Mounting and Connection
1.
Remove the head of the detector by pulling it upwards (2) by turning it (1) up to the short line in the
direction of the counterclockwise direction as seen from the base.
2.
Mount the base using the 2 mounting locations shown.
3.
Make the cable connection according to the following diagram. Make a connection with pole 4 + pole and
pole 1 - by taking pole + number 3 from pole 3 of the next detector.
4.
Use the 3 (+) and 2 (-) connections for the remote indicator.
5.
Replace the detector head. Make sure the line on the head matches the long line on the base
6.
Give the detector power from alarm panel. In the absence of an alarm, the LED on the detector indicates
that it is operating with a blue color for approximately 20 seconds.
Test
Heat Test:
For the detector test it is sufficient to provide air flow at a temperature of about
70 ° C.
1.
Open the hot air flow and check the temperature.
2.
Hold the hot air into the detector. The detector should give an alarm within 30 seconds.
3.
Check that the red LEDs are lit continuously. Reset the detector on the panel.
4.
System can be activated after test
Manufacture
* 2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper recycling, return this product to your local supplier upon
the purchase of equivalent new equipment, or dispose of it at designated collection points. For more
information see: www.recyclethis.info.
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul
/ Türkiye
Telephone:
+90 216 455 88 46
Fax:
+90 216 455 99 06