TFB-3165 

Conventional Manual Call Point, Resettable

 

Installation and User Manual 

Issue Date: 06/10/2017 Rev:03 

IMPORTANT WARNINGS 

GENERAL 

Before using the device read this manual carefully. Keep it 

just in case of necessity. 

Abide  all  the  rules  and  precautions  stated  in  the  manual. 

Follow all the instructions one by one. 

Keep the devices away from water and moisture. 

  CONDITIONS 

Do not energize the device above or below the given limits of 
extreme hot or cold conditions. 

Temperature: 

-10

C ile +60

C a

rası 

Relative Moisture: 

+40°C’de  

 

93%  

SERVICE 

Do  not  try  to  fix  the  device  on  your  own.  Removal  of  cover 
may end up with electricity shock. 

In case of any defect or malfunction, contact with your dealer 
or  with  authorized  service.  All  the  technical  interventions 
have to be done by technicians of company. 

MALFUNCTIONS THAT REQUIRE TECHNICAL SERVICE  

In case of any malfunction or below conditions contact with 
your authorized service,  

✓

When Mains cable or the plug is harmed,  

✓

Contact of device with a fluid,  

✓

Exposure of rain and water,  

✓

Fell down of device or harmed outer cover,  

✓

Serious performance fall on the device,  

✓

Depending on the instructions stated in manual, if your 

device not working properly, further usage or possible wrong 
usage may cause other malfunctions. Contact with your 
authorized service in such terms.  

MAINTENANCE ON YOUR OWN   

Do  not  try  to  fix  the  device  on  your  own.  Removal  of  cover 
may end up with electricity shock. 

In case of any defect or malfunction, contact with your dealer 
or  with  authorized  service.  All  the  technical  interventions 
have to be done by technicians of company. Device must be 
cleaned  up  with  a  dry  fabric.  No-chemicals  are  allowed  for 
cleaning 

TRANSPORTATION 

Device  must  be  carefully  transported  avoiding  all  physical 
bump,  stroke  and  possible  fluid  entry.  Malfunctions  that 
caused by improper transportation is not under warranty. 

 HUMAN AND NATURE CONDITION  

This device contains no chemical or biological elements that 
could harm human condition 

  

 

 

 

 

CE 

 

1922 

Bilgi Elektronik San. ve Tic. A.Ş. 

Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi 

No:1 Kat:2 No:32 Ümraniye / İstanbul / Türkiye 

17 

1922-CPD-0849 

EN 54-11:2001, EN 54-11:2001/A1:2005 

Manual call points 

TFB-3165 

Technical data: See 

BİLGİ-TEC-170425 held by the 

manufacturer. 

MOUNTING AND CONNECTION 

1.  Mount  the  wall  of  the  manual  call  base  so  that  the  fire 

cords pass through the rear hole. Do not tighten the wall 
mounting screws too much. 

 

 

2.  There is an internal 470-ohm resistor between the C and 

R connectors in the manual call point. You do not need to 
connect  an  additional  470  ohms  for  the  connection. 
Connect  the  +  (plus)  cable  from  the  Conventional  Fire 
Alarm  panel  to  the  R  connector,  and the  -  (minus)  cable 
to the C connector. 

 

If your conventional alarm panel is different from the fire 
alarm resistance of 470 ohms, connect the C terminal to 
the negative (-) cable and the NO terminal to the + cable 
with the required fire alarm resistance. 
 
If you need to use NO or NC on another system, you can 
connect a 2-wire cable to terminal C and the other to the 
NO or NC terminal you want to use. 

 

 
3.  At the end of the line, connect the end of line resistance 

according  to  the  brand  and  model  of  the  Conventional 
Fire Alarm Panel which you are using 