background image

-  Second  way:  with  laser  pointer  (if  the  detector  is  on 
the  base),  direct  the  Astra-942  laser  beam  to  the 

detector’s LED using the 

third

 laser button for at least 

1 sec.

 

WARNNING!  
Running  registration  for  several  detectors  at  the 
same time is forbidden.

 

7)  Registration running check: 

 

In  case  of  successful  registration,  you  will 

see  “SD”  in  the  Configuration  module  of 

the  “PKM  Astra  Pro”  or  “Pconf-Pro”  soft-
ware, or you can see 

“SD xxx is registered” 

on the Astra-812 Pro LCD screen. 

 

In case of  unsuccessful registration repeat 
actions from 5) to 7).

 

 
Notice: 

It is possible to start the  registration  mode on 

a  detector  previously  registered  in  another  Extender 
and  not  removed  from  it  only  using  Laser  Pointer 
(Astra 942). 

 

6 REMOVING DETECTOR FROM SYSTEM 

Removing a detector form Extender

’s memory can be 

held 

using  Configuration  module  of  “PKM  Astra-Pro, 

Pconf-Pro or Astra-812 Pro menu.  
 

7  INSTALLATION PLACE 

1)  The  distance  between  the  ceiling  and  sensitive 
element of the detector (the upper edge of the entry of 
smoke flows into the  detector housing) in the place  of 
its  installation  must  be  at  least  25  mm  and  not  more 
than 600 mm. When the detector is located at a height 
of  more  than  6  m,  as  well  as  under  raised  floors  and 
above  suspended  ceilings,  the  option  of  access  for 
maintenance and repair must be determined.

 

 

2) 

Do not install the detector:   

-  across  from  the  air  conditioner  (the  further  the  bet-
ter); 
-  across  from  the  windows  (decrease  of  the  tempera-
ture or dust may cause false alarms); 
3)  Do  not  mask  the  detector  (smoke 

should  freely 

enter the smoke chamber

).  

 

 

8  INSTALLATION  PROCEDURE  

 

1)   Remove the electronic unit from the base

 

 

 

 

 

 

 

 

2) Mark the ceiling through the base 
3)  Insert cables through the mount holes in the detector 
base and connect with terminals (ter and 

– ;  

terminals A and B).  
4) 

Cable type: FRLS 2×2×0.5. 

 
5)  Mount the base on the ceiling 

 

6)  Install the electronic unit into the base according to the 
picture 
 

 

Remove  the  protective cover  before launching the 
detector into service!

 

 

 
 

9  TEST

 

Run mode testing by using Laser pointerAstra-942: 
-  press the top button of the laser pointer 
-  direct  the  laser  beam  to  the  detector

’s  LED  and 

irradiate the LED for 1 sec.  
- receive  a notice Test fire in 5  sec  (1x  flashes  with a 
period of 2 sec. during 30 sec.). A

n entry “Test fire” will 

be  made  in  the  event  log  of  the  Control  Panel  Astra-
812 Pro or PKM Astra Pro, the message “Test fire” will 
be displayed in the PC software Pconf-Pro. 
  

 
 
 

10  WARRANTY

 

The operation warranty period is 5 years from the date 
of  operation  start-up  but  no  longer  than  5  years  6 
months  from  the  date  of  manufacturing  subject  to  the 
requirements of User guide.

 

Reviews: