Tekno Point ELSKOV-12 Use And Installation  Manual Download Page 31

USE AND INSTALLATION MANUAL ELFO

28

INSTALLATION

4.8 PREPARING PIPE REFRIGERATION

4.9 PATH OF PIPES

4.10 EXTRACTION AIR IN PIPES AND COOLING UNIT EVAPORATING

WARNING FOR THE TIGHTENING OF THE VALVE IS ESSENTIAL TO USE
A SECOND KEY.

Only use copper pipes as “cold” and that fit each model. The 
“gas pipe” and the “liquid tube” must be absolutely isolated 
with an insulator of 6 mm. of minimum thickness. Insert the 
flare nuts on the ends of the tubes before you prepare them 

The  radius  of  curvature  of  the  pipes  must  be  equal  to  or 
greater than three and a half times the diameter to the tube 
axis.  Do  not  bend  the  pipe  more  than  three  times  in  a  row 
and not make more than 10 bends on the total length of the 
connection.  In  the  case  where  there  is  a  height  difference 

The  refrigerant  charge  is  contained  only  condensing  unit. 
The  Internal  unit  contains  a  small  amount  of  neutral  gas. 

with  a  flaring  tool.  The  insulated  pipe  separately  with  the 
respective fittings can then be bound to the evacuation pipe 
of the condensate and to electric cables by means of cable 
ties.

between the evaporating unit and the condensing unit greater 
than  5  m.  it  will  be  mandatory  to  prepare  a  siphon  every  3 
m.  The  siphon  must  have  a  radius  of  curvature  as  tight  as
possible.

Therefore, after making the connections will be imperative to 
extract the air contained in said links and Internal units.

4.12 COOLING CONNECTIONS

4.7 DRAINAGE PIPE

The  refrigerant  connections  are  made  on  the  connections 
located on the right side of the machine.

When the unit is in heating, the condensation water produced, 
must be forced out through the appropriate hole of drainages 
oposto on the bottom of the machine, by installing the joint 
drainage so that the water can exit. Remember that the flow 
is gravity.

To connect the joint water drainage:

1. Connect the coupling of external drainage in the hole in the
frame, as shown in the picture below.
2. Connect the discharge tube into the discharge mouth

drain hole

4.11 ADJUSTMENT OF REFRIGERANT CHARGE

In function of the connection length independent way, it may 
be necessary to top up the refrigerant charge (the condensing 
units are preloaded to a 5-meter line). This operation must be 
performed  by  qualified  personnel  and  in  good  standing  of 
the art refrigeration engineer. The completion of charging is 
introduced through the fitting service valve Flare of condensing 

(big road). If the refrigerant line is less than 5 m. “Download” 
the  amount  of  excess  refrigerant.  Any  intervention  on  the 
refrigerant  circuits  imply  compliance  elle  recommendations 
elative disposal of R

32

 in the environment (according local 

regulations).

14

Step 1: Fix the support of outdoor

Select it according to the actual installation situation
1. Select installation location according to the house structure.
2. Fix the support of outdoor unit on the selected location with expansion screws.

Note:

● Take sufficient protecttive measures when installing the 

   outdoor unit.

● Make sure the support can withstand at least four times 

   of the unit weight.

● The outdoor unit should be installed at least 3cm above 
   the the floor in order to install drainjoint.
● For the unit with cooling capacity of 2300W~5000W, 6 

   expansion screws are needed; for the unit with cooling 
   capacity of 6000W~8000W, 8 expansion screws are 
   needed; for the unit with cooling capacity of 10000W
   ~16000W, 10 expansion screws are needed.

Step 2:  Install drain joint

(Only for cooling and heating unit)

1. Connect the outdoor drain joint into the hole 
    on the chassis, as shown in the picture below.
2. Connect the drain hose into the drain vent.

Step 3:  Fix outdoor unit 

1. Place the outdoor unit on the support.
2. Fix the foot holes of outdoor unit with bolts.

at least 3cm above

the the floor

drain joint

foot holes

Installation of outdoor unit

Step 4:  Connect indoor and outdoor pipe

1. Remove the screw on the valve cover of

   outdoor unit and then remove the valve

   cover.

2. Remove the screw cap of valve and aim 

    the pipe joint at the bellmouth of pipe.

valve cover

liquid valve

gas valve

support holes

drain

The connections for the refrigerant lines are of the “flare”.

bottom

Summary of Contents for ELSKOV-12

Page 1: ...mparsa Air Conditioner with recessed condensing unit Klima Anlage mit verdeckt eingebauter Kondensatoreinheit TRIAL ELSKOV3 24 H9 Versione 1 0 MONO ELSKOV 12 H9 ELSKOV 18 H9 DUAL ELSKOV2 14 H9 ELSKOV2...

Page 2: ...2012 EN 60335 2 40 2003 A1 2006 A2 2009 A11 2004 A12 2005 A13 2012 EN 62233 2008 EN 55014 1 2006 A1 2009 A2 2011 EN55014 2 1997 A1 2001 A2 2008 EN 61000 3 2 2014 EN 61000 3 3 2013 EN14511 206 2012 62...

Page 3: ...1 INFORMAZIONI GENERALI 2 DESCRIZIONE 3 VERIFICHE PRELIMINARI 4 INSTALLAZIONE 5 MANUTENZIONE DELL UNIT pagina capitolo 04 07 08 09 17 INDICE ITALIANO 6 AUTODIAGNOSI 18...

Page 4: ...sono provocare gravi lesioni o la morte alle persone esposte PERICOLO ALTE TEMPERATURE Richiama l attenzione su azioni che se non correttamente eseguite possono provocare gravi lesioni alle persone ca...

Page 5: ...re l unit in ambienti asciutti Se l unit esposta direttamente a fonti di calore dirette bisogna che sia protetto da esse 3 L unit deve essere utilizzata solo per scopi prescritti dal produttore 4 Non...

Page 6: ...rrivi la tensione corretta vedere targhetta di identificazione applicata sull apparecchiatura Una tensione non corretta comprometterebbe in modo irreparabile i principali componenti dell apparecchiatu...

Page 7: ...unit 1TFA NA SUV3 H24 1TFA NA 672 430 700 456 312 532 10 mension of the unit 1TFA NA SUV3 H24 1TFA NA 672 430 312 532 552 289 335 DESCRIZIONE 2 DESCRIZIONE Il prodotto reale pu essere diverso si prega...

Page 8: ...ttrico in classe A La messa a terra deve essere effettuata con un dispositivo adatto alla messa a terra Assicurarsi che la messa a terra sia sempre rispettata altrimenti pu causare scosse elettriche 2...

Page 9: ...lazioni con staffa murale Il pannello frontale deve essere ispezionabile pertanto lo spazio frontale deve essere tale da permettere all operatore tutte le operazioni necessarie in fase di installazion...

Page 10: ...versione prolungata 2 fori 200 mm aspirazione in locale tecnico min 500 mm tubazione rigida Distanza max dal muro 2 m lineari 4 m in versione prolungata 2 fori 200 mm aspirazione in locale tecnico min...

Page 11: ...ll acqua 1 Collegare il giunto di drenaggio esterno nel foro sul telaio come mostrato nella foto sottostante 2 Collegare il tubo di scarico nella bocca di scarico foro di drenaggio 4 11 AGGIUSTAMENTO...

Page 12: ...l immagazzinamento prima dell impiego tenere sempre i tubi sigillati con un cappuccio o con nastro adesivo per evitare l ingresso di acqua polvere e sporcizia 2 Lubrificare sempre con olio anticongela...

Page 13: ...del gas 1 Pressurizzare per 3 minuti a 0 3MPa 3 0 bar 2 Pressurizzare per 3 minuti a 1 5MPa 15 0 bar Verr trovata una grossa perdita 3 Pressurizzare per circa 24 ore a 3 0MPa 30 0 bar Verr trovata una...

Page 14: ...connection wire and signal control wire with wire clip only for cooling and heating unit 4 Reinstall the handle Note After tighten the screw pull the power cord slightly to check if it is firm Never c...

Page 15: ...elle variazioni Se varia vuol dire che nel sistema c una perdita e quindi bisogna individuare la perdita Dopo aver completato l esecuzione del vuoto sostituire la pompa per il vuoto con il contenitore...

Page 16: ...amenti alla macchina per mezzo di gruppo monometrico per verificare il corretto funzionamento della valvola pressostatica Verificare che l unit sia installata saldamente L isolamento termico della con...

Page 17: ...resa sulla linea di bassa pressione Caricare la quantit di gas refrigerante indicata sulla targhetta tecnica dell apparecchio in fase liquida Eseguire sempre il controllo dei valori di surriscaldament...

Page 18: ...uori dai limiti ammessi Verificare INS Cattivo funzionamento sonde o pressostati Sostituire il componente INS CAT Intervento protezione termica Verificare isolamento elettrico avvolgimenti CAT Pressio...

Page 19: ...pressione Errore flussostato E5 Protezione bassa pressione del sistema E6 Protezione perdita di refrigerante Protezione blocco valvola E7 Protezione malfunzionamento 4 vie E8 Temperatura ingresso usci...

Page 20: ...i comunicazione tra UI e comando via filo L8 Errore pompa scarico condensante L9 Protezione contro il troppo pieno dell acqua P0 Malfunzionamento EEPROM Unit esterna P1 Carica circuito errata P2 Prote...

Page 21: ...sensore temperatura ingresso aria U3 Errore sensore temperatura uscita aria U4 Errore sensore temperatura scarico compressore U5 Errore sensore temperatura IPM U6 Errore sensore temperatura tubo liqui...

Page 22: ......

Page 23: ...1 GENERAL INFORMATION 2 DESCRIPRION 3 PRELIMINARY CHECKS 4 INSTALLATION 5 MAINTENANCE OF UNITY page chapter 21 24 25 26 34 INDEX ENGLISH 6 SELF DIAGNOSIS 35...

Page 24: ...can cause serious injury or death to exposed persons DANGER HIGH TEMPERATURES Calls attention to actions that if not correctly performed may cause serious personal injury caused by the high temperatu...

Page 25: ...If the unit is directly exposed to direct heat sources need to be protected from them 3 The unit should be used only for purposes specified by the manufacturer 4 Do not insert any object above or belo...

Page 26: ...arrivals the correct voltage see type plate on the equipment applied identification An incorrect voltage compromise irreparably major equipment components 4 If you were to turn on alarms refer to the...

Page 27: ...ension of the unit 1TFA NA SUV3 H24 1TFA NA 672 430 700 456 312 532 10 mension of the unit 1TFA NA SUV3 H24 1TFA NA 672 430 312 532 552 289 335 DESCRIPTION 2 DESCRIPTION For the fastening of the rigid...

Page 28: ...e grounding should be performed with a suitable device to the ground Make sure the ground is always respected otherwise it may cause electric shock 2 The yellow green cable in the cable of the air con...

Page 29: ...of anti vibration spring for installations with wall bracket The front panel must be inspected so the front space should be adequate to permit the operator with all the steps required during installat...

Page 30: ...he wall 2 linear meters 8 m long version 2 holes 200 mm inlet equipment room min 500 mm rigid pipe Maximum distance to the wall 2 m linear 4 m long version 2 holes 200 mm inlet equipment room min 500...

Page 31: ...e joint water drainage 1 Connect the coupling of external drainage in the hole in the frame as shown in the picture below 2 Connect the discharge tube into the discharge mouth drain hole 4 11 ADJUSTME...

Page 32: ...sport and storage prior to use always keep the tubes sealed with a cap or with tape to prevent the ingress of water dust and dirt 2 Always lubricate with freezing oil flange surfaces of the nipples an...

Page 33: ...pressure drops you have to find the leak While pressurizing for 24 hours every change of 1 C of the ambient temperature will result in a variation of 0 01MPa pressure 0 1 kg cm2g It must take this int...

Page 34: ...ng unit 4 Reinstall the handle After tighten the screw pull the power cord slightly to check if it is firm Never cut the power connection wire to prolong or shorten the distance Note Maximum distance...

Page 35: ...ssario Esegui la procedutra sopradescritta per ogni singolo circuito ove presente il raccordo di servizio CARICA ADDIZIONALE DI REFRIGERANTE Se la lunghezza totale L delle tubazioni di collegamento fr...

Page 36: ...eration 2 Press the MODE button to select AUTO COOL DRY FAN and HEAT to see if the operation creates a malfunction of the machine Make sure the unit is installed securely The thermal insulation of the...

Page 37: ...let on the low pressure line Charge the quantity of refrigerant gas indicated on the rating plate of the device in the liquid phase Always check the overheating and undercooling values which must be b...

Page 38: ...ide the permissible limits Check INS Bad operation or pressure probes Replace the part INS CAT Thermal protection trip Check electrical insulation windings CAT Pressure flo High 24 bar Excessive refri...

Page 39: ...otection Flow switch error E5 Low system pressure protection E6 Refrigerant leakage protection Valve block protection E7 4 way malfunction protection E8 Abnormal air inlet outlet temperature H0 Protec...

Page 40: ...ror between UI and wired command L8 Condenser drain pump error L9 Water overflow protection P0 EEPROM malfunction External unit P1 Load wrong circuit P2 Abnormal AC voltage protection of the outdoor u...

Page 41: ...nlet temperature sensor error U3 Air outlet temperature sensor error U4 Compressor discharge temperature sensor error U5 IPM temperature sensor error U6 Liquid tube temperature sensor error U7 Gas pip...

Page 42: ......

Page 43: ...1 ALLGEMEINE INFORMATIONEN 2 BESCHREIBUNG 3 EIGENDIAGNOSE 4 INSTALLATION 5 WARTUNG Seite Kapitel 39 43 45 54 57 INDEX DEUTSCH 6 ANH NGE 58...

Page 44: ...NG Bitte beachten Sie unbedingt diese Anweisungen da diese eine reibungslose Funktionieren der Einheit erlauben 1 ALLGEMEINE INFORMATIONEN U INS CAT U INS CAT 1 2 BEMERKUNGEN Bewahren Sie das Handbuch...

Page 45: ...etzteil mit falscher Spannung und Frequenz kann das Ger t besch digen und ein Brand verursachen Die Spannung muss stabil sein es d rfen keine gro en Schwankungen auftreten Schlie en Sie die Klimaanlag...

Page 46: ...ung desGer tsentspricht unddieVersorgungsspannungswerte m ssen den f r die jeweiligen Maschinen angegebenen Werten entsprechen Alle Maschinen m ssen gem den in den verschiedenen L ndern geltenden Vors...

Page 47: ...mmeln Sie das K ltemittelgas 3 Stellen Sie das Vakuum her 4 Reinigen Sie die Rohrleitungen mit Stickstoff 5 Schneiden oder schwei en Der Schwei vorgang muss von qualifiziertem Personal durchgef hrt we...

Page 48: ...Compressor Compresseur Marca Panasonic Panasonic Refrigerante Refrigerant R frig rant Tipo Type Typologie R32 R32 Carica refrig standard Gaz Refrigerant Kg 0 75 1 00 Carica aggiuntiva oltre la precari...

Page 49: ...nsumption in Stand by Consommation en Stand by W 0 5 0 5 0 5 Pressione sonora Sound level Pression sonore dB A 46 63 63 Potenza sonora Sound power Puissance sonore dB A 57 73 73 Metodo di regolazione...

Page 50: ...the unit 1TFA NA SUV3 H24 1TFA NA 672 430 700 456 312 532 10 mension of the unit 1TFA NA SUV3 H24 1TFA NA 672 430 312 532 552 289 335 2 BESCHREIBUNG Das tats chliche Produkt kann abweichen beziehen Si...

Page 51: ...Verwendung von Federschwingungsd mpfern f r die Installation mit Wandschiene Das Ger t muss von der Frontseite her inspizierbar sein daher Das Ger t muss von der Frontseite her inspizierbar sein daher...

Page 52: ...erforderlich sein eine Zusatzsteckdose zu verwenden Wenden Sie sich an den technischen Kundendienst von Tekno Point um weitere Informationen zu erhalten LUFTEINLASS AUSSENWAND AUSSENWAND Hilfssaugstut...

Page 53: ...ngen werden an der rechten Ger teseite angeschlossen Bei den Anschl ssen f r die K hlleitungen handelt es sich um Flare Anschl sse Das Innenger t muss an den Verfl ssigersatz mit Flare Anschl ssen mit...

Page 54: ...nung und bringen Sie die Leitungsenden mit den Anschl ssen der Ger te in bereinstimmung die Leitungen werden auf der Baustelle eingerichtet bevor sie ber die ffnung gef hrt werden die Enden mit Klebeb...

Page 55: ...nnen Verwenden Sie W rmeisolierband um die Leitungen von der Unterseite des Au enger ts bis zum oberen Ende der Leitung an der Stelle des Wandeintritts zu umh llen Beim Anbringen des Isolierbands muss...

Page 56: ...die rote Hochdruckleitung die von dem roten Absperrschieber mit der Aufschrift HIGH gesperrt wird Der andere nicht angeschlossene Anschluss des Messger ts muss geschlossen bleiben Unterbrechen Sie di...

Page 57: ...umgrad nicht was darauf hinweist dass im K hlkreis keine Verluste vorliegen Die Vakuumpumpe wieder einschalten Den Absperrschieber VAC ffnen Den Vorgang der Vakuumbeaufschlagung noch einige Minuten la...

Page 58: ...e korrekte Funktionsweise pr fen Die Versorgungsspannung des Verfl ssigersatzes muss einen Wert von 10 des auf dem Typenschild der Herstellungsdaten aufweisen Ist dies nicht der Fall wenden Sie sich a...

Page 59: ...tschutz E4 Hochdruckschutz E5 Niederdruckschutz des Systems E6 K ltemittelverlustschutz Ventilsperrenschutz E7 4 Wege Funktionsst rungsschutz E8 Anormale Eingangs Ausgangslufttemperatur H0 Schutz f r...

Page 60: ...in AG gemeldet L7 Kommunikationsfehler zwischen IG und Steuerung ber Draht L8 Pumpenfehler Kondensatablauf L9 Schutz gegen Wasser berlauf P0 Funktionsst rung EEPROM Au enger t P1 Kreislaufbef llungsfe...

Page 61: ...auf den Energieverbrauch ausschlaggebend Der vom Kundendienstzentrum j hrlich einzuhaltende Wartungsplan sieht die folgenden Eingriffe und Kontrollen vor Regelm ige Reinigung des Wasserfilters an der...

Page 62: ...o teknopoint com assistenza teknopoint com Uniquement de cette mani res il nous es possible de garantir une correcte gestion et v rification des param tres de garantie en tablissant donc si l unit est...

Page 63: ......

Page 64: ......

Page 65: ......

Page 66: ...e riscaldamento e ventilazione Con l obbiettivo di offrire comfort e qualit della vita per tutti i tipi di ambienti TEKNO POINT sviluppa soluzioni innovative di climatizzazione applicabili ad edifici...

Reviews: