5  ASSIGNING TO THE SYSTEM 

 

1) 

Turn detector counterclockwise.  
 

2) 

Start assigning on the Security Hub mobile 
or desktop app. Assigning starts for 45-60 
sec. 
 

3) 

Insert battery into the detector: 

 

Secondary

 

– first 

Primary

 - next 

4) 

Detector’s led start flashing: 5x white flash 
in 1 sec. 

 
Make  sure  that  the  assigning  is  successful  on 
the  Security  Hub  mobile  or  desktop  app.  If  as-
signing is unsuccessful, repeat the procedure. 

 

6  RESET PROCEDURE 

1) 

Turn detector counterclockwise.

 

 

2) 

Close the DEL contacts - the red indicator 
will turn on. 

3) 

After turning off the red indicator, open the 
DEL contacts. 

4) 

The  detector  generates  a  notice “No  con-
nection”  and  becomes  available  for  as-
signing to the system. 

 
7  INSTALLATION  PLACE 

 

1) 

The  detector  is  installed  under  the  ceiling.  It 

is allowed to install the detector on the wall, as well 
as  to  mount  it  on  a  cable.  When  suspending  the 
detector on a cable, its stable position and orienta-
tion in space must be ensured. 

 
 
To eliminate false alarms 

2) 

It  is  forbidden  to  mask  the  detector,  heat 

fluxes  must  freely  penetrate  through  the  holes 
in the case; 

3) 

It is forbidden to install the detector in front 

of the air conditioner (in the zone of convection 
flows). 

 
ATTENTION!

  Remove  the  protective  cover 

immediately before commissioning the detector.

 

 

8  INSTALLATION  PROCEDURE  

 

1) 

Remove the elec-
tronic unit from the 
base

  

 

 

2)

 Mount the base on 

ceiling 

 

 

3) 

 Insert battery. 

 

Secondary

 

– first 

 

Primary

 - next 

 

4) 

 Install the electronic unit. 

5) 

 Perform detector test (see section 9).

 

 

9  TESTING 

The test is performed by the laser tester "Astra-
942" (not included in delivery set). 
 
To activate the 

«Test» 

mode: 

- press the 

red button

 of the laser tester;

 

direct laser beam to the detector’s LED; 

-  irradiate the LED for 

1 sec

LED should turn on in red for 2 sec. 
 

 

 

detector’s LED:

 

-

  normal  work:  1x  red  flash  in  every  2  sec. 

during 30 sec.  

-

  if there is a defect or malfunction: 3x red flash 

in 25 sec. period.

 

  Security  Hub

 

mobile  app

:  fire  alarm  notifi-

cation. 

 

10  WARRANTY 

 

The  operation  warranty  period  is  5  years  from 
the date of manufacturing, which is indicated on 
housing and box of detector. 

 
 

 

Mount holes