Mounting and Connection 

1.

 

Remove the head of the detector by pulling it upwards (2) by turning it (1) up to the short line in the 

direction of the counterclockwise direction as seen from the base. 

2.

 

Mount the base using the 2 mounting locations shown.  

 

 

 

 

 

3.

 

Make the cable connection according to the following diagram. Make a connection with pole 4 + pole and 
pole 1 - by taking pole + number 3 from pole 3 of the next detector. 

4.

 

Use the 3 (+) and 2 (-) connections for the remote indicator. 

5.

 

Replace the detector head. Make sure the line on the head matches the long line on the base  

6.

 

Give the detector power from alarm panel. In the absence of an alarm, the LED on the detector indicates 
that it is operating with a blue color for approximately 20 seconds.  

 

 

 

 

 

 

 

 

 

Test 

Heat Test: 

For the detector test it is sufficient to provide air flow at a temperature of about 

70 ° C.

 

1.

 

Open the hot air flow and check the temperature.  

2.

 

Hold the hot air into the detector. The detector should give an alarm within 30 seconds. 

3.

 

Check that the red LEDs are lit continuously. Reset the detector on the panel.  

4.

 

System can be activated after test 

 
 

 

 
 

 
 

 

Manufacture 

 

 

 

 

 

*  2012/19/EU  (WEEE  directive):  Products  marked  with  this  symbol  cannot  be  disposed  of  as  unsorted 

municipal waste in the European Union. For proper recycling, return this product to your local supplier upon 
the  purchase  of  equivalent  new  equipment,  or  dispose  of  it  at  designated  collection  points.  For  more 

information see: www.recyclethis.info. 
 

Bilgi Elektronik San. ve Tic. A.Ş.

 

Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi

 

No:1 Kat:2 No:32 Ümraniye / İstanbul

 

/ Türkiye

 

 

Telephone:

 +90 216 455 88 46 

Fax: 

+90 216 455 99 06 

Sales: 

[email protected]

   

Technical Support: 

[email protected]

 

 

 

 

 

 

 

 

Reviews: