Mounting and Connection 

1.

 

Remove the head of the flasher from the base. 

2.

 

Mount the base part on the wall, using 2 of the 4 markings marked on the base.  

 

 

3.

 

Connect the cable according to the following diagram. Connect terminal 4 

+

 and terminal 1 

“–“

, connect 

to the next detector with number 1 

-

, number 4 

+

 .  

 

 

4.

 

Replace the flasher. Make sure that the line on the head meets the long line on the base.  

5.

 

Turn the flasher clockwise to the base, making sure that the terminals are tight.

   

Test 

1.

 

TFS-119X sirens and flashers are tested in the menu TFP-12XX Analogue Addressable Fire Alarm panels. 

2.

 

Check if flasher error occurs when panel is operated. 

3.

 

If flasher error, make sure the connections are made correctly. 

4.

 

If no flasher error, move the panel to the test position from the menus. 

5.

 

Run the flasher test. Observe the flasher side / flash status during the test period.  

6.

 

If the devices continuous warning lights are flashing during the test, the test is completed. 

 

 

Supported Flasher Modes and 
Descriptions

 

 
 

 
 

 

1922

 

Bilgi Elektronik San. ve Tic. A.Ş.

 

Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi

 

No:1 Kat:2 No:32 Ümraniye / İstanbul

 

20 

1922-CPR-1302

 

EN 54-23 

Fire alarm devices - Visual alarm device (VAD) 

intended for use in and around buildings

 

Duration of operation: Pass 
Provision for external conductors: Pass 
Flammability of materials: Pass 
Enclosure protection: Pass 
Access: Pass 
Manufacturer's adjustments: Pass 
On-site adjustment of behaviour: Pass 
Requirements for software controlled devices: Pass 
Coverage volume: Pass 
Variation of light output: Pass 
Minimum and maximum light intensity: Pass 
Light colour: Red / White 
Light temporal pattern / frequency of flashing: Pass /

 

1Hz %25Duty 

Marking and data: Pass 
Synchronization: Pass 

Durability: 

Temperature resistance: Pass 
Humidity resistance: Pass 
Shock and vibration resistance: Pass 
Corrosion resistance: Pass 
Electrical stability: Pass 

Technical data: see 

BİLGİ-TEC-200110-3 held by the manufacturer. 

 

Manufacture 

 

 

 

 

 

*

 2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste 

in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent 
new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info

 

Bilgi Elektronik San. ve Tic. A.Ş.

 

Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi

 

No:1 Kat:2 No:32 

Ümraniye / İstanbul

 

/ Türkiye

 

 

Telephone:

 +90 216 455 88 46 

Fax:

 +90 216 455 99 06 

www.bilgielektronik.com.tr 

[email protected]

 

[email protected]  

 

 

 

 

Summary of Contents for TFS-1193R

Page 1: ...a sırasında oluşan arızalar garanti kapsamı dışındadır İnsan ve Çevre Sağlığı Bu cihaz insan sağlığına zarar verecek herhangi bir kimyasal veya biyolojik madde içermez Alt Modeller TFS 1193R Adresli Yangın Alarm Flaşörü Kırmızı TFS 1193W Adresli Yangın Alarm Flaşörü Beyaz 13 6 2014 tarihli ve 29029 sayılı Resmî Gazete de yayımlanan Satış Sonrası Hizmetler Yönetmeliği eki listede tespit ve ilan edi...

Page 2: ... 1 Kat 2 No 32 Ümraniye İstanbul 20 1922 CPR 1302 EN 54 23 Binaların içinde ve etrafında kullanım amaçlı yangın alarm cihazları görüntülü alarm cihazı GAC Çalışma süresi Geçti Dış iletkenler için şart Geçti Malzemelerin yanabilirliği Geçti Mahfaza koruması Geçti Erişim Geçti Üreticinin ayarlamaları Geçti Yerinde davranış ayarı Geçti Yazılım kontrollü cihazlar için şartlar Geçti Kapsama hacmi Geçti...

Page 3: ...e technical interventions have to be done by technicians of company Device must be cleaned up with a dry fabric No chemicals are allowed for cleaning Transportation Device must be carefully transported avoiding all physical bump stroke and possible fluid entry Malfunctions that caused by improper transportation is not under warranty Human and Environmental Health This device contains no chemical o...

Page 4: ...ice VAD intended for use in and around buildings Duration of operation Pass Provision for external conductors Pass Flammability of materials Pass Enclosure protection Pass Access Pass Manufacturer s adjustments Pass On site adjustment of behaviour Pass Requirements for software controlled devices Pass Coverage volume Pass Variation of light output Pass Minimum and maximum light intensity Pass Ligh...

Reviews: