Indicator LEDs

 

 

 

Blue LED 

Red LED 

Yellow LED 

Any error situation  

(Pollution etc..) 

Blinks with 1 sec. intervals 

The device is in normal 

operation mode 
(can be turned off.) 

Blinks with 20 sec. intervals 

Alarm state 

Constant 

Short circuit state 

Constant 

 

 
Terminals

 

 

No. 1 

NEG.(-) supply input  

No. 2 

NEG.(-) supply output, NEG. (-) input of parallel notification light 

No. 3 

POS. (+) input of parallel notification light 

No. 4 

POS.(+) supply input, POS.(+) supply output 

No. 5 

Earth connection 

 

 
 

 
 

 
 

 

 
 

Installation and Connection 

1.

 

Turn (1) the detector head counterclockwise to the short line and pull (2) it up to disassemble from the 

base. 

2.

 

Mount the base part by using the mounting place shown (2).  

 

 

 

3.

 

Make the cable connections according to the following diagram. Make the connection by observing that 
the polarity of Leg No. 4 is (+) and Leg No. 1 is (

), and then by connecting (-) pole from No 2 and (+) 

pole from No. 4 of the current detector to No.1 of the next detector. 
  

4.

 

Use the connections No. 3(+) and 2(-) for the parallel notification light. 

5.

 

Install the detector head into its place. Make sure that the line on the head piece is aligned with the long 
line on the base.  

6.

 

Energize the detector. The LED on the detector will blink blue light once in every 20 seconds in the state 
without an alarm in order to indicate that the device is in operation. (This feature may be turned off from 

the panel) 

7.

 

Make the chasis(earth) connection of the cable continuously over the Leg No. 5 between the loop output 

and the last detector. 

 
 

 
 

 
 

 
 

 
 

 
 

 
 
 

 
 

 
 

 
 

 
 

Test 

Observable smoke flow must be provided in order to obtain correct results.  

In order to perform a smoke test, ensure that the smoke goes into the smoke detection chamber min. for 1 

minute by using a burning material or test spray. The LED lights and indicates the alarm when sufficient 
amount of smoke enters into the chamber. 

 
1.

 

Fend of the smoke source when the device goes into the alarm state.  

2.

 

Check to see whether the red LED’s light continuously

. Reset the detector from the panel. 

3.

 

The detector must be sent to the service if it does not produce alarm within 1 minute. 

4.

 

The system may be activated after the test is performed. 

 
 

 
 

 
 

 
 

 
 

 
 

Warning:

 The product operates only with Teknim TFP-121x, TFP-122x and TFP-123x Intelligent Addressable 

Fire Alarm panels. 

A: Head 

B: LED’s

 

C: Base 

Loop Connection 

Connector 

Parallel Notification Light 

(TFA-1196) 