TFB-3165
Conventional Manual Call Point, Resettable
Installation and User Manual
Issue Date: 06/10/2017 Rev:03
IMPORTANT WARNINGS
GENERAL
✓
Before using the device read this manual carefully. Keep it
just in case of necessity.
✓
Abide all the rules and precautions stated in the manual.
Follow all the instructions one by one.
✓
Keep the devices away from water and moisture.
CONDITIONS
Do not energize the device above or below the given limits of
extreme hot or cold conditions.
Temperature:
-10
C ile +60
C a
rası
Relative Moisture:
+40°C’de
≤
93%
SERVICE
Do not try to fix the device on your own. Removal of cover
may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer
or with authorized service. All the technical interventions
have to be done by technicians of company.
MALFUNCTIONS THAT REQUIRE TECHNICAL SERVICE
In case of any malfunction or below conditions contact with
your authorized service,
✓
When Mains cable or the plug is harmed,
✓
Contact of device with a fluid,
✓
Exposure of rain and water,
✓
Fell down of device or harmed outer cover,
✓
Serious performance fall on the device,
✓
Depending on the instructions stated in manual, if your
device not working properly, further usage or possible wrong
usage may cause other malfunctions. Contact with your
authorized service in such terms.
MAINTENANCE ON YOUR OWN
Do not try to fix the device on your own. Removal of cover
may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer
or with authorized service. All the technical interventions
have to be done by technicians of company. Device must be
cleaned up with a dry fabric. No-chemicals are allowed for
cleaning
TRANSPORTATION
Device must be carefully transported avoiding all physical
bump, stroke and possible fluid entry. Malfunctions that
caused by improper transportation is not under warranty.
HUMAN AND NATURE CONDITION
This device contains no chemical or biological elements that
could harm human condition
CE
1922
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul / Türkiye
17
1922-CPD-0849
EN 54-11:2001, EN 54-11:2001/A1:2005
Manual call points
TFB-3165
Technical data: See
BİLGİ-TEC-170425 held by the
manufacturer.
MOUNTING AND CONNECTION
1. Mount the wall of the manual call base so that the fire
cords pass through the rear hole. Do not tighten the wall
mounting screws too much.
2. There is an internal 470-ohm resistor between the C and
R connectors in the manual call point. You do not need to
connect an additional 470 ohms for the connection.
Connect the + (plus) cable from the Conventional Fire
Alarm panel to the R connector, and the - (minus) cable
to the C connector.
If your conventional alarm panel is different from the fire
alarm resistance of 470 ohms, connect the C terminal to
the negative (-) cable and the NO terminal to the + cable
with the required fire alarm resistance.
If you need to use NO or NC on another system, you can
connect a 2-wire cable to terminal C and the other to the
NO or NC terminal you want to use.
3. At the end of the line, connect the end of line resistance
according to the brand and model of the Conventional
Fire Alarm Panel which you are using