................................... up to 95 at +35 

°

С   

                                                                         

no moisture condensation

 

Delivery Set 

 
Astra-Z-3645  ............................................................................. 1 pcs. 
Battery ....................................................................................... 1 pcs. 
Operating Manual .................................................................... 1 copy. 
 

Structure 

 

4.1 

The  detector  is  designed  as  a  unit  consisting  of  a  removable 

cover, a base and a printed circuit board with radio elements (Fig. 2), 
the battery from the delivery set is pre-installed. 

 

 

 

Fig. 2 

 

4.2 

The following indicators are mounted on the printed circuit board: 

red 

– for detector operability supervision, white – for wireless network 

status indication. 

 

Information Capacity 

 

Table 1 

– Notification – Detector indicators and control panel 

 

Notification 

type 

Red  

indicator 

White  

indicator 

Control 

panel 

Detector standby 
mode start 

Lights up 

once 

for 

1 s

 after power up 

 

 

Norm 

Not lit 

+

 

Violation 

Lights up 

once 

for 

0.2 s 

 

Power ON 

Not lit

 

Power failure 

Blinks

 3 times 

every 

25 s

 

 

Network search  

 

Blinks 

5 times a 

second 

for

 1 to 

60 s

 

− 

No network 

 

 
Blinks

 2 times 

every 

25 s 

 

− 

Radio module 
failure 

 

 
Blinks

 3 times 

every 

25 s 

 

“+” – the notification is given,   “–” – the notification is not given 

 

Note 

–  When  “Power  failure”  notification  is  given,  replace  the  battery 

within 

two months

 

Pre-Starting Procedure 

 

6.1 

After transportation in conditions differing from those of operation, 

the detector must be kept unpacked for at least 4 hours in the operat-
ing conditions. 

 

6.2  Running Detector. Battery Replacement 

 

Step-1

 

  

Remove the detector cover by unscrewing 4 screws from the base side 

 Step-2

  

Install  the  battery  (to  replace,  remove 
the old battery, wait at least 2 min and 
install the new one).  
The  red  indicator  lights  up  for 

1  s

  (if 

after 

60  s

  the 

red 

indicator  blinks 

times 

every  25  s,  the  battery  is 

discharged and must be replaced). 

 

Step-3

   

Close the detector cover by screwing 4 screws from the base side 

 

6.3  Registering the Detector in the Wireless Network

 

 

Detector  registration  is  required  for  detector  identification  in  the  wire-
less network in which it shall operate. 
 

 

Step-1 

According  to  Astra-Zitadel  System  Control  Panel`s 

Operating 

Manual *

 perform the following procedure: 

1)

  Install 

Software  ** 

(MSS  Astra-Z,  Pconf-Z  or  MSS  Astra  Pro) 

intended for configuring Control Panel; 

2) 

Create wireless network.

 

Step-2 

Perform 

p. 6.2

 

Step-3  

Switch  the  control  panel  to 

Wireless  device  registration

  mode  by 

the  method  described  in  the  appropriate  Astra-Zitadel  System 
Control Panel`s 

Operating manual *. 

The mode activates for 60 s for registration of 1 wireless device.

 

Fig. 1

 

Reviews: