Редакция 517-v1_0
3
3
а
WALL MOUNTING
3b
CORNER MOUNTING
3c
MOUNTING USING BRACKET
Press out blanks from brack-
et mounting slots
4a
,
4b
Mark mounting holes on
the wall at the desired
height using the base.
ATTENTION!
Detector base should be
positioned strictly as per
figure for Step 3
4c
Mark mounting holes on the
wall at the required height
applying
the
bracket
to
mounting surface. Mount the
bracket on the wall.
Mounting holes
5a
,
5b
Insert power supply and
alarm loop wires through
the dedicated wire access
hole in the detector base.
Fix the base to the wall
or in the corner
5c
Align base projection of the
detector with the bracket slot
for the ball and drive a screw
from inside of the base into
the bracket ball. Position the
detector as required and
tighten the locking screw. If
anti-sabotage zone monitor-
ing is required, set the vertical
tilt angle to
20º
.
The bracket makes it possible
to turn the detector horizontally
and vertically by
40º
6
Match nib on the base hook
with a slot on the PC board
depending on the chosen de-
tection range.
Secure the PC board with a
screw.
7
Connect wires to the detector terminals
8
Switch the detector ON. The indicator shall blink
once per
second
within 60 s
– the detector is being switched to the
standby mode
9
Remove jumpers from plugs
Mem
and
Sens
.
Install the jumper on plug
Ind
10
Place back the cover of the
detector (until clicks)
11
Perform
test-pass
in the secured
area at a speed of
0.5
m/s in order
to determine detection zones.
At the moment of detection (the
indicator lights up for
4s
) you
should stop, spot the place and
then return one step back and
continue moving.
Repeat the
TEST-pass
moving back.
The sensitive zones configured by the lens will be in the
middle between the spotted places.
12
Push the lock on the bottom
base from the cover slot.
Remove the cover.